{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E95M5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E95M5","canonicalUrl":"https://aoctrl.com/schneider/LC1E95M5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E95M5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact TVS contactor, 3P(3 NO), AC-3 ≤ 440 V 95 A, 220 V AC coil, LC1E95M5.","salesMarkdown":"The LC1E95M5 is a 3-pole EasyPact TVS contactor rated 95 A in AC-3 duty at ≤ 440 V, which is the motor-switching current category per EN/IEC 60947-4-1. That 95 A figure governs the maximum full-load current of a three-phase induction motor it can switch — not the resistive heating rating. For resistive loads (AC-1), the contactor carries a higher current, but for motor control the AC-3 number is the one that decides fit. The 220 V AC coil means the pull-in and hold voltage is standard line-to-neutral on a 220/380 V system or phase-to-phase on a 220 V delta supply. Mounts on DIN rail or a backplate, so it fits standard panel layouts. The 85 mm width and 127 mm height are compact for a 95 A frame — leaves room for auxiliary blocks alongside without crowding the gland plate. Rated for operation up to 3000 m altitude without derating, which covers most industrial sites and high-altitude installations without needing to downrate the current. ## Integration notes Mechanical robustness: the contactor withstands 3 Gn vibration when closed and 7 Gn shock when closed, which is sufficient for most conveyor and pump applications but not for direct engine-mount duty. The 10 MOhm insulation resistance on the power circuit at 500 VDC is the standard figure for a new contactor; expect it to drop with age and contamination, which is why periodic insulation testing is part of the maintenance schedule.","metaTitle":"Schneider LC1E95M5 EasyPact TVS Contactor, 95A AC-3, 220VAC","metaDescription":"Schneider Electric LC1E95M5 EasyPact TVS contactor, 3-pole, 95A AC-3 at ≤440V, 220V AC coil. Active production. DIN rail/plate mount. EN/IEC 60947 certified. Source to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"121 mm","Range":"Easy TeSys","Width":"85 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$111.14","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fc3ad65388ef7b19f99c27bf52bac88b.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC1E95M5/easypact-tvs-contactor-3p3-no-ac3-440-v-95a-220-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E95M5/alternatives.json"},"ai":{"faq":[{"question":"What standards does the LC1E95M5 comply with?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T 14048 series equivalents. It also meets the glow-wire test at 850 °C per IEC 60695-2-1 and has protective treatment TH (pollution degree 3) per IEC 60068-2-30."},{"question":"What is the mounting method for this contactor?","answer":"The LC1E95M5 mounts on either DIN rail or a backplate, giving flexibility for panel layout. The 85 mm width and 121 mm depth fit standard enclosure footprints."},{"question":"What utilisation categories does the LC1E95M5 support?","answer":"It supports AC-3 (motor starting/running), AC-3e (enhanced motor switching), and AC-1 (resistive load) categories. For motor control, the AC-3 rating of 95 A at ≤ 440 V is the selection criterion."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E95M5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E95M5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}