{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1854E7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1854E7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1854E7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1854E7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F1854E7, 4-pole contactor, 275 A AC-1 rated operational current, 48 V AC 40-400 Hz control circuit, plate mount.","salesMarkdown":"Its headline rating is 275 A at ≤ 440 V AC-1 (at < 40 °C), meaning it can continuously carry and break resistive loads up to that current level — think large heating banks, furnace elements, or industrial ovens where inrush is minimal. The 48 V AC control coil (40-400 Hz) pulls in at 1070 VA inrush and holds at 9.9 VA; the operating limits are 0.85-1.1 Uc for pickup and 0.2-0.55 Uc for dropout at 55 °C, so verify your control transformer sizing against the inrush figure if the coil circuit is shared with other loads. Rated insulation voltage is 1000 V per IEC 60947-4-1, with an impulse withstand of 8 kV (overvoltage category III), so it's suitable for direct panel connection on 400 V or 690 V line supplies. The 4 NO main poles are rated for 275 A continuous in AC-1; for motor duty (AC-3) the power dissipation per pole jumps to 12 W vs 25 W in AC-1, reflecting the higher switching stress of inductive loads. ## Mounting, wiring, and panel integration This contactor mounts to a plate (not DIN rail), so factor in drilling and tapping for the 4-point baseplate. Dimensions are 208.5 mm wide × 174 mm high × 181 mm deep — it's a substantial frame that needs clear access for the power circuit connections. Power terminals accept bar (25 × 3 mm busbar), ring lugs, or bolted connections for up to 150 mm² cable; the tightening torque is 18 N·m on the power side. Control circuit wiring uses screw clamp terminals accepting 1-4 mm² flexible or solid, torqued to 1.2 N·m. The IP2X front face with shrouds meets IEC 60529 and VDE 0106 for finger-safe front access. Heat dissipation runs 8-9.8 W total, with 25 W per pole in AC-1 duty. In a sealed enclosure, that heat adds up — allow ventilation or derating if the panel ambient exceeds 55 °C. The TH protective treatment indicates tropicalisation for humid environments, which is standard on TeSys F contactors but worth noting if the gear lives in a non-conditioned plant space. The contactor is designed and certified to IEC 60947-4-1, EN 60947-4-1, IEC 60947-1, EN 60947-1, and JIS C8201-4-1. Rated breaking capacity is 1480 A per IEC 60947-4-1. Associated fuse protection is 200 A aM or 315 A gG at ≤ 440 V. The average impedance per pole is 0.33 mΩ at Ith 275 A, 50 Hz. For cross-border compliance documentation (RoHS, REACH, UL), the manufacturer's standard declarations apply — confirm with your compliance team if specific cert copies are needed for your jurisdiction.","metaTitle":"Schneider Electric LC1F1854E7 TeSys F Contactor, 275 A AC-1,","metaDescription":"Schneider Electric LC1F1854E7 TeSys F contactor, 275 A rated operational current in AC-1, 48 V AC 40-400 Hz coil. EOL status; sourced to order against RFQ. Complies with IEC 60947-","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"181 mm","Width":"208.5 mm","Height":"174 mm","Current":"275 A (at <40 °C) at <= 440 V AC-1","Voltage":"690 V AC 50/60 Hz","Application":"Resistive load","Coil Voltage":"48 V AC 40...400 Hz","Operating Time":"35 ms closing at Uc) 130 ms opening at Uc)","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"1480 A conforming to IEC 60947-4-1","Insulation Voltage Ui":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 40...400 Hz","Utilization Category":"AC-1","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...55 °C","Permissible Ambient Air Temperature Around The Device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/302249f19ddbce118f5041b9763b82d2.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F1854E7/tesys-f-contactor-4p-4-no-ac1-440-v-275-a-coil-48-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1854E7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1854E7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1854E7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}