{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1154G6L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1154G6L","canonicalUrl":"https://aoctrl.com/schneider/LC1F1154G6L","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1154G6L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F1154G6L, 4-pole contactor, 200 A rated operational current (AC-1), 120 V AC 60 Hz coil, plate mount.","salesMarkdown":"The Schneider LC1F1154G6L is a 4-pole (4 NO) TeSys F contactor rated for 200 A in AC-1 utilisation category, meaning it is designed for resistive loads — heaters, ovens, lighting banks — not for motor starting (that would be AC-3). The coil pulls 120 V AC at 60 Hz, with an inrush of 660 VA at 60 Hz and a hold-in draw of 55 VA. Closing time runs 23 to 35 ms; opening is faster at 5 to 15 ms. That operating speed matters when you need to sequence multiple contactors in a heating zone — the spread is tight enough to avoid overlap on a resistive bank. This is a plate-mount contactor (no DIN-rail clip), so plan for a backplate or sub-panel. Dimensions are 7.9 in wide by 10.4 in tall by 6.7 in deep — that is a substantial footprint, roughly the size of a small loaf. Power connections are bolted, accepting two bars 20 x 3 mm or ring terminals up to 95 mm². Torque the power circuit to 88.5 lbf·in (10 N·m) and the control circuit to 10.6 lbf·in (1.2 N·m). The headline number is 200 A at ≤ 440 V AC in AC-1 duty. That is the resistive load rating — do not use it for motor starting at that current without derating to AC-3. For motor loads, the UL/CSA horsepower ratings are the ones to watch: 30 hp at 200 V AC, 40 hp at 230 V AC, 75 hp at 460 V AC, and 100 hp at 575 V AC. The rated breaking capacity is 920 A per IEC 60947-4-1, and the associated fuse recommendation is 125 A aM or 200 A gG at ≤ 440 V. The contactor is TH-treated for tropical environments (protective treatment against humidity and fungus).","metaTitle":"Schneider LC1F1154G6L TeSys F Contactor, 200 A AC-1, 120 VAC","metaDescription":"Schneider TeSys F LC1F1154G6L 4-pole contactor, 200 A AC-1 resistive load, 120 VAC 60 Hz coil. EOL phase-out. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"6.7 in (171 mm)","Width":"7.9 in (200.5 mm)","Height":"10.4 in (265 mm)","Category":"39997-CANADIAN PRODUCTS","Standards":"EN 60947-1 IEC 60947-1 IEC 60947-4-1 JIS C8201-4-1 EN 60947-4-1","Operating time":"23...35 ms closing 5...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"12...16 W","Mounting Support":"Plate","Range of Product":"TeSys F","Device short name":"LC1F","Poles description":"4P","Tightening torque":"Power circuit 88.5 lbf.in (10 N.m) Control circuit 10.6 lbf.in (1.2 N.m)","Inrush power in VA":"660 VA, 60 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed6 Gn, 5...300 Hz Shocks contactor open9 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms","Nbr. of units in pkg.":"1","Associated fuse rating":"125 A aM at 200 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Power circuit 2 bars 20 x 3 mm Power circuit lugs-ring terminals 1 0.1 in² (95 mm²) Power circuit connector 1 0.1 in² (95 mm²) Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bolted connection","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"920 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","motor power HP (UL / CSA)":"30 hp at 200 V AC 40 hp at 230 V AC 75 hp at 460 V AC 100 hp at 575 V AC","Power dissipation per pole":"15 W AC-1","[Uc] control circuit voltage":"120 V AC 60 Hz","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"200 A (at <104 °F (40 °C)) at <= 440 V AC AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"-40...140 °F (-40...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1100 A 104 °F (40 °C) - 10 s 640 A 104 °F (40 °C) - 30 s 520 A 104 °F (40 °C) - 1 min 400 A 104 °F (40 °C) - 3 min 320 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"200 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"140...158 °F (60...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5a4f96d1b5e7b89e0a4eedd9c275cfde.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1F1154G6L/tesys-f-nonreversing-contactor-4p-open-600v-115a-120vac-60hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1154G6L/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to the LC1F1154G6L in the TeSys F family?","answer":"The closest active replacement would be a current-production TeSys F contactor with the same 4-pole, 200 A AC-1 rating and 120 VAC coil. The exact order code depends on the current catalogue; contact us with your RFQ and we can cross-reference the official successor."},{"question":"Where can I buy the LC1F1154G6L?","answer":"We source the LC1F1154G6L through independent distribution and surplus channels. It is quoted to order against an RFQ — availability and current pricing are confirmed at quote time."},{"question":"What are the key specifications of the LC1F1154G6L?","answer":"It is a 4-pole (4 NO) contactor rated 200 A in AC-1 (resistive load) at ≤ 440 V AC, with a 120 V AC 60 Hz coil. Dimensions are 7.9 x 10.4 x 6.7 in. It is plate-mount, IP2X front face, and rated for 30-100 hp depending on voltage (UL/CSA)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1154G6L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1154G6L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}