{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E80008M5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E80008M5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E80008M5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E80008M5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, 4-pole, 110 A AC-1, 220 V AC 50 Hz coil, screw clamp terminals, DIN rail or plate mount.","salesMarkdown":"Its headline rating is 110 A AC-1 at ≤415 V — that's the current it can make and break in resistive duty, so it handles heating elements, lighting banks, or transformer primary switching where inrush is low. The 220 V AC 50 Hz coil pulls 200 VA inrush at cos φ 0.75, then settles to 6–10 W heat dissipation. Coil drop-out is guaranteed between 0.3 and 0.6 Uc, operational pickup between 0.7 and 1.25 Uc, so it stays pulled in down to about 154 V and drops out reliably below 132 V. The contactor is rated for AC-1 utilisation category per IEC 60947-4-1, with a rated insulation voltage (Ui) of 690 V and a rated breaking capacity of 640 A at 440 V. Mechanical durability is 3 million cycles, electrical durability 350,000 cycles in AC-1. Maximum operating rate is 1200 cycles per hour at 60 °C. ## Integration notes Mounts on DIN rail or plate — 95 mm wide, 127 mm tall, 120 mm deep. Power circuit terminals accept 4–50 mm² flexible with cable end; control circuit terminals take 1–4 mm² solid or flexible. Tightening torque: 12 N·m on power, 1.2 N·m on control. No auxiliary contacts built in — the contactor ships without them, so add a separate auxiliary block if you need feedback or interlocking.","metaTitle":"Schneider Electric LC1E80008M5WBIN Easy TeSys Contactor, 110","metaDescription":"Schneider Electric LC1E80008M5WBIN Easy TeSys contactor, 110 A AC-1 rated at ≤415 V, 220 V AC 50 Hz coil. Active production. DIN rail or plate mount. 4P, 2 NO + 2 NC. Sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"120 mm","Range":"Easy TeSys","Width":"95 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"6...20 ms on opening 20...35 ms on closing","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"6...10 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"0.8 mOhm - Ith 110 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 12 N.m","Inrush power in VA":"200 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"3000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","Associated fuse rating":"160 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1200 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 4...16 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 4...50 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"640 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"800 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"9.7 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"110 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"20 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"640 A 40 °C - 10 s for power circuit 320 A 40 °C - 60 s for power circuit 135 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"110 A (at 40 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E80008M5WBIN/easy-tesys-contactor-4p4-no-ac1-415-v-80a-415-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E80008M5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1E80008M5WBIN in the same family?","answer":"Within the Easy TeSys range, the closest sibling is the LC1E80008M5W — same 110 A AC-1 rating, same 4-pole 2 NO + 2 NC configuration, same 220 V AC 50 Hz coil. The only difference is the suffix (BIN vs no BIN), which typically indicates a packaging or regional variant rather than a functional change. Both are active and pin-compatible for the same mounting footprint."},{"question":"What compliance documentation does Schneider Electric provide for this contactor?","answer":"The contactor is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, and EN/IEC 60947-5-1, plus the Chinese equivalents GB/T 14048.1, GB/T 14048.4, and GB/T 14048.5. It carries IP20 protection per IEC 60529 and TH protective treatment per IEC 60068. Fire resistance is 850 °C per IEC 60695-2-1. Standard Schneider documentation includes the datasheet, installation manual, and declaration of conformity covering these standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E80008M5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E80008M5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}