{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F1854Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F1854Q7","canonicalUrl":"https://aoctrl.com/schneider/LC1F1854Q7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F1854Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F1854Q7, 4-pole contactor, 275 A AC-1 rated operational current, 380 V AC 40-400 Hz coil, plate mount.","salesMarkdown":"The LC1F1854Q7 is flagged end-of-life (EOL) by the manufacturer. The headline rating is 275 A at ≤ 440 V in AC-1 utilisation category (resistive load). AC-1 is the continuous-current rating for heater banks, lighting, or transformer primary switching — not motor starting. For motor duty (AC-3), the power dissipation per pole drops to 12 W versus 25 W in AC-1, so the contactor's thermal capacity is sized for the resistive curve. The 4 NO power poles are all normally open; there are no built-in auxiliary contacts on this base unit. The control circuit is a 380 V AC coil rated for 40–400 Hz, with an inrush of 1070 VA and a hold-in consumption of 9.9 VA. The coil pickup range is 0.85–1.1 Uc at 55 °C; dropout occurs between 0.2 and 0.55 Uc. This means a 380 V nominal coil will hold in down to roughly 323 V and drop out between 76 V and 209 V — relevant for brownout coordination in a control panel. The contactor is plate-mounted (not DIN-rail), so panel layout must account for the 181 mm depth, 208.5 mm width, and 174 mm height. Power-circuit connections accept bar (25 x 3 mm busbar), lugs (150 mm² cable), or bolted connections — typical for a panel builder wiring a high-current resistive load bank. The part is certified to IEC 60947-4-1 and EN 60947-4-1 (the contactor standard), plus IEC 60947-1 and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1, with an impulse withstand of 8 kV. The front face carries IP2X protection with shrouds — finger-safe but not washdown-rated. ## Deployment Context This contactor is sized for a 275 A resistive load in a panel — typically a large oven, furnace, or transformer bank. The plate-mount form factor and bar/lug power connections mean it integrates into a busbar system, not a DIN-rail assembly. The 380 V AC coil ties directly into a 380 V control transformer; no DC supply or rectifier is needed.","metaTitle":"Schneider Electric LC1F1854Q7 TeSys F Contactor, 275 A AC-1,","metaDescription":"Schneider Electric LC1F1854Q7 TeSys F contactor, 275 A rated operational current (AC-1), 4 NO poles, 380 V AC coil. End-of-life (EOL) status; sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"181 mm","Width":"208.5 mm","Height":"174 mm","Current":"275 A (at <40 °C) at <= 440 V AC-1","Voltage":"690 V AC 50/60 Hz","Application":"Resistive load","Coil Voltage":"380 V AC 40...400 Hz","Operating Time":"35 ms closing at Uc) 130 ms opening at Uc)","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"1480 A conforming to IEC 60947-4-1","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 40...400 Hz","Utilization Category":"AC-1","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...55 °C","Permissible Ambient Air Temperature Around The Device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5959d845ac7d59cc238d23fe4c87eb6a.pdf","sourceUrl":"https://www.se.com/za/en/product/LC1F1854Q7/tesys-f-contactor-4p-4-no-ac1-440-v-275-a-coil-380-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F1854Q7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F1854Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F1854Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}