{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E80004N5WB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E80004N5WB","canonicalUrl":"https://aoctrl.com/schneider/LC1E80004N5WB","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E80004N5WB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control LC1E80004N5WB, 4-pole contactor, 100 A AC-1 at ≤440 V, 415 V AC 50 Hz coil, DIN-rail or plate mount, IP20.","salesMarkdown":"## Integrator's quick-fit note The coil is 415 V AC 50 Hz wide-range, with a dropout threshold of 0.3–0.6 Uc and a pick-up range of 0.7–1.25 Uc across -5 to 55 °C — verify your control transformer secondary matches before wiring. Mounts on DIN rail or plate via screw-clamp terminals. Power-circuit terminals accept 4–50 mm² solid or flexible with cable end; control-circuit terminals take 1–4 mm². Tighten power terminals to 12 N·m, control terminals to 1.2 N·m. The IP20 finger-safe enclosure suits enclosed panel installation — not for washdown zones. AC-1 rating at 100 A means this contactor is sized for resistive loads where the current stays sinusoidal and the switching arc is modest — think electric heaters, ovens, or lamp banks. The 4-NO pole configuration gives four independent normally-open power poles, so you can switch three phases plus a neutral or split the load across separate circuits. Electrical durability is 350,000 cycles at AC-1; mechanical durability is 3 million cycles, so in a cycling application like a conveyor heater bank it will outlast most maintenance intervals. Associated fuse rating is 160 A gG at ≤690 V, coordination type 1 for the power circuit — meaning the contactor may need replacement after a fault, but the upstream fuse clears the short without damaging the panel wiring. Rated breaking capacity is 640 A at 440 V; rated making capacity is 800 A at 440 V, both per IEC 60947.","metaTitle":"Schneider Electric LC1E80004N5WB Easy TeSys Contactor, 100 A","metaDescription":"Schneider Electric LC1E80004N5WB Easy TeSys 4-pole contactor, 100 A AC-1 at ≤440 V, 415 V 50 Hz coil. Active production. DIN-rail or plate mount. IP20. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"120 mm","Range":"Easy TeSys","Width":"95 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"6...20 ms on opening 20...35 ms on closing","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"6...10 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"0.8 mOhm - Ith 100 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 12 N.m","Inrush power in VA":"200 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"3000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","Associated fuse rating":"160 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1200 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 4...16 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 4...50 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"640 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Product or component type":"Contactor","Irms rated making capacity":"800 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"9.7 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"100 A (at <55 °C) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"20 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"640 A 40 °C - 10 s for power circuit 320 A 40 °C - 60 s for power circuit 135 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"100 A (at 55 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a2d7912560aa94ca2db21832bcdb6952.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E80004N5WB/contactoreasy-tesys-controllc1e4p4noac1-100a415v50hz-wide-range/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E80004N5WB/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1E80004N5WB in the same family?","answer":"Within the Easy TeSys Control range, a direct peer would be a 4-pole contactor with the same coil voltage but a different current rating. The LC1E80004N5WB is specifically rated 100 A AC-1; a lower-current sibling (e.g., 80 A AC-1) or higher-current variant (e.g., 115 A AC-1) would differ in terminal size and thermal dissipation. Verify your load current before substituting."},{"question":"What is the depth of LC1E80004N5WB?","answer":"The depth is 120 mm. Combined with a width of 95 mm and height of 127 mm, it fits standard DIN-rail enclosures with adequate side clearance for wiring."},{"question":"What compliance documentation does this brand provide for LC1E80004N5WB?","answer":"The contactor is certified to EN/IEC 60947-1, -4-1, and -5-1, plus GB/T 14048.1, -4, and -5. Fire resistance is tested to 850 °C per IEC 60695-2-1. Protective treatment is TH conforming to IEC 60068 for tropical environments. RoHS and REACH declarations are standard for Schneider Electric's Easy TeSys line; request them with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E80004N5WB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E80004N5WB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}