{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1504X6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1504X6","canonicalUrl":"https://aoctrl.com/schneider/LC1F1504X6","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1504X6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LC1F1504X6, 4-pole AC contactor, 250 A rated operational current (AC-1 at 440 V), 4 NO power poles, AC 60 Hz control.","salesMarkdown":"The LC1F1504X6 is a 4-pole contactor from the TeSys F series, rated 250 A in AC-1 utilisation category at ≤ 440 V — that's the resistive-load curve (heater banks, lighting, non-inductive furnaces). The 4 NO pole configuration means all four main poles are normally-open; there are no built-in NC auxiliary contacts on the power side, so any interlocking or status feedback must come from a separate auxiliary contact block added to the front. The control circuit is AC 60 Hz with a coil voltage rating of 600 V AC — verify your control transformer matches the frequency and voltage range, as the coil hold-in drops to 55 VA at 60 Hz. The contactor is plate-mounted, not DIN-rail snap-on, so factor in the panel drilling and the 159.3 lbf·in (18 N·m) power-circuit torque for the bolted connections. For motor loads, note that the 250 A figure is AC-1 resistive; the AC-3 motor-switching rating is lower (not listed in this evidence, but typical for this frame size). The associated fuse recommendation is 160 A aM or 250 A gG at ≤ 440 V, so the upstream protection should be sized to that curve, not the contactor's own thermal capacity. The IP2X front-face protection with shrouds keeps fingers out but is not washdown-rated — this is a panel-interior part, not a field-mounted enclosure. ## Deployment context In a panel, the LC1F1504X6 mounts to a plate — not a DIN rail — so the enclosure layout must include a drilled mounting surface. The power connections are bolted bars or ring terminals up to 120 mm²; the control circuit uses screw-clamp terminals accepting 1–4 mm² flexible or solid wire. The 12–16 W heat dissipation means the panel's thermal budget must account for the contactor's continuous resistive load; at 2400 cycles per hour maximum, the mechanical durability of 10 Mcycles is generous for a fixed-speed pump or conveyor contactor running a few cycles per minute.","metaTitle":"Schneider LC1F1504X6 TeSys F Contactor, 250 A AC-1, 4 NO, EO","metaDescription":"Schneider Electric LC1F1504X6 TeSys F 4-pole contactor, 250 A AC-1 at 440 V, 4 NO. EOL stage. Sourced to order against RFQ. Standards: IEC 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"6.7 in (171 mm)","Range":"TeSys","Width":"7.9 in (200.5 mm)","Height":"6.7 in (170 mm)","Category":"22336-CTR,F-LINE,AC,OPEN,NONREV","Standards":"EN 60947-4-1 EN 60947-1 JIS C8201-4-1 IEC 60947-4-1 IEC 60947-1","Operating time":"23...35 ms closing 5...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"12...16 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.35 mOhm - Ith 250 A 50 Hz","Device short name":"LC1F","Poles description":"4P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 159.3 lbf.in (18 N.m)","Compatibility code":"LC1F","Inrush power in VA":"660 VA, 60 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Control circuit type":"AC 60 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"160 A aM at 250 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bar 2 25 x 3 mm Power circuit lugs-ring terminals 1 0.2 in² (120 mm²) Power circuit connector 1 0.2 in² (120 mm²) Power circuit bolted connection","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1200 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","Power dissipation per pole":"22 W AC-1","[Uc] control circuit voltage":"600 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"250 A (at <104 °F (40 °C)) at <= 440 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"55 VA, 60 Hz 0.3 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"-40...140 °F (-40...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1200 A 104 °F (40 °C) - 10 s 700 A 104 °F (40 °C) - 30 s 600 A 104 °F (40 °C) - 1 min 450 A 104 °F (40 °C) - 3 min 350 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"250 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"140...158 °F (60...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad3cc737c31e4961cd7d78cbe020c4e7.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1F1504X6/tesys-f-contactor-4p-4-no-ac1-440-v-250-a-coil-600-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1504X6/alternatives.json"},"ai":{"faq":[{"question":"What is the rated operational current of LC1F1504X6?","answer":"The rated operational current (Ie) is 250 A at ≤ 104 °F (40 °C) at ≤ 440 V in AC-1 utilisation category."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1504X6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1504X6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}