{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1000Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1000Q7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1000Q7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1000Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F1000Q7, 3-pole contactor, AC-3 1000 A at ≤440 V, coil 380 V AC 40-400 Hz, plate mount, EOL phase-out.","salesMarkdown":"The Schneider Electric LC1F1000Q7 is a TeSys F 3-pole contactor rated for 1000 A in AC-3 duty at ≤440 V AC, 50/60 Hz, with a 380 V AC control coil. The 1250 A AC-1 thermal current (Ith) covers the resistive heating case, so it's also usable for high-current resistive banks or furnace loads. The 380 V AC coil pulls in across 40-400 Hz. Closing time runs 40-80 ms; opening takes 100-200 ms. That's a standard opening delay for a contactor this size — the arc chutes need that window to clear the ionized path on a 1000 A break. Rated breaking capacity is 8 kA per IEC 60947-4-1, backed by a short-time withstand (Icw) of 10 kA for 10 seconds at 40 °C. If you need a drop-in replacement from current production, a parametric cross-reference to a similar TeSys F frame size is possible — but the coil voltage (380 V AC) and the 1000 A AC-3 rating narrow the field. We can help identify a substitute during the RFQ process. Plate-mounted — no DIN rail clip on this frame size. The footprint is 438 mm wide by 332 mm high by 238.6 mm deep. That's a large contactor; plan for a backplate or sub-panel with enough clearance for the arc chute ventilation and the power bus bars. Power circuit connections are via bar (3 or 4 cables). Control circuit terminals are screw clamp, accepting 1 to 4 mm² flexible or solid. IP20 on the front face with shrouds fitted — that's touch-safe but not washdown-rated. Install inside a cabinet rated for the environment. Permissible ambient around the device extends to -40 to 60 °C, but the -5 to 40 °C operating window is the one that governs switching duty. Above 40 °C, derate per the thermal curve. Designed and tested to EN 60947-1, EN 60947-4-1, IEC 60947-4-1, and IEC 60947-1. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1, with an impulse withstand (Uimp) of 8 kV. Overvoltage category III — suitable for fixed-installation distribution boards and industrial panels. Protective treatment TH indicates tropicalized protection against heat and humidity. ## Selection and sizing notes That translates to roughly 560 kW at 380-400 V three-phase, or 670 kW at 440 V. The AC-1 rating (1250 A) is higher because resistive loads have no inrush — the contactor's thermal capacity is the limit, not the arc interruption. Associated fuse rating is 1400 A gG at ≤440 V for short-circuit protection. Maximum operating rate is 600 cycles per hour at 55 °C. Power dissipation per pole is 200 W in AC-1 duty. At 1250 A, that's about 0.16 mΩ per pole — consistent with the 0.1 mOhm average impedance at 1250 A, 50 Hz. For panel thermal calculations, budget 600 W total dissipation across all three poles under full AC-1 load.","metaTitle":"TeSys F LC1F1000Q7 Contactor, 1000 A AC-3, 380 V AC Coil","metaDescription":"Schneider TeSys F LC1F1000Q7 3-pole contactor. 1000 A AC-3 at ≤440 V, 380 V AC coil. EOL phase-out. Sourced to order against RFQ. IEC 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"238.6 mm","Width":"438 mm","Height":"332 mm","Current":"1250 A (at 1000 A (at <55 °C) at <= 440 V AC AC-3","Voltage":"440 V AC 50/60 Hz","Application":"Resistive load, Motor control","Coil Voltage":"380 V AC 40...400 Hz","Operating Time":"40...80 ms closing 100...200 ms opening","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"8 kA conforming to IEC 60947-4-1","Insulation Voltage Ui":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Temp Operating Max":"40 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 40...400 Hz","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...40 °C","Permissible Ambient Air Temperature Around The Device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/42e6ec984f7b21b061b6803b7618136c.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F1000Q7/tesys-f-contactor-3p-3-no-ac3-440-v-1000-a-coil-380-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1000Q7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1000Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1000Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}