{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1000Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1000Q7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1000Q7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1000Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F1000Q7, 3-pole contactor, AC-3 1000 A at ≤440 V, coil 380 V AC 40-400 Hz, plate mount, EOL phase-out.","salesMarkdown":"The Schneider Electric LC1F1000Q7 is a TeSys F 3-pole contactor rated for 1000 A in AC-3 duty at ≤440 V AC, 50/60 Hz, with a 380 V AC control coil. The 1250 A AC-1 thermal current (Ith) covers the resistive heating case, so it's also usable for high-current resistive banks or furnace loads. The 380 V AC coil pulls in across 40-400 Hz. Closing time runs 40-80 ms; opening takes 100-200 ms. That's a standard opening delay for a contactor this size — the arc chutes need that window to clear the ionized path on a 1000 A break. Rated breaking capacity is 8 kA per IEC 60947-4-1, backed by a short-time withstand (Icw) of 10 kA for 10 seconds at 40 °C. If you need a drop-in replacement from current production, a parametric cross-reference to a similar TeSys F frame size is possible — but the coil voltage (380 V AC) and the 1000 A AC-3 rating narrow the field. We can help identify a substitute during the RFQ process. Plate-mounted — no DIN rail clip on this frame size. The footprint is 438 mm wide by 332 mm high by 238.6 mm deep. That's a large contactor; plan for a backplate or sub-panel with enough clearance for the arc chute ventilation and the power bus bars. Power circuit connections are via bar (3 or 4 cables). Control circuit terminals are screw clamp, accepting 1 to 4 mm² flexible or solid. IP20 on the front face with shrouds fitted — that's touch-safe but not washdown-rated. Install inside a cabinet rated for the environment. Permissible ambient around the device extends to -40 to 60 °C, but the -5 to 40 °C operating window is the one that governs switching duty. Above 40 °C, derate per the thermal curve. Designed and tested to EN 60947-1, EN 60947-4-1, IEC 60947-4-1, and IEC 60947-1. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1, with an impulse withstand (Uimp) of 8 kV. Overvoltage category III — suitable for fixed-installation distribution boards and industrial panels. Protective treatment TH indicates tropicalized protection against heat and humidity. ## Selection and sizing notes That translates to roughly 560 kW at 380-400 V three-phase, or 670 kW at 440 V. The AC-1 rating (1250 A) is higher because resistive loads have no inrush — the contactor's thermal capacity is the limit, not the arc interruption. Associated fuse rating is 1400 A gG at ≤440 V for short-circuit protection. Maximum operating rate is 600 cycles per hour at 55 °C. Power dissipation per pole is 200 W in AC-1 duty. At 1250 A, that's about 0.16 mΩ per pole — consistent with the 0.1 mOhm average impedance at 1250 A, 50 Hz. For panel thermal calculations, budget 600 W total dissipation across all three poles under full AC-1 load.","metaTitle":"TeSys F LC1F1000Q7 Contactor, 1000 A AC-3, 380 V AC Coil","metaDescription":"Schneider TeSys F LC1F1000Q7 3-pole contactor. 1000 A AC-3 at ≤440 V, 380 V AC coil. EOL phase-out. Sourced to order against RFQ. IEC 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"238.6 mm","Range":"TeSys","Width":"438 mm","Height":"332 mm","Standards":"EN 60947-1 EN 60947-4-1 IEC 60947-4-1 IEC 60947-1","Operating time":"40...80 ms closing 100...200 ms opening","lifecycle_stage":"eol_hot","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 1250 A 50 Hz","Device short name":"LC1F","Motor Power Range":"315 kW at 220...230 V 3 phases 560 kW at 380...400 V 3 phases 630 kW at 415 V 3 phases 670 kW at 440 V 3 phases","Poles description":"3P","Compatibility code":"LC1F","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-1","Contactor application":"Motor control Resistive load","Associated fuse rating":"1400 A gG at <= 440 V","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 3 cable(s) Power circuit: bar 4 cable(s)","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"8 kA conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"200 W AC-1","[Uc] control circuit voltage":"380 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"1250 A (at 1000 A (at <55 °C) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 440 V AC 50/60 Hz","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"10000 A 40 °C - 10 s 7500 A 40 °C - 30 s 5500 A 40 °C - 1 min 4200 A 40 °C - 3 min 3000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"1250 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/42e6ec984f7b21b061b6803b7618136c.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F1000Q7/tesys-f-contactor-3p-3-no-ac3-440-v-1000-a-coil-380-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1000Q7/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for LC1F1000Q7?","answer":"We source the LC1F1000Q7 to order against an RFQ through our independent distribution network. Submit an RFQ for current pricing and availability confirmation at quote time."},{"question":"What is the closest alternative to LC1F1000Q7 in the TeSys F family?","answer":"There is no official successor order code listed. A parametric cross-reference within the TeSys F range would need to match the 1000 A AC-3 rating, 3-pole configuration, and 380 V AC coil voltage. We can help identify a substitute during the RFQ process."},{"question":"What is LC1F1000Q7's depth?","answer":"The depth is 238.6 mm."},{"question":"What range does LC1F1000Q7 belong to?","answer":"It belongs to the Schneider Electric TeSys F range of contactors."},{"question":"What compliance documentation does Schneider provide for LC1F1000Q7?","answer":"The contactor is designed and tested to EN 60947-1, EN 60947-4-1, IEC 60947-4-1, and IEC 60947-1. It carries an overvoltage category III rating and protective treatment TH (tropicalized)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1000Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1000Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}