{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E80008M5WB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E80008M5WB","canonicalUrl":"https://aoctrl.com/schneider/LC1E80008M5WB","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E80008M5WB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control LC1E80008M5WB, 4-pole contactor, 100 A AC-1 at ≤440 V, 220 V AC 50 Hz coil, DIN rail or plate mount.","salesMarkdown":"The Schneider Electric LC1E80008M5WB is a 4-pole contactor from the Easy TeSys Control range, rated for 100 A in AC-1 duty at ≤440 V — that's the resistive load curve, so it's sized for heaters, lighting banks, or other non-inductive circuits where inrush stays low. The 220 V AC 50 Hz coil pulls 200 VA inrush at 50 Hz, then settles to 6–10 W heat dissipation on the control side. Pole composition is 2 NO + 2 NC, with no built-in auxiliary contacts — you add those separately if the circuit needs feedback or interlocking. Rated insulation voltage hits 690 V, and the breaking capacity at 440 V is 640 A, so it clears faults cleanly within its AC-1 envelope. Power terminals accept up to 50 mm² cable (solid or flexible with ferrule), torqued to 12 N·m. Control-circuit screw clamps take 1–4 mm² at 1.2 N·m. IP20 finger-safe protection is fine for enclosed panels; not rated for washdown environments. AC-1 at 100 A is the headline number — it's the thermal current the main poles carry continuously in resistive service. Don't substitute a motor-rated (AC-3) contactor here unless you verify the coil and pole count match; this part is specced for resistive loads, not inductive motor starts. Mechanical durability is 3 million cycles, electrical durability 350,000 cycles at AC-1 — so it's built for frequent switching in oven or furnace control, not a once-a-day pump start. Operating altitude goes to 3000 m without derating, so it works in high-elevation plants without a current haircut.","metaTitle":"Schneider Electric LC1E80008M5WB Easy TeSys Contactor, 100 A","metaDescription":"Schneider Electric LC1E80008M5WB Easy TeSys contactor, 100 A rated operational current at ≤440 V AC-1, 4-pole, 220 V AC 50 Hz coil. Current lifecycle stage. DIN rail or plate mount","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"120 mm","Range":"Easy TeSys","Width":"95 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"6...20 ms on opening 20...35 ms on closing","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"6...10 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"0.8 mOhm - Ith 100 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 12 N.m","Inrush power in VA":"200 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068-2-30","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"3000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","Associated fuse rating":"160 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1200 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 4...16 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 4...50 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"640 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"800 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"9.7 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"100 A (at <55 °C) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"20 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"640 A 40 °C - 10 s for power circuit 320 A 40 °C - 60 s for power circuit 135 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"100 A (at 55 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/994e392b828c67d657b85b6c6f805ef9.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E80008M5WB/easypact-tvs-contactor-4p-ctr-100a-ac12no+2nc220v-50hz-wb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E80008M5WB/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"Rated operational current is 100 A at ≤440 V AC in AC-1 (resistive) duty. Rated insulation voltage is 690 V. Breaking capacity at 440 V is 640 A. The coil is 220 V AC 50 Hz with a 200 VA inrush."},{"question":"What compliance standards does this part meet?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, GB/T 14048.1, GB/T 14048.4, and GB/T 14048.5. Fire resistance is 850 °C per IEC 60695-2-1. Protective treatment is TH conforming to IEC 60068-2-30."},{"question":"What is the mounting and wiring specification?","answer":"Mounts on DIN rail or plate. Power terminals accept 4–50 mm² cable, torqued to 12 N·m. Control terminals accept 1–4 mm², torqued to 1.2 N·m. IP20 protection rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E80008M5WB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E80008M5WB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}