{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1504Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1504Q7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1504Q7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1504Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LC1F1504Q7, 4-pole contactor, 250 A AC-1, 380 V AC 40-400 Hz coil, plate mount.","salesMarkdown":"The Schneider Electric LC1F1504Q7 is a TeSys F series 4-pole contactor with a 380 V AC 40-400 Hz control coil, rated for 250 A in AC-1 utilisation category — meaning it's built for switching resistive loads like heaters or furnaces, not motor starting. The 4 NO power pole configuration and 250 A continuous rating at 440 V make it a heavy-duty line contactor for panel builders working on ovens, kilns, or large resistive banks. Heat dissipation runs 5.9 to 7.2 W total, so panel ventilation is minimal for a contactor this size. Control circuit is AC only, 380 V at 40-400 Hz, with operational limits of 0.85 to 1.1 Uc and drop-out between 0.2 and 0.55 Uc. Inrush power hits 770 VA at 20 °C, then hold-in drops to 8.1 VA — the coil draw matters for transformer sizing if you're feeding multiple contactors from a single control transformer. Closing time is 35 ms, opening 130 ms at rated voltage. Mechanical durability is rated at 10 million cycles, and the maximum operating rate is 2400 cycles per hour at 55 °C — that's one cycle every 1.5 seconds, fine for cyclic resistive loads but not for high-speed motor jogging. Ambient operating range is -40 to 60 °C, storage -60 to 80 °C, with no derating up to 3000 m altitude. Mounting is plate-only — no DIN-rail clip on this frame size, so plan for a backplate or mounting plate with the 171 mm depth, 200.5 mm width, and 170 mm height. Power circuit connections accept bar (25 x 3 mm busbar), ring terminals up to 120 mm², or bolted connection. Control wiring uses screw clamp terminals accepting 1 to 4 mm² flexible or solid, with tightening torque of 1.2 N.m for control and 18 N.m for power. IP2X front face with shrouds per IEC 60529 and VDE 0106 — not washdown-rated, so keep it in a closed panel. The LC1F1504Q7 complies with EN 60947-1, IEC 60947-1, JIS C8201-4-1, EN 60947-4-1, and IEC 60947-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Impulse withstand voltage is 8 kV, overvoltage category III. Protective treatment is TH (tropicalized) for humid environments. Associated fuse protection is 160 A aM or 250 A gG at <= 440 V.","metaTitle":"Schneider LC1F1504Q7 TeSys F Contactor, 250 A AC-1, 380 V Co","metaDescription":"Schneider Electric LC1F1504Q7 TeSys F 4-pole contactor, 250 A rated operational current in AC-1, 380 V AC 50/60 Hz coil. End-of-life status; sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"171 mm","Range":"TeSys","Width":"200.5 mm","Height":"170 mm","Standards":"EN 60947-1 IEC 60947-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-4-1","Operating time":"35 ms closing (at Uc) 130 ms opening (at Uc)","lifecycle_stage":"eol_hot","Heat dissipation":"5.9...7.2 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.35 mOhm - Ith 250 A 50 Hz","Device short name":"LC1F","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 18 N.m","Compatibility code":"LC1F","Inrush power in VA":"770 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"160 A aM at 250 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm Power circuit: lugs-ring terminals 1 cable(s) 120 mm² Power circuit: connector 1 cable(s) 120 mm² Power circuit: bolted connection","IP degree of protection":"IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106","Rated breaking capacity":"1200 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"22 W AC-1","[Uc] control circuit voltage":"380 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"250 A (at <40 °C) at <= 440 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-40...60 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1200 A 40 °C - 10 s 700 A 40 °C - 30 s 600 A 40 °C - 1 min 450 A 40 °C - 3 min 350 A 40 °C - 10 min","[Ith] conventional free air thermal current":"250 A (at 40 °C)","Permissible ambient air temperature around the device":"60...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/52cd6645381135cbdbb78910811cac95.pdf","sourceUrl":"https://www.se.com/hk/en/product/LC1F1504Q7/tesys-f-contactor-4p-4-no-ac1-440-v-250-a-coil-380-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1504Q7/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F1504Q7 and get a price?","answer":"The LC1F1504Q7 is available to order through independent industrial automation distributors. Submit an RFQ to receive a current price and availability quote — pricing and stock are confirmed at quote time."},{"question":"What are the key specifications of LC1F1504Q7?","answer":"The LC1F1504Q7 is a 4-pole contactor rated 250 A in AC-1 (resistive load) at <= 440 V, with a 380 V AC 40-400 Hz control coil. It measures 171 mm deep, 200.5 mm wide, 170 mm high, and mounts on a plate. Mechanical durability is 10 million cycles."},{"question":"What compliance standards does LC1F1504Q7 meet?","answer":"It complies with EN 60947-1, IEC 60947-1, JIS C8201-4-1, EN 60947-4-1, and IEC 60947-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Protective treatment is TH (tropicalized)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1504Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1504Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}