{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E80F7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E80F7","canonicalUrl":"https://aoctrl.com/schneider/LC1E80F7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E80F7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E80F7, 3P(3NO) contactor, 80 A AC-3/AC-3e ≤440 V, 110 V AC 50/60 Hz coil, DIN-rail mount.","salesMarkdown":"The Schneider Electric LC1E80F7 is a three-pole contactor from the Easy TeSys Control range, rated 80 A in AC-3 and AC-3e utilisation categories at ≤440 V, with a 110 V AC 50/60 Hz coil. The 85 mm width and 127 mm height are the usual three-pole contactor footprint — check the 121 mm depth for enclosure depth clearance, especially on shallow backplates. The IP2X degree of protection means the contactor body resists finger ingress, but it is not sealed against dust or moisture — fit it inside an enclosure rated for the environment. AC-3e is the same duty but with enhanced electrical endurance for frequent cycling. The non-overlap time of 1.5 ms on both energisation and de-energisation between NC and NO contacts guarantees that the normally-closed and normally-open poles never close simultaneously — important for interlocking reversing starters or bypass circuits where overlap would short the supply. The TH protective treatment (pollution degree 3 per IEC 60068-2-30) means it handles humid, mildly corrosive atmospheres — typical for industrial control rooms but not for direct washdown.","metaTitle":"Schneider LC1E80F7 Easy TeSys Contactor, 80A, 110V AC Coil","metaDescription":"Schneider Electric LC1E80F7 Easy TeSys Control contactor, 3P, 80A AC-3/AC-3e at ≤440V, 110V AC 50/60Hz coil. Active production. DIN-rail mount. EN/IEC 60947 compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"121 mm","Range":"Easy TeSys","Width":"85 mm","title":"LC1E80F7","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","description":"Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3/AC-3e,<=440V,80A,110V AC coil,50/60Hz","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/193977bae514d0782b07e3122b49f4b0.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1E80F7/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v80a110v-ac-coil50-60hz/"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The headline rating is 80 A in AC-3/AC-3e at ≤440 V with a 110 V AC 50/60 Hz coil. It is a three-pole contactor (3P, 3NO) and mounts on DIN rail or plate. Dimensions: 85 mm wide, 127 mm high, 121 mm deep."},{"question":"What standards does this contactor comply with?","answer":"It complies with EN/IEC 60947-1, 60947-4-1, 60947-5-1, GB/T 14048.1, 14048.4, 14048.5, and the glow-wire test at 850 °C per IEC 60695-2-1. It also meets the fire-resistance requirements of EN/IEC 60335-1 and 60335-2-40 Annex JJ."},{"question":"What is the non-overlap time between NC and NO contacts?","answer":"The guaranteed non-overlap time is 1.5 ms on both energisation and de-energisation, ensuring the NC and NO poles never close simultaneously."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E80F7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E80F7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}