{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1000M7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1000M7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1000M7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1000M7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LC1F1000M7, 3-pole contactor, 1250 A AC-3 at ≤440 V, 220 V AC 40–400 Hz coil, plate mount.","salesMarkdown":"The LC1F1000M7 is a TeSys F direct-on-line contactor rated 1250 A conventional free-air thermal current (Ith) at 40 °C and 1250 A rated operational current (Ie) in AC-3 duty at ≤440 V, 50/60 Hz. That AC-3 figure governs motor switching — it handles 560 kW at 380–400 V three-phase, 630 kW at 415 V, and 670 kW at 440 V. Short-time withstand current (Icw) is 10 kA for 10 s, 7.5 kA for 30 s, and 3 kA for 10 min at 40 °C — this defines the coordination window with upstream protective devices. The 220 V AC control coil (40–400 Hz) draws through screw-clamp terminals accepting 1–4 mm² flexible or solid wire. Plate-mounted, not DIN rail; the 438 mm width and 332 mm height demand panel layout planning. ## Lifecycle and sourcing reality — EOL hot phase This part is flagged EOL hot (end-of-life, active phase-out). The TeSys F series is being superseded by newer TeSys ranges. If you are stocking spares for an existing panel, buy the last-run quantity now; if designing new, evaluate the current TeSys replacement family. ## Deployment and integration Plate-mounted in a motor control centre or standalone enclosure. The 0.1 mΩ average impedance at 1250 A 50 Hz means about 156 W dissipation per pole in AC-1 — adequate ventilation or forced cooling needed in a closed panel. Operating altitude 3000 m without derating; ambient range -5 to 40 °C operating, -60 to 80 °C storage.","metaTitle":"Schneider TeSys F LC1F1000M7 Contactor, 1250 A AC-3, 220 V C","metaDescription":"TeSys F LC1F1000M7 3-pole contactor rated 1250 A AC-3 at ≤440 V, 220 V AC coil. EOL hot phase. Sourced to order against RFQ. Motor power up to 670 kW.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"238.6 mm","Range":"TeSys","Width":"438 mm","Height":"332 mm","Standards":"EN 60947-1 IEC 60947-4-1 EN 60947-4-1 IEC 60947-1","Operating time":"40...80 ms closing 100...200 ms opening","lifecycle_stage":"eol_hot","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 1250 A 50 Hz","Device short name":"LC1F","Motor Power Range":"315 kW at 220...230 V 3 phases 560 kW at 380...400 V 3 phases 630 kW at 415 V 3 phases 670 kW at 440 V 3 phases","Poles description":"3P","Compatibility code":"LC1F","Motor starter type":"Direct on-line contactor","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3","Contactor application":"Motor control Resistive load","Associated fuse rating":"1400 A gG at <= 440 V","Contactor coil voltage":"220 V AC standard","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 3 cable(s) Power circuit: bar 4 cable(s)","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"8 kA conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"200 W AC-1","[Uc] control circuit voltage":"220 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"1250 A (at 1000 A (at <55 °C) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 440 V AC 50/60 Hz","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"10000 A 40 °C - 10 s 7500 A 40 °C - 30 s 5500 A 40 °C - 1 min 4200 A 40 °C - 3 min 3000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"1250 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ca2b852f2a8e838f7d22537086185840.pdf","sourceUrl":"https://www.se.com/za/en/product/LC1F1000M7/contactor-tesys-f-3p3no-ac3-440v-1000a-220v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1000M7/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1F1000M7 in the TeSys family?","answer":"The evidence does not list a pin-compatible direct successor. For a new design, evaluate the current TeSys range (e.g., TeSys GV or TeSys Deca) for equivalent AC-3 current rating and coil voltage. The LC1F1000M7 remains the correct spare for existing TeSys F panels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1000M7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1000M7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}