{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E65004M5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E65004M5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E65004M5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E65004M5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, LC1E65004M5WBIN, 4-pole NO, 85 A AC-1 rated operational current, 220 V AC 50 Hz coil, IP20.","salesMarkdown":"Its 85 A rated operational current (at ≤415 V AC, <40 °C) makes it a fit for heater banks, lighting circuits, or other non-inductive loads where the current is steady and inrush is low. The coil is 220 V AC at 50 Hz, wide-range control circuit type, with a 160 VA inrush at 20 °C and 6–10 W heat dissipation in steady state. Drop-out voltage is 0.3–0.6 Uc, operational pick-up is 0.7–1.25 Uc across the -5 to 55 °C range. Mounts on DIN rail or a plate, with screw-clamp terminals on both power and control circuits. Power terminals accept 2.5–25 mm² flexible with cable end, control terminals 1–4 mm². Tightening torque is 5 N.m on the power side, 1.2 N.m on control. The 85 A AC-1 rating is the continuous resistive current the contactor can carry without exceeding its thermal limits. For motor loads (AC-3 duty), you would need to derate — this part is not specified for AC-3, so it is best kept on resistive or lightly inductive circuits where the switching arc is less severe. The rated breaking capacity is 520 A at 440 V, and the making capacity is 650 A at 440 V AC — both per IEC 60947, confirming it can close into and interrupt fault currents within its rating. Mechanical durability is 5 million cycles; electrical durability is 350,000 cycles at AC-1. Maximum operating rate is 1200 cycles per hour at 60 °C. The associated fuse recommendation is 125 A gG at ≤690 V, coordination type 1. IP20 protection keeps fingers out but does not seal against dust or moisture — install inside a panel. For BOM freeze or long-term planning, the IEC 60947 compliance and multiple national standards (GB/T 14048 series) mean the part is accepted across European and Chinese regulatory frameworks. No successor or replacement part is flagged — the current code is the active variant. Dimensions are 127 mm height, 85 mm width, 125 mm depth — a compact 4-pole footprint that fits standard DIN-rail enclosures. The contactor has no auxiliary contact block fitted (auxiliary contact composition: without), so if you need feedback or interlocking, add a side-mount auxiliary block separately. Operating time is 20–26 ms on closing, 8–12 ms on opening. The 4 NO pole composition means all four poles are normally open — no NC poles in the base unit. For applications requiring a normally closed path, you will need an external auxiliary contact. Average impedance is 1 mΩ at Ith 85 A, 50 Hz for the power circuit, with power dissipation per pole at 6.4 W AC-1. Total heat load in the enclosure is roughly 25.6 W from the poles plus 6–10 W from the coil — account for this in thermal design.","metaTitle":"Schneider Electric LC1E65004M5WBIN Easy TeSys Contactor, 85","metaDescription":"Schneider Electric LC1E65004M5WBIN Easy TeSys Control contactor, 85 A rated operational current at ≤415 V AC AC-1, 4 NO poles, 220 V AC 50 Hz coil, IP20. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"125 mm","Range":"Easy TeSys","Width":"85 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"20...26 ms on closing 8...12 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"6...10 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"1 mOhm - Ith 85 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 5 N.m","Inrush power in VA":"160 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"5000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","Associated fuse rating":"125 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1200 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 2.5...25 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 2.5...10 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 2.5...25 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 2.5...16 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"520 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Product or component type":"Contactor","Irms rated making capacity":"650 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"6.4 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"85 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"15 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"520 A 40 °C - 10 s for power circuit 260 A 40 °C - 60 s for power circuit 110 A 40 °C - 600 s for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E65004M5WBIN/easy-tesys-contactor-4p2no-+-2nc-60a-ac1-up-to-415v-coil-415v-ac-50-60hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E65004M5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"The LC1E65004M5WBIN is rated 85 A AC-1 at ≤415 V AC for resistive loads, with a 220 V AC 50 Hz coil. It has 4 NO poles, IP20 protection, and mounts on DIN rail or plate. Rated insulation voltage is 690 V."},{"question":"What compliance standards does this contactor meet?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T 14048 series. Fire resistance is 850 °C per IEC 60695-2-1. Protective treatment is TH conforming to IEC 60068 for tropical environments."},{"question":"What is the difference between this Easy TeSys contactor and a standard TeSys D contactor?","answer":"The Easy TeSys Control range is a streamlined, cost-optimised line for basic resistive and low-duty switching. Compared to the full TeSys D series, it typically has fewer auxiliary options, no AC-3 motor ratings, and a simpler accessory ecosystem. The LC1E65004M5WBIN is best for heater or lighting panels where AC-1 is the primary duty — not for motor starting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E65004M5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E65004M5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}