{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1000N7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1000N7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1000N7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1000N7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F1000N7, 3-pole contactor, AC-3 rated 1000 A at ≤440 VAC, coil 415 VAC 50/60 Hz, end-of-life lifecycle.","salesMarkdown":"The LC1F1000N7 is a TeSys F 3-pole contactor rated for 1000 A AC-3 at ≤440 VAC, meaning it handles motor switching up to that current in the standard motor-duty category. For resistive loads (AC-1), the conventional free-air thermal current Ith is 1250 A at 40°C. The 415 VAC control coil operates from 40 to 400 Hz, so a standard 50/60 Hz control transformer works without modification. Motor power capability spans 315 kW at 220-230 V three-phase up to 670 kW at 440 V three-phase. The contactor carries EN 60947-1 and IEC 60947-4-1 certifications, covering the standard for contactors and motor-starters. Rated impulse withstand voltage is 8 kV, overvoltage category III, so it's suitable for fixed-installation distribution panels. For a BOM freeze or replacement project, the official successor within the TeSys F range should be verified against your specific duty and control voltage. Mounting is plate-type, not DIN rail — expect to bolt the contactor to a backplate or sub-panel. Dimensions are 438 mm wide, 332 mm high, 238.6 mm deep, so panel layout must account for the footprint and clearance for power bus bars. Power circuit connections use bar-type terminals accepting 3 or 4 cables; control circuit connections are screw clamp terminals accepting 1 to 4 mm² flexible or solid wire. The front face carries IP20 protection with shrouds per IEC 60529 and VDE 0106. Associated fuse rating is 1400 A gG at ≤440 V for short-circuit coordination. Rated breaking capacity is 8 kA per IEC 60947-4-1, and the rated short-time withstand current (Icw) is 10,000 A for 10 seconds at 40°C — figures needed for selectivity studies in a distribution panel. Power dissipation per pole is 200 W in AC-1 duty, so thermal management inside the enclosure matters — forced ventilation or derating may be needed if multiple contactors are ganged.","metaTitle":"Schneider LC1F1000N7 TeSys F Contactor, 1000 A AC-3, 415 VAC","metaDescription":"Schneider LC1F1000N7 TeSys F contactor, 3-pole, AC-3 rated 1000 A at ≤440 VAC. 415 VAC 50/60 Hz coil. EOL lifecycle. Sourced to order against RFQ. EN/IEC 60947 certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"238.6 mm","Range":"TeSys","Width":"438 mm","title":"LC1F1000N7","Height":"332 mm","Standards":"EN 60947-1 IEC 60947-4-1 EN 60947-4-1 IEC 60947-1","description":"TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 1000 A - coil 415 V AC","Operating time":"40...80 ms closing 100...200 ms opening","lifecycle_stage":"eol_hot","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 1250 A 50 Hz","Device short name":"LC1F","Motor Power Range":"315 kW at 220...230 V 3 phases 560 kW at 380...400 V 3 phases 630 kW at 415 V 3 phases 670 kW at 440 V 3 phases","Poles description":"3P","Compatibility code":"LC1F","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-1","Contactor application":"Motor control Resistive load","Associated fuse rating":"1400 A gG at <= 440 V","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 3 cable(s) Power circuit: bar 4 cable(s)","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"8 kA conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"200 W AC-1","[Uc] control circuit voltage":"415 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"1250 A (at 1000 A (at <55 °C) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 440 V AC 50/60 Hz","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"10000 A 40 °C - 10 s 7500 A 40 °C - 30 s 5500 A 40 °C - 1 min 4200 A 40 °C - 3 min 3000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"1250 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/53a45810f13c7548291843724b714e4e.pdf","sourceUrl":"https://www.se.com/au/en/product/LC1F1000N7/tesys-f-contactor-3p-3-no-ac3-440-v-1000-a-coil-415-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1000N7/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Schneider provide for LC1F1000N7?","answer":"The LC1F1000N7 is certified to EN 60947-1 and IEC 60947-4-1. The front face carries IP20 protection per IEC 60529 and VDE 0106. Protective treatment is TH (tropicalized). RoHS/REACH compliance documentation should be available from Schneider Electric's documentation portal or your distributor."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1000N7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1000N7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}