{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1000W7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1000W7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1000W7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1000W7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F1000W7, 3P NO contactor, AC-3 rated 1000 A at ≤440 V, coil 265-277 V AC 40-400 Hz, plate mount, IP20 front face.","salesMarkdown":"It carries a rated operational current of 1000 A at ≤440 V AC in AC-3 duty (1250 A conventional free-air thermal current Ith at 40 °C), and can switch motors up to 670 kW at 440 V or 560 kW at 380-400 V three-phase. The coil is rated 265-277 V AC at 40-400 Hz, with closing time 40-80 ms and opening 100-200 ms. Mounts to a plate (not DIN rail) — plan for the footprint: 438 mm wide, 332 mm tall, 238.6 mm deep. Power connections use bars (3 or 4 cables); control wiring is screw-clamp terminals accepting 1-4 mm² flexible or solid. The front face carries IP20 protection with shrouds per IEC 60529 and VDE 0106. Operating altitude up to 3000 m without derating; ambient air temperature for operation -5 to 40 °C, with permissible extended range -40 to 60 °C around the device. Conforms to IEC 60947-1, IEC 60947-4-1, EN 60947-1, and EN 60947-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1 (1500 V per VDE 0110 group C), impulse withstand voltage 8 kV, overvoltage category III. Short-time withstand current 10 kA for 10 s at 40 °C. Protective treatment TH for tropical environments.","metaTitle":"TeSys F LC1F1000W7 Contactor, 3P AC-3 1000 A, 265-277 V AC C","metaDescription":"Schneider TeSys F LC1F1000W7 contactor, 3P NO, AC-3 rated 1000 A at ≤440 V, coil 265-277 V AC. End-of-life phase-out; sourced to order against RFQ. IEC/EN 60947.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"238.6 mm","Width":"438 mm","Height":"332 mm","Current":"1250 A (at 1000 A (at <55 °C) at <= 440 V AC AC-3","Voltage":"440 V AC 50/60 Hz","Application":"Resistive load, Motor control","Coil Voltage":"265...277 V AC 40...400 Hz","Operating Time":"40...80 ms closing 100...200 ms opening","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"8 kA conforming to IEC 60947-4-1","Insulation Voltage Ui":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Temp Operating Max":"40 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 40...400 Hz","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...40 °C","Permissible Ambient Air Temperature Around The Device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/43ae1b7c244c068ecba012ec0f9b8cd3.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F1000W7/tesys-f-contactor-3p-3-no-ac3-440-v-1000-a-coil-265-277-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1000W7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1000W7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1000W7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}