{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F150P5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F150P5","canonicalUrl":"https://aoctrl.com/schneider/LC1F150P5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F150P5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, LC1F150P5, 3-pole contactor, 250 A rated operational current (AC-3), 230 V AC 50 Hz coil, plate mount, 171 x 163.5 x 170 mm.","salesMarkdown":"The LC1F150P5: The 250 A AC-3 rating governs motor switching — that's the current the contactor can make and break across a typical induction motor load. For resistive heating (AC-1), the thermal current Ith is 250 A at 50 Hz, with 22 W dissipation per pole. The 0.35 mOhm average impedance per pole at 250 A gives a voltage drop worth checking against your load's minimum operating voltage. Plate-mounted, not DIN-rail — plan for a drilled backplate or sub-panel. Dimensions are 171 mm deep, 163.5 mm wide, 170 mm tall. Power connections accept bar (25 x 3 mm busbar), ring lugs up to 120 mm², or bolted connection. Control wiring uses screw clamp terminals, 1 to 4 mm² flexible or solid. Torque power circuit connections to 18 N·m, control circuit to 1.2 N·m. Front face with shrouds achieves IP2X. ## Standards and Environmental Range Certified to IEC 60947-4-1 and EN 60947-4-1, the standard for contactors and motor-starters. Rated insulation voltage is 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 Group C. Overvoltage category III suits fixed-installation distribution panels. Protective treatment is TH (tropicalized) for humid environments.","metaTitle":"Schneider Electric LC1F150P5 TeSys F Contactor, 250 A AC-3,","metaDescription":"LC1F150P5 TeSys F contactor, 250 A rated operational current (AC-3), 230 V 50 Hz coil. End-of-life status; sourced to order against RFQ. Motor power up to 100 kW at 690 V. IEC 6094","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"171 mm","Width":"163.5 mm","Height":"170 mm","Current":"250 A (at 150 A (at <55 °C) at <= 440 V AC-3","Voltage":"<= 460 V DC","Application":"Resistive load, Motor control","Coil Voltage":"230 V AC 50 Hz","Operating Time":"23...35 ms closing 5...15 ms opening","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"1200 A conforming to IEC 60947-4-1","Insulation Voltage Ui":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Temp Operating Max":"60 °C","Temp Operating Min":"-40 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 50 Hz","Utilization Category":"AC-4 AC-1 AC-3","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-40...60 °C","Permissible Ambient Air Temperature Around The Device":"60...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8df297e2a0887cdf58e97b5a079c7672.pdf","sourceUrl":"https://www.se.com/th/en/product/LC1F150P5/tesys-f-contactor-3p-3-no-ac3-440-v-250-a-coil-230-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F150P5/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F150P5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F150P5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}