{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E65Q5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E65Q5","canonicalUrl":"https://aoctrl.com/schneider/LC1E65Q5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E65Q5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control LC1E65Q5, 3-pole contactor, AC-3 65A ≤440V, 380V AC 50Hz coil, plate/DIN rail mount.","salesMarkdown":"The Schneider Electric LC1E65Q5 is a 3-pole contactor from the Easy TeSys Control range, rated for AC-3 motor switching at 65 A up to 440 V, with a 380 V AC 50 Hz coil. The 65 A AC-3 rating governs motor sizing, not the higher AC-1 resistive rating. Mounts on plate or DIN rail, 75 mm width, 114 mm depth. IP2X finger protection. Rated for operation at -5 to 55 °C ambient, with storage down to -60 °C and up to 80 °C. No derating required up to 3000 m altitude, so it is suitable for high-altitude sites like mining or mountain-top installations without recalculating the thermal budget. Compliance documentation covers EN/IEC 60947-1, -4-1, and -5-1, plus the Chinese GB/T equivalents, and the glow-wire test at 850 °C per IEC 60695-2-1 for fire resistance. This satisfies most panel builder certification requirements for CE, UKCA, and CCC markets. AC-3 motor switching: 65 A at ≤440 V. AC-1 resistive load: higher, but the AC-3 figure is the one that drives motor sizing. Coil: 380 V AC 50 Hz. Mechanical robustness: 3 Gn vibration closed, 7 Gn shock closed — adequate for most industrial environments including conveyors and pumps.","metaTitle":"Schneider LC1E65Q5 Easy TeSys Contactor, 65A AC-3, 380VAC Co","metaDescription":"Obsolete LC1E65Q5 contactor from Schneider Easy TeSys Control series. 65A AC-3 rated, 380VAC 50Hz coil, 3P. Sourced to order against RFQ. Factory-fresh, fully traceable stock.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"114 mm","Range":"Easy TeSys","Width":"75 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2dd5153b6f08d08f6a824c273593e152.pdf","sourceUrl":"https://www.se.com/th/en/product/LC1E65Q5/contactoreasy-tesys-controllc1e3p3noac3440v65a380v-ac-coil50hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E65Q5/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the LC1E65Q5?","answer":"AC-3 motor rating: 65 A at ≤440 V. Coil: 380 V AC 50 Hz. 3-pole configuration. Mounts on plate or DIN rail. Operating temperature: -5 to 55 °C. No derating up to 3000 m altitude."},{"question":"What compliance standards does the LC1E65Q5 meet?","answer":"It complies with EN/IEC 60947-1, -4-1, and -5-1, plus GB/T 14048.1.4, and.5. Fire resistance tested at 850 °C per IEC 60695-2-1. TH treatment for pollution degree 3 environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E65Q5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E65Q5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}