{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E95E5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E95E5","canonicalUrl":"https://aoctrl.com/schneider/LC1E95E5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E95E5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E95E5, 3-pole contactor, AC-3 95A at ≤440V, 48V AC coil, DIN-rail or plate mount.","salesMarkdown":"The coil is 48 V AC, so it pulls in and holds on a 48 VAC control supply. The non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation — this prevents shoot-through in reversing or star-delta circuits where the two contactors must never close simultaneously. ## Where it fits and how it mounts Dimensions are 85 mm wide, 127 mm high, 121 mm deep — fits a standard contactor footprint for this current class. IP2X protection means the contactor body is finger-safe but not sealed against moisture; it belongs in a clean, dry enclosure, not a washdown zone. ## Environmental and compliance profile The TH protective treatment (pollution degree 3 per IEC 60068-2-30) means it withstands humid, corrosive atmospheres — typical for industrial panels in non-conditioned plant floors. Operates without derating up to 3000 m altitude, and meets mechanical robustness of 1.5 Gn vibration (contacts open) and 3 Gn (closed), plus shock ratings of 6 Gn open and 7 Gn closed. Fire resistance tested to 850 °C per IEC 60695-2-1. Compliant with EN/IEC 60947-1, -4-1, -5-1, GB/T 14048 series, and relevant clauses of EN/IEC 60335 for household appliance safety — so it is accepted across European, Chinese, and many other regulatory jurisdictions.","metaTitle":"Schneider Electric LC1E95E5 Easy TeSys Contactor, 95A AC-3,","metaDescription":"Obsolete 3-pole contactor from Easy TeSys range. AC-3 rated 95A at ≤440V, 48V AC coil. DIN-rail or plate mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"121 mm","Range":"Easy TeSys","Width":"85 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1e1175c8007d2384789f41a6179117f.pdf","sourceUrl":"https://www.se.com/in/en/product/LC1E95E5/easy-tesys-contactor-3p3-no-ac3-440-v-95a-48-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E95E5/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC1E95E5?","answer":"AC-3 rated 95 A at ≤440 V for motor switching, with a 48 V AC coil. It is a 3-pole contactor (3 NO main poles) from the Easy TeSys Control range."},{"question":"What standards does the LC1E95E5 comply with?","answer":"It complies with EN/IEC 60947-1, -4-1, -5-1, GB/T 14048.1.4.5, and relevant clauses of EN/IEC 60335. Fire resistance is 850 °C per IEC 60695-2-1."},{"question":"How do I source the LC1E95E5?","answer":"Since it is obsolete, we source it to order against an RFQ. Provide your quantity and we will check available inventory or locate a traceable surplus unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E95E5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E95E5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}