{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F115V5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F115V5","canonicalUrl":"https://aoctrl.com/schneider/LC1F115V5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F115V5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor, LC1F115V5, 3-pole, 55 kW at 400 V AC-3, 200 A rated, 400 V AC 50 Hz coil, plate mount.","salesMarkdown":"The LC1F115V5 is a 3-pole contactor from the TeSys F range, rated for 55 kW motor switching at 380–400 V AC in AC-3 duty (the standard category for squirrel-cage motor starting). That 55 kW figure at 400 V is the load the contactor handles in normal starting and running — not the resistive-heater rating, which is higher. For AC-1 resistive loads the thermal current (Ith) is 200 A at 50 Hz, with 15 W dissipation per pole. Control circuit is 400 V AC 50 Hz, with a pickup range of 0.85–1.1 Uc and drop-out between 0.35–0.55 Uc. Inrush is 550 VA at 50 Hz; hold-in drops to 45 VA. Operating time is 23–35 ms closing, 5–15 ms opening — fast enough for most motor control but not for high-speed reversing without interlocking. This part is in end-of-life (hot) phase — the manufacturer has flagged it for discontinuation. No official successor order code appears in the record. If you are freezing a new design, consider whether a current-production TeSys F variant with the same footprint and ratings can be qualified. Mounts on a plate — not DIN rail. Dimensions are 162 mm high, 163.3 mm wide, 171 mm deep. Power circuit connections accept bar (up to 20 x 3 mm busbar), ring lugs, or connectors for up to 95 mm² cable. Control circuit uses screw clamp terminals for 1–4 mm² flexible or solid. Tightening torque is 10 N·m on the power circuit, 1.2 N·m on the control circuit. IP2X front face with shrouds per IEC 60529. Designed to IEC 60947-4-1, IEC 60947-1, EN 60947-4-1, EN 60947-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 group C. Overvoltage category III. Protective treatment TH (tropicalized). Mechanical durability 10 million cycles. Maximum operating rate 2400 cycles per hour at 55 °C. Altitude 3000 m without derating.","metaTitle":"Schneider Electric LC1F115V5 TeSys F Contactor, 55 kW AC-3","metaDescription":"Schneider Electric LC1F115V5 TeSys F contactor, 55 kW at 400 V AC-3, 200 A rated, 3-pole, 400 V AC coil. End-of-life phase. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"171 mm","Range":"TeSys","Width":"163.3 mm","Height":"162 mm","Standards":"EN 60947-4-1 EN 60947-1 JIS C8201-4-1 IEC 60947-4-1 IEC 60947-1","Motor power kW":"55 kW at 380...400 V AC 50/60 Hz (AC-3) 59 kW at 415 V AC 50/60 Hz (AC-3) 59 kW at 440 V AC 50/60 Hz (AC-3) 75 kW at 500 V AC 50/60 Hz (AC-3) 80 kW at 660...690 V AC 50/60 Hz (AC-3) 30 kW at 220...230 V AC 50/60 Hz (AC-3) 18.5 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"23...35 ms closing 5...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"12...16 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.37 mOhm - Ith 200 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Power circuit: 10 N.m Control circuit: 1.2 N.m","Compatibility code":"LC1F","Inrush power in VA":"550 VA, 50 Hz cos phi 0.3 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 50 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-1 AC-4","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Associated fuse rating":"125 A aM at 200 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm Power circuit: lugs-ring terminals 1 cable(s) 95 mm² Power circuit: connector 1 cable(s) 95 mm² Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bolted connection","IP degree of protection":"IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106","Rated breaking capacity":"920 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"15 W AC-1 5 W AC-3","[Uc] control circuit voltage":"400 V AC 50 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 50/60 Hz (at 55 °C) Drop-out: 0.35...0.55 Uc 50/60 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"200 A (at 115 A (at <55 °C) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"45 VA, 50 Hz cos phi 0.3 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-40...60 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1100 A 40 °C - 10 s 640 A 40 °C - 30 s 520 A 40 °C - 1 min 400 A 40 °C - 3 min 320 A 40 °C - 10 min","[Ith] conventional free air thermal current":"200 A (at 40 °C)","Permissible ambient air temperature around the device":"60...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/84ade9fe707e41a9d5da28fbafe3d094.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC1F115V5/tesys-f-contactor-3p-3-no-ac3-440-v-115-a-coil-400-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F115V5/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F115V5 and get a price?","answer":"We source and quote the LC1F115V5 to order against an RFQ. Availability and current pricing are confirmed at the time of your quote request — submit an RFQ through this listing."},{"question":"What is the closest alternative to LC1F115V5 in the TeSys F family?","answer":"No official successor order code is listed. A current-production TeSys F contactor with the same 200 A AC-3 rating and 400 V AC coil may be footprint-compatible, but the exact pin-compatible replacement must be verified against the panel layout and control voltage."},{"question":"What compliance documentation does Schneider provide for LC1F115V5?","answer":"The contactor is designed to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. It carries overvoltage category III and protective treatment TH. Specific RoHS/REACH/UL declarations should be requested with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F115V5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F115V5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}