{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F115B622L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F115B622L","canonicalUrl":"https://aoctrl.com/schneider/LC1F115B622L","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F115B622L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor, LC1F115B622L, 3-pole, 200 A AC-3 rated operational current, 24 V AC 60 Hz coil, 2 NO + 2 NC auxiliary contacts, end-of-life status.","salesMarkdown":"## TeSys F Contactor — LC1F115B622L For a quick fit check: this contactor delivers 55 kW at 380–400 V AC, 59 kW at 415/440 V, and 75 kW at 500 V; on UL/CSA duty it's rated 75 hp at 460 V AC and 100 hp at 575 V AC. The coil is 24 V AC 60 Hz (Uc), with an operational range of 0.85–1.1 Uc and a drop-out band of 0.35–0.55 Uc at 55 °C. Auxiliary contacts are built in as 2 NO + 2 NC. The LC1F115B622L carries approvals to IEC 60947-4-1, EN 60947-4-1, EN 60947-1, and JIS C8201-4-1. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Overvoltage category III. The front face with shrouds achieves IP2X per IEC 60529 and VDE 0106. Protective treatment is TH (tropicalized). ## Integration Notes Mounting is plate-based (not DIN rail), so plan for a backplate or sub-panel in the enclosure. Power circuit connections accept two bars (20 x 3 mm), ring terminals up to 95 mm², or a connector for 95 mm². Control circuit terminals are screw-clamp, accepting 1–4 mm² flexible or solid (without cable end) or 1–2.5 mm² flexible with cable end. Tightening torque: power circuit 10 N·m, control circuit 1.2 N·m. Dimensions: 6.7 in (171 mm) deep, 6.4 in (163.3 mm) wide, 10.4 in (265 mm) high. Heat dissipation is 12–16 W total; per pole it's 15 W in AC-1 and 5 W in AC-3. Associated fuse rating: 125 A aM or 200 A gG at ≤ 440 V.","metaTitle":"Schneider Electric LC1F115B622L TeSys F Contactor, 200 A AC-","metaDescription":"Schneider Electric LC1F115B622L TeSys F contactor, 200 A rated operational current (AC-3), 55 kW at 400 V. 24 V AC 60 Hz coil, 2 NO + 2 NC aux. End-of-life (EOL) — sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"6.7 in (171 mm)","Width":"6.4 in (163.3 mm)","Height":"10.4 in (265 mm)","Category":"39997-CANADIAN PRODUCTS","Standards":"JIS C8201-4-1 IEC 60947-1 EN 60947-4-1 EN 60947-1 IEC 60947-4-1","Motor power kW":"55 kW at 380...400 V AC 50/60 Hz 59 kW at 415 V AC 50/60 Hz 59 kW at 440 V AC 50/60 Hz 75 kW at 500 V AC 50/60 Hz 80 kW at 660...690 V AC 50/60 Hz 65 kW at 1000 V AC 50/60 Hz 30 kW at 220...230 V AC 50/60 Hz","Operating time":"23...35 ms closing 5...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"12...16 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.37 mOhm - Ith 200 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Power circuit 88.5 lbf.in (10 N.m) Control circuit 10.6 lbf.in (1.2 N.m)","Inrush power in VA":"660 VA, 60 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3","Contactor application":"Motor control Resistive load","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed6 Gn, 5...300 Hz Shocks contactor open9 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms","Nbr. of units in pkg.":"1","Associated fuse rating":"125 A aM at 200 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Power circuit 2 bars 2 20 x 3 mm Power circuit lugs-ring terminals 1 0.1 in² (95 mm²) Power circuit connector 1 0.1 in² (95 mm²) Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"920 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","motor power HP (UL / CSA)":"30 hp at 200 V AC 40 hp at 230 V AC 75 hp at 460 V AC 100 hp at 575 V AC","Power dissipation per pole":"15 W AC-1 5 W AC-3","[Uc] control circuit voltage":"24 V AC 60 Hz","Auxiliary contact composition":"2 NO + 2 NC","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"200 A (at 115 A (at <131 °F (55 °C)) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"-40...140 °F (-40...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1100 A 104 °F (40 °C) - 10 s 640 A 104 °F (40 °C) - 30 s 520 A 104 °F (40 °C) - 1 min 400 A 104 °F (40 °C) - 3 min 320 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"200 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"140...158 °F (60...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/509e9f3f3aa07ccf9ad0b0913187ce10.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1F115B622L/tesys-f-nonreversing-contactor-3p-open-600v-115a-24ac-60hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F115B622L/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F115B622L?","answer":"We source this EOL contactor to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What are the key ratings for LC1F115B622L?","answer":"Rated operational current (Ie) is 200 A at ≤ 440 V AC in AC-3 duty. Motor power is 55 kW at 400 V, 75 kW at 500 V, and 80 kW at 690 V. Coil voltage is 24 V AC 60 Hz. Auxiliary contacts: 2 NO + 2 NC."},{"question":"What is the closest alternative to LC1F115B622L?","answer":"A form-fit-function alternative would be another TeSys F contactor in the same frame size and AC-3 current class (200 A), but with a different coil voltage or auxiliary contact arrangement. Check the spec line yourself — the coil voltage (24 V AC 60 Hz) and the 2 NO + 2 NC aux configuration are the binding constraints for a drop-in swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F115B622L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F115B622L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}