{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E80004M5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E80004M5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E80004M5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E80004M5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control LC1E80004M5WBIN, 4-pole contactor, 110 A AC-1, 4 NO, 220 V AC 50 Hz coil, screw clamp terminals.","salesMarkdown":"It carries a rated operational current of 110 A at up to 415 V AC, with 4 normally open main poles and a 220 V AC 50 Hz control coil. No auxiliary contacts are fitted on this variant. Rated insulation voltage is 690 V, and the contactor can make 800 A and break 640 A at 440 V — figures that confirm it handles inrush and fault clearing within its AC-1 envelope. The control coil draws 200 VA inrush at 50 Hz and dissipates 6 to 10 W in steady state, which matters for transformer sizing in the panel. Power terminals accept 4 to 50 mm² solid or flexible with cable end; control terminals take 1 to 4 mm². Tighten power connections to 12 N·m and control wires to 1.2 N·m — that torque on the screw clamp terminals keeps the joint stable under load cycling. Compliant with EN/IEC 60947-1, 60947-4-1, and 60947-5-1, plus the Chinese GB/T equivalents. Protective treatment TH per IEC 60068 for tropical environments. ## Durability and operating conditions Rated for 350,000 electrical cycles in AC-1 and 3,000,000 mechanical cycles. Maximum operating rate is 1,200 cycles per hour at 60 °C. Withstands vibration up to 3 Gn when closed and shocks up to 7 Gn — figures that matter if the panel is mounted on a machine frame. Operating altitude goes to 3,000 m without derating.","metaTitle":"Schneider LC1E80004M5WBIN Easy TeSys Contactor, 110 A AC-1,","metaDescription":"Schneider Electric Easy TeSys LC1E80004M5WBIN 4-pole contactor. 110 A rated operational current AC-1, 4 NO main poles, 220 VAC 50 Hz coil. Active production. Sourced to order again","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"120 mm","Range":"Easy TeSys","Width":"95 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"6...20 ms on opening 20...35 ms on closing","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"6...10 W for control circuit","Mounting support":"Plate DIN rail","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"0.8 mOhm - Ith 110 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 12 N.m","Inrush power in VA":"200 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"3000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","Associated fuse rating":"160 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1200 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 4...16 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 4...50 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"640 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Product or component type":"Contactor","Irms rated making capacity":"800 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"9.7 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"110 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"20 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"640 A 40 °C - 10 s for power circuit 320 A 40 °C - 60 s for power circuit 135 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"110 A (at 40 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E80004M5WBIN/easy-tesys-contactor-4p2-no-+-2-nc-ac1-415-v-60a-415-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E80004M5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Schneider provide for this part?","answer":"The contactor is certified to EN/IEC 60947-1, 60947-4-1, and 60947-5-1, plus the Chinese GB/T equivalents. It carries protective treatment TH per IEC 60068 for tropical environments and fire resistance to 850 °C per IEC 60695-2-1. Schneider typically provides a declaration of conformity covering these standards with the shipment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E80004M5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E80004M5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}