{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F150KUE","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F150KUE","canonicalUrl":"https://aoctrl.com/schneider/LC1F150KUE","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F150KUE","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LC1F150KUE, 3-pole contactor, 250 A rated operational current (AC-3 at ≤440 V), 100-250 V AC/DC control circuit, plate mount.","salesMarkdown":"The LC1F150KUE is a 3-pole contactor from the TeSys F series, rated for 250 A in AC-3 duty at ≤440 V. AC-3 is the standard utilisation category for squirrel-cage motor starting. The control circuit accepts 100-250 V AC 50/60 Hz or 100-380 V DC, with a wide operational range: 85-275 V AC and 85-418 V DC at 55 °C. Drop-out thresholds are 0-60 V AC and 0-45 V DC, giving clean release margins. The coil is electronic, compatible with PLC 24 V DC inputs per IEC 61131-2 Type 2, though the coil voltage itself is the higher range — the PLC compatibility refers to the input interface, not the coil drive. Rated breaking capacity is 1200 A per IEC 60947-4-1, and making capacity is 1500 A. The associated fuse recommendation is 315 A gG or 200 A aM at ≤440 V. Mounts on a plate, not a DIN rail. The power circuit uses bolted connections accepting bars, busbars (25 x 3 mm), lugs, or connectors up to 120 mm². Control wiring is via screw-clamp terminals for 0.2-2.5 mm² solid or flexible wire. Tightening torque is 18 N·m on the power side, 0.6 N·m on control — a torque wrench is expected for the power terminals. Dimensions are 171 mm deep, 163.5 mm wide, 170 mm tall. Protective treatment TH indicates tropicalisation — resistance to heat and humidity, relevant for non-conditioned environments.","metaTitle":"Schneider TeSys F LC1F150KUE Contactor, 250 A AC-3, 100-250","metaDescription":"Schneider Electric TeSys F LC1F150KUE contactor. 250 A rated operational current (AC-3 at 440 V). 100-250 VAC/DC control coil. EN/IEC 60947-4-1. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"171 mm","Range":"TeSys","Width":"163.5 mm","Height":"170 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1","Operating time":"40...80 ms closing 6...54 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"2.2...5.5 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.35 mOhm - Ith 250 A 50 Hz","Device short name":"LC1F","Inrush power in W":"270...320 W (at 20 °C)","Poles description":"3P","Tightening torque":"Power circuit: 18 N.m Control circuit: 0.6 N.m","Compatibility code":"LC1F","Inrush power in VA":"280...310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)","Operating altitude":"3000 m without derating","Input compatibility":"PLC 24 V DC conforming to IEC 61131-2 Type 2","Control circuit type":"AC at 50/60 Hz electronic DC","Input voltage limits":"0...5 V off-state for PLC input 11...30 V on-state for PLC input","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-4","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Associated fuse rating":"315 A gG at 200 A aM at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm Power circuit: lugs-ring terminals 1 cable(s) 120 mm² Power circuit: connector 1 cable(s) 120 mm² Power circuit: bolted connection Control circuit: screw clamp terminals 1 cable(s) 0.2...2.5 mm²solid Control circuit: screw clamp terminals 1 cable(s) 0.2...2.5 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 0.25...2.5 mm²flexible with cable end","Rated breaking capacity":"1200 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Irms rated making capacity":"1500 A conforming to IEC 60947-4-1","Power dissipation per pole":"22 W AC-1 8 W AC-3","[Uc] control circuit voltage":"100...250 V AC 50/60 Hz 100...380 V DC","[Ui] rated insulation voltage":"380 V conforming to IEC 60947-4-1","Control circuit voltage limits":"Operational: 85...275 V AC 50/60 Hz (at 55 °C) Operational: 85...418 V DC (at 55 °C) Drop-out: 0...60 V AC 50/60 Hz (at 55 °C) Drop-out: 0...45 V DC (at 55 °C)","Hold-in power consumption in W":"2.5...4 W at 20 °C","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"250 A (at 150 A (at <55 °C) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"4.5...7 VA, 50/60 Hz cos phi 0.5 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-40...60 °C","[Uimp] rated impulse withstand voltage":"6 kV","[Icw] rated short-time withstand current":"1200 A 40 °C - 10 s 700 A 40 °C - 30 s 600 A 40 °C - 1 min 450 A 40 °C - 3 min 350 A 40 °C - 10 min","[Ith] conventional free air thermal current":"250 A (at 40 °C)","Permissible ambient air temperature around the device":"60...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/680a92fe436d7136355c9444f49d418d.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F150KUE/tesys-f-contactor-3p-3-no-ac3-440-v-150-a-coil-100250v-ac-100380v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F150KUE/alternatives.json"},"ai":{"faq":[{"question":"What control voltage does the LC1F150KUE use?","answer":"100-250 V AC 50/60 Hz or 100-380 V DC. The coil operates down to 85 V and up to 275 V AC or 418 V DC at 55 °C."},{"question":"What standards does the LC1F150KUE comply with?","answer":"EN/IEC 60947-1 and EN/IEC 60947-4-1. Overvoltage category III. Protective treatment TH for tropical environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F150KUE","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F150KUE when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}