{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1400Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1400Q7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1400Q7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1400Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F1400Q7, 3-pole contactor, 1400 A AC-1, 380 V AC 50/60 Hz coil, plate mount.","salesMarkdown":"The Schneider Electric LC1F1400Q7 is a 3-pole TeSys F contactor rated for 1400 A in AC-1 utilisation category (resistive loads), with a 380 V AC control coil at 40...400 Hz. Plate-mounted, sized for panel integration at 438 mm wide by 332 mm tall by 238.6 mm deep. Short-time withstand (Icw) is 8000 A for 10 s, 6000 A for 30 s, tapering to 2600 A for 10 min — useful for coordinating with upstream fuses or breakers during a fault-clearing delay. The associated fuse recommendation is 1600 A gG at ≤ 440 V. Control circuit is AC only, 380 V nominal, with an operational range of 0.85...1.1 Uc and drop-out between 0.3...0.5 Uc. Inrush power is 2200 VA at cos φ 0.9; hold-in consumption drops to 36 VA. Opening time is 100...170 ms, closing 40...75 ms — the asymmetry matters for sequencing interlocks. Heat dissipation is 36 W total, 150 W per pole in AC-1 duty, so panel ventilation or spacing for that thermal load is needed. Standards coverage includes IEC 60947-4-1, EN 60947-1, EN 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1 — the UL/CSA marks clear it for North American panels. Rated insulation voltage is 1000 V per IEC/UL, 1500 V per VDE 0110 Group C. Impulse withstand is 8 kV, overvoltage category III. Protective treatment is TH (tropicalised) for humid environments. ## Integration notes Plate-mounted — no DIN-rail clip. Power circuit connections are bar-type (busbar cross-section up to 100 x 5 mm) or bolted; control circuit uses screw-clamp terminals accepting 1...4 mm² flexible or solid. Tightening torque is 58 N·m on the power side, 1.2 N·m on the control side. The 438 mm width and 332 mm height require a backplate or sub-panel with clearance for busbar runs and arc-chamber venting.","metaTitle":"Schneider Electric LC1F1400Q7 TeSys F Contactor, 1400 A AC-1","metaDescription":"Schneider Electric LC1F1400Q7 TeSys F contactor, 1400 A AC-1, 380 V AC 50/60 Hz coil. IEC 60947-4-1, UL/CSA. EOL phase — sourced to order against RFQ. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"238.6 mm","Range":"TeSys","Width":"438 mm","Height":"332 mm","Standards":"IEC 60947-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Operating time":"100...170 ms opening 40...75 ms closing","lifecycle_stage":"eol_hot","Heat dissipation":"36 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 1700 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 58 N.m","Compatibility code":"LC1F","Inrush power in VA":"2200 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Associated fuse rating":"1600 A gG at <= 440 V","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 100 x 5 mm Power circuit: bolted connection","Rated breaking capacity":"2100 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"150 W AC-1","[Uc] control circuit voltage":"380 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C 1000 V conforming to UL 60947-4-1","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"1400 A (at <40 °C) AC AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"36 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"8000 A 40 °C - 10 s 6000 A 40 °C - 30 s 4500 A 40 °C - 1 min 4000 A 40 °C - 3 min 2600 A 40 °C - 10 min","[Ith] conventional free air thermal current":"1400 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d54588a4f7e47be4b48ec870bf2c83c4.pdf","sourceUrl":"https://www.se.com/be/en/product/LC1F1400Q7/tesys-f-contactor-3p-3-no-ac1-1000-v-1400-a-coil-380-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1400Q7/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for LC1F1400Q7?","answer":"Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront; the part is sourced to order via independent distribution channels."},{"question":"What is the closest alternative to LC1F1400Q7 in the TeSys F family?","answer":"No official successor order code is listed in the lifecycle record. A parametric cross-reference within the TeSys F range would need to match the 1400 A AC-1 rating, 380 V AC coil, and 3-pole configuration — but without a documented replacement, each BOM substitution requires individual validation."},{"question":"What compliance documentation does this brand provide for LC1F1400Q7?","answer":"The contactor carries IEC 60947-4-1, EN 60947-1, EN 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1 standards. Rated insulation voltage is 1000 V per IEC/UL. Protective treatment is TH (tropicalised). The evidence does not list RoHS or REACH declarations specifically."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1400Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1400Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}