{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F150Q522L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F150Q522L","canonicalUrl":"https://aoctrl.com/schneider/LC1F150Q522L","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F150Q522L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, 3-pole contactor, LC1F150Q522L, 250 A AC-3 rated operational current, 380 V AC 50 Hz coil, 3 NO + 2 NO + 2 NC auxiliary contacts.","salesMarkdown":"The Schneider Electric LC1F150Q522L is a 3-pole contactor from the TeSys F series, rated for 250 A operational current in AC-3 duty (motor switching) at up to 440 V AC. It carries a 380 V AC 50 Hz control coil and is built to IEC 60947-4-1, with a rated insulation voltage of 1000 V per that standard and 1500 V per VDE 0110 group C. ## Motor Power Ratings and Application This contactor switches motor loads across a wide voltage range: 75 kW at 380–400 V AC, 80 kW at 415 V, 90 kW at 500 V, and 100 kW at 660–690 V, all in AC-3. For UL/CSA installations, it is rated 100 hp at 460 V AC and 125 hp at 575 V AC. The AC-4 rating (reversing/inching duty) is 22 kW at 400 V. It also handles resistive loads (AC-1) and is specified for both motor control and resistive load applications. ## Physical Integration and Wiring The contactor measures 6.4 in wide by 6.7 in deep by 11.9 in high (163.5 x 171 x 301 mm) and is plate-mounted. Power circuit connections use bolted terminals or ring lugs up to 120 mm²; control circuit wiring uses screw clamp terminals accepting 1–4 mm² flexible or solid wire. Tightening torque is 159.3 lbf·in (18 N·m) for power and 10.6 lbf·in (1.2 N·m) for control. The front face with shrouds provides IP2X protection per IEC 60529. ## Auxiliary Contacts and Control Circuit Built-in auxiliary contacts are 2 NO + 2 NC. The control coil operates at 380 V AC 50 Hz, with an operational voltage range of 0.85–1.1 Uc and a drop-out range of 0.35–0.55 Uc. Inrush power is 550 VA at 50 Hz; hold-in consumption is 45 VA. Closing time is 23–35 ms, opening 5–15 ms. The contactor withstands vibration at 6 Gn (closed) and shock at 15 Gn (closed). Maximum operating rate is 2400 cycles per hour at 55 °C. Heat dissipation is 12–16 W, with 22 W per pole in AC-1 and 8 W per pole in AC-3.","metaTitle":"Schneider Electric LC1F150Q522L TeSys F Contactor, 250 A AC-","metaDescription":"Schneider Electric LC1F150Q522L TeSys F contactor. 250 A rated operational current (AC-3), 380 V AC 50 Hz coil. EOL lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"6.7 in (171 mm)","Width":"6.4 in (163.5 mm)","Height":"11.9 in (301 mm)","Category":"US10NET39997","Standards":"IEC 60947-4-1 IEC 60947-1 EN 60947-1 JIS C8201-4-1 EN 60947-4-1","Motor power kW":"65 kW at 1000 V AC 50/60 Hz (AC-3) 75 kW at 380...400 V AC 50/60 Hz (AC-3) 80 kW at 415 V AC 50/60 Hz (AC-3) 80 kW at 440 V AC 50/60 Hz (AC-3) 90 kW at 500 V AC 50/60 Hz (AC-3) 100 kW at 660...690 V AC 50/60 Hz (AC-3) 40 kW at 220...230 V AC 50/60 Hz (AC-3) 22 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"23...35 ms closing 5...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"12...16 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.35 mOhm - Ith 250 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 159.3 lbf.in (18 N.m)","Inrush power in VA":"550 VA, 50 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-4 AC-1 AC-3","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed6 Gn, 5...300 Hz Shocks contactor open9 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms","Nbr. of units in pkg.":"1","Associated fuse rating":"160 A aM at 250 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bolted connection Power circuit 2 bars 25 x 3 mm Power circuit lugs-ring terminals 1 0.2 in² (120 mm²) Power circuit connector 1 0.2 in² (120 mm²)","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1200 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","motor power HP (UL / CSA)":"40 hp at 200 V AC 50 hp at 230 V AC 100 hp at 460 V AC 125 hp at 575 V AC","Power dissipation per pole":"22 W AC-1 8 W AC-3","[Uc] control circuit voltage":"380 V AC 50 Hz","Auxiliary contact composition":"2 NO + 2 NC","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"250 A (at 150 A (at <131 °F (55 °C)) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"-40...140 °F (-40...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1200 A 104 °F (40 °C) - 10 s 700 A 104 °F (40 °C) - 30 s 600 A 104 °F (40 °C) - 1 min 450 A 104 °F (40 °C) - 3 min 350 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"250 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"140...158 °F (60...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2b6835fc74115f7e7c08cd6b2001a0be.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1F150Q522L/tesys-f-nonreversing-contactor-3p-open-600v-150a-380vac-50hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F150Q522L/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC1F150Q522L?","answer":"Rated operational current is 250 A in AC-3 at ≤ 440 V AC. Motor power ranges from 75 kW at 380–400 V AC-3 to 100 kW at 660–690 V AC-3. The control coil is 380 V AC 50 Hz. It has 3 main poles NO and 2 NO + 2 NC auxiliary contacts."},{"question":"Where can I buy the LC1F150Q522L?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What standards does the LC1F150Q522L comply with?","answer":"It complies with IEC 60947-4-1, IEC 60947-1, EN 60947-1, JIS C8201-4-1, and EN 60947-4-1. Rated insulation voltage is 1000 V per IEC and 1500 V per VDE 0110 group C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F150Q522L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F150Q522L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}