{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F150V5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F150V5","canonicalUrl":"https://aoctrl.com/schneider/LC1F150V5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F150V5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F150V5, 3-pole contactor, 250 A rated operational current, 75 kW at 400 V AC (AC-3), 400 V AC 50 Hz coil, plate mount, EOL phase.","salesMarkdown":"It carries a rated operational current of 250 A in AC-3 duty at ≤ 440 V and switches motors up to 75 kW at 380–400 V AC, 80 kW at 415 V, and 100 kW at 660–690 V. The coil is 400 V AC 50 Hz, drawing 550 VA inrush and 45 VA hold-in. ## Lifecycle Status: End-of-Life (EOL) — What That Means for You The LC1F150V5 is in an end-of-life (EOL) phase. Schneider Electric no longer manufactures this order code. Sourcing is through independent distribution against an RFQ. The 250 A AC-3 rating is the motor-switching current — it governs the maximum full-load current of a squirrel-cage motor the contactor can break under starting conditions. That translates to 75 kW on a 400 V supply. The AC-1 rating (resistive load) is higher, but for motor control, AC-3 is the one that decides fit. The contactor also carries an AC-4 rating (22 kW at 400 V) for plugging or inching duty, where the load is switched under full stall current. The insulation voltage is 1000 V, and the overvoltage category is III, meaning it's designed for fixed-installation panels, not plug-in equipment. Mounts to a plate — not DIN rail, so plan for bolt-down installation with the 25 x 3 mm busbar or ring-terminal connections on the power circuit. The control circuit uses screw-clamp terminals accepting 1–4 mm² flexible or solid wire. Dimensions are 170 mm high, 163.5 mm wide, 171 mm deep. The front face carries IP2X protection with shrouds, meaning finger-safe from the front once shrouded, but the sides and bottom are open for ventilation. Heat dissipation runs 12–16 W total, with 8 W per pole in AC-3 and 22 W per pole in AC-1 — factor that into panel thermal calculations if it's in a sealed enclosure.","metaTitle":"Schneider TeSys F LC1F150V5 Contactor, 250 A, 75 kW AC-3, EO","metaDescription":"Schneider Electric TeSys F LC1F150V5 3-pole contactor, 250 A rated operational current, 75 kW at 400 V AC-3. EOL phase. Sourced to order against RFQ. IEC 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"171 mm","Width":"163.5 mm","Height":"170 mm","Current":"250 A (at 150 A (at <55 °C) at <= 440 V AC-3","Voltage":"<= 460 V DC","Application":"Resistive load, Motor control","Coil Voltage":"400 V AC 50 Hz","Operating Time":"23...35 ms closing 5...15 ms opening","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"1200 A conforming to IEC 60947-4-1","Insulation Voltage Ui":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Temp Operating Max":"60 °C","Temp Operating Min":"-40 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 50 Hz","Utilization Category":"AC-4 AC-3 AC-1","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-40...60 °C","Permissible Ambient Air Temperature Around The Device":"60...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e3741d8bef272f8aae09a27c6e7a3ecc.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC1F150V5/tesys-f-contactor-3p-3-no-ac3-440-v-250-a-coil-400-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F150V5/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F150V5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F150V5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}