{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E80008N5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E80008N5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E80008N5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E80008N5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys LC1E80008N5WBIN, 4-pole contactor, 110 A AC-1 at ≤415 V, 415 V AC 50 Hz coil, screw clamp terminals, IP20.","salesMarkdown":"The Schneider Electric Easy TeSys LC1E80008N5WBIN is a 4-pole contactor rated for resistive load switching under utilisation category AC-1. Its rated operational current is 110 A at ≤415 V AC, 40 °C ambient, which means it is sized for heater banks, lighting stages, or other purely resistive circuits where inrush stays under 1.2× steady-state. The coil is 415 V AC at 50 Hz, a wide-range AC control type that holds in from 0.7 to 1.25 Uc and drops out between 0.3 and 0.6 Uc across the -5 to 55 °C band. The 110 A AC-1 rating governs the continuous current the main poles can carry without exceeding a 9.7 W per-pole dissipation. That dissipation figure, combined with the 6 to 10 W control-circuit heat loss, matters when the contactor is packed into a sealed enclosure — the total thermal load must be vented or the 40 °C ambient derating curve applies. Breaking capacity is 640 A at 440 V, and making capacity is 800 A at 440 V AC, both conforming to IEC 60947-4-1. These are the fault-clearing and closure-surge limits for the power circuit — the contactor can interrupt a bolted fault up to 640 A and close onto a load drawing up to 800 A peak, provided the upstream protection (a 160 A gG fuse at ≤690 V, coordination type 1) clears any higher fault. The 4-pole configuration is 2 NO + 2 NC, with no built-in auxiliary contact block. If you need feedback to a PLC or a seal-in circuit, an add-on block will be required — the base contactor carries only the main poles. Mounts on either a DIN rail or a plate, per the mounting support spec. The IP20 finger-safe protection means it is suitable for installation inside a locked panel but not in a washdown or outdoor location without an outer enclosure. Power-circuit terminals accept 4 to 50 mm² solid or flexible cable with a ferrule, tightened to 12 N·m. Control-circuit terminals take 1 to 4 mm² solid or flexible (1 to 2.5 mm² with ferrule) at 1.2 N·m. The TH protective treatment per IEC 60068 indicates the contactor is treated for tropical/humid environments. ## Mechanical and electrical endurance Rated for 350,000 electrical cycles under AC-1 load and 3,000,000 mechanical cycles. The maximum operating rate is 1,200 cycles per hour at 60 °C. Vibration resistance is 1.5 Gn (open) and 3 Gn (closed) across 5 to 300 Hz; shock resistance is 6 Gn open, 7 Gn closed for 11 ms. These figures confirm suitability for machinery with moderate vibration, provided the contactor is not expected to switch under those vibration levels.","metaTitle":"Schneider Easy TeSys LC1E80008N5WBIN Contactor, 110 A AC-1,","metaDescription":"Schneider Electric Easy TeSys LC1E80008N5WBIN contactor, 110 A rated operational current at 415 V AC-1, 4-pole, 415 V AC 50 Hz coil. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"120 mm","Range":"Easy TeSys","Width":"95 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"6...20 ms on opening 20...35 ms on closing","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"6...10 W for control circuit","Mounting support":"Plate DIN rail","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"0.8 mOhm - Ith 110 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 12 N.m","Inrush power in VA":"200 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"3000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","Associated fuse rating":"160 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1200 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 4...16 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 4...50 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 4...50 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"640 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"800 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"9.7 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"110 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"20 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"640 A 40 °C - 10 s for power circuit 320 A 40 °C - 60 s for power circuit 135 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"110 A (at 40 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/65f1c680c368461447c466d90be4a8fa.pdf","sourceUrl":"https://www.se.com/in/en/product/LC1E80008N5WBIN/easy-tesys-contactor-4p4-no-ac1-415-v-80a-380-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E80008N5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What is the rated operational current and utilisation category?","answer":"The rated operational current is 110 A at ≤415 V AC under utilisation category AC-1, meaning it is designed for resistive loads such as heaters or lighting."},{"question":"What is the control circuit voltage?","answer":"The control circuit voltage is 415 V AC at 50 Hz, with a wide-range AC control type that operates between 0.7 and 1.25 Uc and drops out between 0.3 and 0.6 Uc."},{"question":"What standards does this contactor comply with?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T 14048.1, GB/T 14048.4, and GB/T 14048.5 standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E80008N5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E80008N5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}