{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F150G5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F150G5","canonicalUrl":"https://aoctrl.com/schneider/LC1F150G5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F150G5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F150G5, 3-pole contactor, 250 A AC-3 rated operational current, 75 kW at 400 V AC, 127-132 V AC 50 Hz coil.","salesMarkdown":"## Motor power across voltage taps The LC1F150G5 delivers 75 kW at 380–400 V AC, 80 kW at 415 V and 440 V, 90 kW at 500 V, and 100 kW at 660–690 V AC — all in AC-3 switching category. At 220–230 V it handles 40 kW. For AC-4 reversing or inching duty, the rating drops to 22 kW at 400 V. These figures define the motor frame size this contactor can handle across common global supply voltages. Designed to IEC 60947-4-1 and IEC 60947-1, with JIS C8201-4-1 for Japanese markets. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Overvoltage category III suits fixed-installation distribution panels. The front face carries IP2X protection with shrouds fitted, meeting IEC 60529 and VDE 0106 for finger-safe touch protection. The manufacturer lists this contactor as end-of-life (EOL). Given the EOL status, verifying fit with the existing panel layout and control voltage is the first step for a last-time buy quantity. ## Panel integration Mounts to a plate (not DIN rail). Dimensions: 6.7 in (171 mm) depth, 6.4 in (163.5 mm) width, 6.7 in (170 mm) height. Power connections are bolted bar or lug-ring terminals accepting up to 120 mm²; control circuit wiring uses screw-clamp terminals for 1–4 mm² flexible or solid conductors. Tightening torque: 159.3 lbf.in (18 N.m) on the power circuit, 10.6 lbf.in (1.2 N.m) on control. The 0.35 mOhm average impedance at 250 A 50 Hz means heat dissipation runs 12–16 W total, with 22 W per pole in AC-1 and 8 W per pole in AC-3 — factor this into enclosure thermal calculations.","metaTitle":"LC1F150G5 TeSys F Contactor, 250 A AC-3, 75 kW at 400 V","metaDescription":"Schneider Electric LC1F150G5 TeSys F contactor, 250 A AC-3, 75 kW at 400 V. End-of-life status; sourced to order against RFQ. Standards: IEC 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"6.7 in (171 mm)","Range":"TeSys","Width":"6.4 in (163.5 mm)","Height":"6.7 in (170 mm)","Category":"22336-CTR,F-LINE,AC,OPEN,NONREV","Standards":"EN 60947-1 IEC 60947-4-1 IEC 60947-1 JIS C8201-4-1 EN 60947-4-1","Motor power kW":"75 kW at 380...400 V AC 50/60 Hz (AC-3) 80 kW at 415 V AC 50/60 Hz (AC-3) 80 kW at 440 V AC 50/60 Hz (AC-3) 90 kW at 500 V AC 50/60 Hz (AC-3) 100 kW at 660...690 V AC 50/60 Hz (AC-3) 40 kW at 220...230 V AC 50/60 Hz (AC-3) 22 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"23...35 ms closing 5...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"12...16 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.35 mOhm - Ith 250 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 159.3 lbf.in (18 N.m)","Compatibility code":"LC1F","Inrush power in VA":"550 VA, 50 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Control circuit type":"AC 50 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-4 AC-1 AC-3","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"160 A aM at 250 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bar 2 25 x 3 mm Power circuit lugs-ring terminals 1 0.2 in² (120 mm²) Power circuit connector 1 0.2 in² (120 mm²) Power circuit bolted connection","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1200 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","Power dissipation per pole":"22 W AC-1 8 W AC-3","[Uc] control circuit voltage":"127...132 V AC 50 Hz","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"250 A (at 150 A (at <131 °F (55 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"45 VA, 50 Hz 0.3 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"-40...140 °F (-40...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1200 A 104 °F (40 °C) - 10 s 700 A 104 °F (40 °C) - 30 s 600 A 104 °F (40 °C) - 1 min 450 A 104 °F (40 °C) - 3 min 350 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"250 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"140...158 °F (60...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7b9d51c37e4ca3d53eaf9afd951e21f8.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1F150G5/tesys-f-contactor-3p-3-no-ac3-440-v-250-a-coil-127-132-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F150G5/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of LC1F150G5?","answer":"Rated operational current is 250 A in AC-3 at ≤ 440 V. Motor power is 75 kW at 400 V AC, 80 kW at 415/440 V, 90 kW at 500 V, and 100 kW at 660–690 V. Coil voltage is 127–132 V AC 50 Hz."},{"question":"What compliance documentation does this contactor carry?","answer":"It complies with IEC 60947-4-1, IEC 60947-1, JIS C8201-4-1, and EN 60947-4-1. Rated insulation voltage is 1000 V per IEC and 1500 V per VDE 0110 group C. Overvoltage category III."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F150G5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F150G5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}