{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1000RD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1000RD","canonicalUrl":"https://aoctrl.com/schneider/LC1F1000RD","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1000RD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F1000RD, 3-pole contactor, AC-3 1000 A at ≤440 V, coil 440 V DC, plate mount.","salesMarkdown":"The Schneider Electric TeSys F LC1F1000RD is a 3-pole (3 NO) contactor rated for heavy motor and resistive loads, with a conventional free air thermal current (Ith) of 1250 A at 40 °C and a rated operational current (Ie) of 1000 A in AC-3 duty at ≤440 V AC. That AC-3 rating is the figure that governs motor switching — it means the contactor handles the high inrush of squirrel-cage motors during starting and breaking, not just steady-state resistive current. The coil is DC standard at 440 V DC, so verify your control voltage matches before wiring. ## Motor Power and Breaking Capacity The LC1F1000RD covers a wide motor power range: 315 kW at 220–230 V three-phase, 560 kW at 380–400 V, 630 kW at 415 V, and 670 kW at 440 V. The rated breaking capacity is 8 kA per IEC 60947-4-1, and the rated short-time withstand current (Icw) holds 10 kA for 10 seconds at 40 °C — figures that matter for coordination with upstream protective devices. The associated fuse recommendation is 1400 A gG at ≤440 V. This part is in end-of-life (EOL) phase-out status. Mounting is plate-based — not DIN-rail snap-on — so plan for bolt-down integration in the panel. Dimensions are 438 mm wide, 332 mm high, and 238.6 mm deep. The IP20 front face with shrouds (per IEC 60529 and VDE 0106) means finger-safe from the front but not sealed against moisture; keep it in a clean, dry enclosure. Power circuit connections use bar-type terminals for 3 or 4 cables; control circuit uses screw clamp terminals accepting 1–4 mm² flexible or solid wire. Certified to EN/IEC 60947-1 and 60947-4-1. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 Group C. Impulse withstand voltage (Uimp) is 8 kV, overvoltage category III. The TH protective treatment indicates tropicalization for humid environments.","metaTitle":"Schneider TeSys F LC1F1000RD Contactor, 1000 A AC-3, 440 VDC","metaDescription":"Schneider Electric TeSys F LC1F1000RD contactor, 3-pole, 1000 A AC-3 rated operational current, 440 VDC coil. EOL phase-out; sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"238.6 mm","Width":"438 mm","Height":"332 mm","Application":"Resistive load Motor control","Operating Time":"40...80 ms closing 100...200 ms opening","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"8 kA conforming to IEC 60947-4-1","Temp Operating Max":"40 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"DC standard","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...40 °C","Permissible Ambient Air Temperature Around The Device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/37a031516b1b6bdd49261fee1a247f39.pdf","sourceUrl":"https://www.se.com/za/en/product/LC1F1000RD/tesys-f-contactor-3p-3-no-ac3-440-v-1000-a-coil-440-v-dc/"},"ai":{"faq":[{"question":"What compliance documentation does Schneider provide for LC1F1000RD?","answer":"The contactor is certified to EN/IEC 60947-1 and 60947-4-1. The evidence does not list RoHS, REACH, UL, or CSA specific marks, but the standards compliance and TH protective treatment (tropicalization) are documented."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1000RD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1000RD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}