{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1000MD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1000MD","canonicalUrl":"https://aoctrl.com/schneider/LC1F1000MD","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1000MD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LC1F1000MD, 3-pole contactor, 1250 A AC-3 rated operational current, 220 V DC control coil, plate mount.","salesMarkdown":"## TeSys F LC1F1000MD — 1250 A AC-3 Power Contactor The Schneider Electric LC1F1000MD is a TeSys F series 3-pole contactor rated for 1250 A in AC-3 duty at ≤440 V AC, 50/60 Hz. That AC-3 rating governs motor switching — it handles 560 kW at 380–400 V three-phase, 630 kW at 415 V, and 670 kW at 440 V. The coil is 220 V DC standard, with closing time 40–80 ms and opening 100–200 ms. AC-1 resistive load rating is 1250 A; AC-3 motor duty is 1000 A at ≤55 °C. The associated fuse rating is 1400 A gG at ≤440 V. Short-time withstand (Icw) is 10 kA for 10 s, 7.5 kA for 30 s — enough for coordination with upstream protection. Rated breaking capacity is 8 kA per IEC 60947-4-1. Plate-mounted — no DIN-rail clip on this frame size. Dimensions: 438 mm wide, 332 mm high, 238.6 mm deep. Power connections are bar-type, accepting 3 or 4 cables. Control circuit uses screw clamp terminals, 1–4 mm² flexible or solid. IP20 front face with shrouds per IEC 60529. Certified to IEC 60947-4-1 and IEC 60947-1 (EN equivalents). Rated insulation voltage 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 group C. Impulse withstand voltage 8 kV. Overvoltage category III. Protective treatment TH for tropical environments. Ambient operating range -5 to 40 °C; storage -60 to 80 °C.","metaTitle":"Schneider TeSys F LC1F1000MD Contactor, 1250 A AC-3, 220 VDC","metaDescription":"Schneider Electric LC1F1000MD TeSys F contactor. 1250 A rated operational current (AC-3), 220 VDC coil, 3-pole. EOL lifecycle. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"238.6 mm","Range":"TeSys","Width":"438 mm","Height":"332 mm","Standards":"IEC 60947-4-1 IEC 60947-1 EN 60947-1 EN 60947-4-1","Operating time":"40...80 ms closing 100...200 ms opening","lifecycle_stage":"eol_hot","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 1250 A 50 Hz","Device short name":"LC1F","Motor Power Range":"315 kW at 220...230 V 3 phases 560 kW at 380...400 V 3 phases 630 kW at 415 V 3 phases 670 kW at 440 V 3 phases","Poles description":"3P","Compatibility code":"LC1F","Motor starter type":"Direct on-line contactor","Operating altitude":"3000 m without derating","Control circuit type":"DC standard","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-1","Contactor application":"Resistive load Motor control","Associated fuse rating":"1400 A gG at <= 440 V","Contactor coil voltage":"220 V DC standard","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 3 cable(s) Power circuit: bar 4 cable(s)","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"8 kA conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"200 W AC-1","[Uc] control circuit voltage":"220 V DC","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"1250 A (at 1000 A (at <55 °C) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 440 V AC 50/60 Hz","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"10000 A 40 °C - 10 s 7500 A 40 °C - 30 s 5500 A 40 °C - 1 min 4200 A 40 °C - 3 min 3000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"1250 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8d3b26db47bfb475c7eceab4dc882b30.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F1000MD/tesys-f-contactor-3p-3-no-ac3-440-v-1000-a-coil-220-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1000MD/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F1000MD and get a price?","answer":"We source the LC1F1000MD to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit a request for quotation."},{"question":"What is the rated motor power for LC1F1000MD at 400 V?","answer":"560 kW at 380–400 V three-phase, 630 kW at 415 V, and 670 kW at 440 V, all in AC-3 duty."},{"question":"What coil voltage does LC1F1000MD use?","answer":"220 V DC standard control circuit voltage."},{"question":"What compliance documentation does Schneider provide for LC1F1000MD?","answer":"The contactor is certified to IEC 60947-4-1, IEC 60947-1, and their EN equivalents. Rated insulation voltage 1000 V (IEC) / 1500 V (VDE 0110 group C), impulse withstand 8 kV, overvoltage category III. Protective treatment TH for tropical environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1000MD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1000MD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}