{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E65F5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E65F5","canonicalUrl":"https://aoctrl.com/schneider/LC1E65F5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E65F5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E65F5, 3P contactor, 65 A AC-3 at ≤440 V, 110 V AC coil 50 Hz, DIN rail/plate mount.","salesMarkdown":"The Schneider Electric LC1E65F5 is an Easy TeSys Control contactor, three-pole (3P, all NO), rated 65 A in AC-3 utilisation category at ≤440 V. AC-3 is the standard duty for starting and stopping squirrel-cage induction motors — that 65 A figure is what governs motor sizing, not the higher AC-1 resistive rating. The coil pulls 110 V AC at 50 Hz; verify your control transformer matches that frequency before wiring. It also carries AC-3e (enhanced motor starting) and AC-1 (resistive load) categories, so it handles heater banks or lighting as well, but the AC-3 number is the one that decides fit for a motor branch circuit. Depth is 114 mm, which matters when you're squeezing it into a shallow enclosure alongside a starter or overload relay. Also listed for EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ, which covers glow-wire and flammability in appliance applications — useful if this contactor ends up in an HVAC or refrigeration panel. Operates from -5 °C to 55 °C ambient, stores from -60 °C to 80 °C. TH protective treatment per IEC 60068-2-30 means it handles humidity cycling (pollution degree 3) — fine for unheated electrical rooms in temperate climates. Derating starts above 3000 m altitude. ## Switching timing and mechanical robustness That's the window where both sets are open — critical if you're using the NC as a feedback mirror in a safety circuit; you need that gap to avoid a race condition in the PLC scan. Vibration tested to 1.5 Gn (open) and 3 Gn (closed) across 5–300 Hz; shock rated at 6 Gn open, 7 Gn closed. That's standard for industrial panel mounting — no special isolation required unless you're bolting it directly to a vibrating machine base.","metaTitle":"Schneider LC1E65F5 Easy TeSys Contactor, 65A AC-3, 110V AC C","metaDescription":"Schneider Electric LC1E65F5 Easy TeSys Control contactor, 3P, 65A AC-3 at ≤440V, 110V AC 50Hz coil. Active production. DIN rail or plate mount. EN/IEC 60947 certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"114 mm","Range":"Easy TeSys","Width":"75 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$86.64","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/162aa8eeefe9ea3c191477fa2c293760.pdf","sourceUrl":"https://www.se.com/id/en/product/LC1E65F5/contactoreasy-tesys-controllc1e3p3noac3440v65a110v-ac-coil50hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E65F5/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The headline rating is 65 A in AC-3 duty at ≤440 V — that's the motor-switching current. The coil is 110 V AC, 50 Hz. Mounts on DIN rail or plate, dimensions 75 mm wide × 127 mm tall × 114 mm deep."},{"question":"What standards does the LC1E65F5 comply with?","answer":"It is certified to EN/IEC 60947-1, -4-1, and -5-1, plus the Chinese GB/T equivalents. It also meets EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ for appliance applications. Fire resistance is 850 °C per IEC 60695-2-1."},{"question":"Can I use this contactor for resistive loads like heaters?","answer":"Yes, it carries an AC-1 utilisation category for resistive loads. The AC-3 65 A rating is for motor starting; the AC-1 rating will be higher, so for a resistive bank the part is conservatively rated."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E65F5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E65F5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}