{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1504V7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1504V7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1504V7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1504V7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor, LC1F1504V7, 4-pole NO, 250 A AC-1 at ≤440 V, 400 V AC 50/60 Hz coil, plate mount, EOL lifecycle.","salesMarkdown":"## TeSys F 4-Pole Contactor, 250 A AC-1 — EOL Sourcing Note The Schneider Electric LC1F1504V7 is a TeSys F contactor with four normally-open power poles, rated 250 A in AC-1 utilisation category at ≤440 V and ≤40 °C — meaning it is sized for resistive loads such as heaters or large lighting banks, not motor starting. The 400 V AC control coil draws 770 VA inrush, holding at 8.1 VA. ## Dimensions, Mounting, and Wiring The LC1F1504V7 measures 171 mm deep by 200.5 mm wide by 170 mm high and mounts to a plate (not DIN rail). Power circuit connections accept bar (25 x 3 mm busbar), ring-terminal lugs up to 120 mm², or bolted connection; torque to 18 N·m. Control circuit uses screw-clamp terminals accepting 1 to 4 mm² flexible or solid, torqued to 1.2 N·m. IP2X front-face protection with shrouds per IEC 60529. Designed and tested to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1, impulse withstand voltage 8 kV, overvoltage category III. Protective treatment TH for tropical environments. Operating altitude 3000 m without derating. Associated fuse rating 160 A aM or 250 A gG at ≤440 V.","metaTitle":"Schneider LC1F1504V7 TeSys F Contactor, 250 A AC-1, 4 NO, 40","metaDescription":"Schneider Electric LC1F1504V7 TeSys F contactor, 250 A AC-1 resistive load, 4 NO, 400 V AC coil. EOL lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"171 mm","Range":"TeSys","Width":"200.5 mm","Height":"170 mm","Standards":"JIS C8201-4-1 EN 60947-1 IEC 60947-1 IEC 60947-4-1 EN 60947-4-1","Operating time":"35 ms closing (at Uc) 130 ms opening (at Uc)","lifecycle_stage":"eol_hot","Heat dissipation":"5.9...7.2 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.35 mOhm - Ith 250 A 50 Hz","Device short name":"LC1F","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 18 N.m","Compatibility code":"LC1F","Inrush power in VA":"770 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"160 A aM at 250 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm Power circuit: lugs-ring terminals 1 cable(s) 120 mm² Power circuit: connector 1 cable(s) 120 mm² Power circuit: bolted connection","IP degree of protection":"IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106","Rated breaking capacity":"1200 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"22 W AC-1","[Uc] control circuit voltage":"400 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"250 A (at <40 °C) at <= 440 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-40...60 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1200 A 40 °C - 10 s 700 A 40 °C - 30 s 600 A 40 °C - 1 min 450 A 40 °C - 3 min 350 A 40 °C - 10 min","[Ith] conventional free air thermal current":"250 A (at 40 °C)","Permissible ambient air temperature around the device":"60...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2c21c2aa47081d681c61f11512aa7d5d.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC1F1504V7/tesys-f-contactor-4p-4-no-ac1-440-v-250-a-coil-400-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1504V7/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F1504V7?","answer":"We source this EOL contactor to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What is the closest alternative to LC1F1504V7?","answer":"Within the TeSys F family, a functionally similar 4-pole NO contactor with a 400 V AC coil and comparable AC-1 rating would be the closest parametric match. Verify pole count, coil voltage, and mounting before substituting."},{"question":"What compliance documentation does Schneider provide for LC1F1504V7?","answer":"The contactor is certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage 1000 V, impulse withstand 8 kV, overvoltage category III. Standard documentation includes the declaration of conformity and test reports per those standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1504V7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1504V7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}