{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E65Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E65Q6","canonicalUrl":"https://aoctrl.com/schneider/LC1E65Q6","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E65Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, contactor, LC1E65Q6, 3P(3NO), AC-3/AC-3e ≤440V 65A, 380V AC coil 60Hz.","salesMarkdown":"The 65 A AC-3 figure governs how large an induction motor it can start and stop under load; for purely resistive loads (AC-1) the contactor can carry a higher current. ## Lifecycle reality and sourcing This part is marked obsolete by the manufacturer. There is no official successor order code listed, meaning a direct drop-in replacement from Schneider is not documented. For a line-down situation or a BOM freeze, the only sourcing channel is the surplus and broker market — quoted strictly to order against an RFQ. Do not plan a new design around this order code; the risk of supply drying up is real. Mounts on DIN rail or a plate, with dimensions of 75 mm wide by 127 mm tall by 114 mm deep. IP2X protection means it is finger-safe but not sealed against dust or moisture; keep it inside a rated enclosure. The operating altitude is 3000 m without derating — useful for high-altitude installations where air insulation degrades. ## What to watch for The non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation. That is a deliberate break-before-make delay to prevent simultaneous closure — critical if you are using the NC contact for a safety interlock or a mechanical brake. The mechanical robustness figures (3 Gn vibration closed, 7 Gn shock closed) are typical for a contactor this size, but the open-contact vibration limit of 1.5 Gn means a high-vibration environment could cause nuisance chatter if the contactor is not energised.","metaTitle":"Schneider LC1E65Q6 Easy TeSys Contactor, 65A AC-3, 380V 60Hz","metaDescription":"Obsolete Schneider LC1E65Q6 Easy TeSys Control contactor. 3P(3NO), AC-3/AC-3e ≤440V 65A, 380V AC 60Hz coil. Sourced to order against RFQ. Standards: EN/IEC 60947.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"114 mm","Range":"Easy TeSys","Width":"75 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aa68711c50abc9d5d8f50e42a3f63afa.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E65Q6/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v65a380v-ac-coil60hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E65Q6/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings for the LC1E65Q6?","answer":"It is a 65 A contactor in AC-3 duty (motor switching) at up to 440 V, with a 380 V AC 60 Hz coil. It also carries AC-3e and AC-1 utilisation categories."},{"question":"What is the mounting and dimension footprint of the LC1E65Q6?","answer":"It mounts on DIN rail or a plate. Dimensions are 75 mm wide, 127 mm tall, and 114 mm deep. The 114 mm depth is the critical dimension for enclosure clearance."},{"question":"What compliance standards does the LC1E65Q6 meet?","answer":"It meets EN/IEC 60947-1, -4-1, and -5-1, plus GB/T equivalents. It also passes a 850 °C glow-wire test and is rated for pollution degree 3 environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E65Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E65Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}