{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E65004N5WB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E65004N5WB","canonicalUrl":"https://aoctrl.com/schneider/LC1E65004N5WB","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E65004N5WB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control LC1E65004N5WB, 4-pole contactor, 80 A AC-1 at ≤440 V, 415 V 50 Hz AC control, screw clamp terminals, plate/DIN rail mount.","salesMarkdown":"The contactor is built to EN/IEC 60947-4-1 and GB/T 14048.4 standards, so it meets the common panel and machine-build compliance requirements across Europe and China. The 80 A AC-1 rating is the thermal current (Ith) for resistive loads — think heater banks, lighting, or transformer primaries. For motor loads you would need the AC-3 rating, which is not listed here; this part is specified for resistive duty. The 415 V 50 Hz control coil is a wide-range AC type, with operational limits of 0.7 to 1.25 Uc and drop-out at 0.3 to 0.6 Uc, so it holds in on a stiff supply but drops cleanly on undervoltage. The 4 NO pole configuration means all four poles are normally open, which is the standard for line-side switching. Mechanical durability is 5 million cycles, and electrical durability is 350,000 cycles under AC-1 duty. That puts it in the range for frequent switching in process control or HVAC cycling. The maximum operating rate is 1200 cycles per hour at 60 °C, so it can keep pace with a fast-cycling line. The dimensions are 127 mm high, 85 mm wide, and 125 mm deep, so it occupies a standard contactor footprint. Power circuit terminals accept 2.5 to 25 mm² solid or flexible wire with cable ends; control circuit terminals take 1 to 4 mm². Tightening torque is 5 N·m on the power side and 1.2 N·m on the control side — a torque driver is needed for the power connections. The IP2X finger protection means it is safe for open-panel use but not washdown-rated. It also meets IEC 60695-2-1 for glow-wire fire resistance at 850 °C and has TH protective treatment per IEC 60068-2-30 for humid environments. These cover the typical compliance documentation a quality or controls engineer would need for a panel build or machine certification.","metaTitle":"Schneider Electric LC1E65004N5WB Easy TeSys Contactor, 80 A","metaDescription":"Schneider Electric LC1E65004N5WB Easy TeSys contactor, 80 A rated operational current at ≤440 V AC-1, 415 V 50 Hz control. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"125 mm","Range":"Easy TeSys","Width":"85 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"20...26 ms on closing 8...12 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"6...10 W for control circuit","Mounting support":"Plate DIN rail","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"1 mOhm - Ith 80 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 5 N.m","Inrush power in VA":"160 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"5000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","Associated fuse rating":"125 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1200 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 2.5...25 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 2.5...10 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 2.5...25 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 2.5...16 mm² - cable stiffness: solid","IP degree of protection":"IP2X conforming to IEC 60529","Rated breaking capacity":"520 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Product or component type":"Contactor","Irms rated making capacity":"650 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"6.4 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"80 A (at <55 °C) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"15 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"520 A 40 °C - 10 s for power circuit 260 A 40 °C - 60 s for power circuit 110 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"80 A (at 55 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/80baac62e923cd352f25d5f00d25ec56.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E65004N5WB/contactoreasy-tesys-controllc1e4p4noac1-80a415v50hz-wide-range/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E65004N5WB/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"Rated operational current is 80 A at ≤440 V AC in AC-1 duty. Control circuit voltage is 415 V AC 50 Hz. Mechanical durability is 5 million cycles, electrical durability 350,000 cycles under AC-1."},{"question":"What compliance standards does it meet?","answer":"It complies with EN/IEC 60947-1, -4-1, -5-1, GB/T 14048.1, -4, -5, and IEC 60695-2-1 for glow-wire at 850 °C. It also has TH protective treatment for humid environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E65004N5WB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E65004N5WB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}