{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F185B722L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F185B722L","canonicalUrl":"https://aoctrl.com/schneider/LC1F185B722L","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F185B722L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F185B722L, 3-pole contactor, 275 A AC-3 rated operational current, 90 kW at 380-400 V, 24 V AC coil, end-of-life status.","salesMarkdown":"The Schneider Electric LC1F185B722L is a 3-pole TeSys F contactor rated for 275 A in AC-3 duty (motor switching) and 90 kW at 380–400 V AC. The 24 V AC control coil draws 805 VA inrush at 50 Hz and 55 VA holding. It carries 2 NO + 2 NC auxiliary contacts built in. For resistive loads (AC-1), the same pole set handles higher current; the power dissipation per pole climbs to 25 W in AC-1 versus 12 W in AC-3, so thermal management in the enclosure matters if you run it near the resistive limit. Motor power is listed per voltage: 90 kW at 380–400 V, 100 kW at 415 V and 440 V, 110 kW at 500 V and 660–690 V, and 55 kW at 220–230 V. The UL/CSA horsepower ratings run 50 hp at 200 V up to 150 hp at 575 V — useful if the panel ships to a North American site. The contactor is rated for 1000 V insulation (IEC) and 1500 V (VDE 0110 Group C), with overvoltage category III. That means it's designed for fixed-installation distribution panels, not for surge-prone outdoor feeders. For high-duty applications like frequent conveyor indexing, that rate sets the practical limit. Mounting is plate-based, not DIN rail — the footprint is 305 mm high, 168.5 mm wide, 181 mm deep. Power connections use bolted bars (2 x 25 x 3 mm) or ring terminals up to 150 mm². Control wiring is screw-clamp, accepting 1–4 mm² flexible or solid. The front face with shrouds carries IP2X protection (finger-safe). Associated fuse sizing: 200 A aM or 315 A gG at ≤ 440 V. The rated breaking capacity is 1480 A per IEC 60947-4-1, which governs its ability to clear a fault without welding. Designed and certified to EN 60947-1, IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. The TH protective treatment indicates it's tropicalized — suitable for humid or mildly corrosive environments.","metaTitle":"Schneider Electric LC1F185B722L TeSys F Contactor, 275 A AC-","metaDescription":"Schneider Electric LC1F185B722L TeSys F contactor, 3-pole, 275 A AC-3 rated operational current, 90 kW at 400 V. End-of-life (EOL) status; sourced to order. EN/IEC 60947 certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"7.1 in (181 mm)","Width":"6.6 in (168.5 mm)","Height":"12.008 in (305 mm)","Category":"39997-CANADIAN PRODUCTS","Standards":"EN 60947-1 IEC 60947-4-1 EN 60947-4-1 IEC 60947-1 JIS C8201-4-1","Motor power kW":"90 kW at 380...400 V AC 50/60 Hz 100 kW at 415 V AC 50/60 Hz 100 kW at 440 V AC 50/60 Hz 110 kW at 500 V AC 50/60 Hz 110 kW at 660...690 V AC 50/60 Hz 100 kW at 1000 V AC 50/60 Hz 55 kW at 220...230 V AC 50/60 Hz","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"18...24 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.33 mOhm - Ith 275 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 159.3 lbf.in (18 N.m)","Inrush power in VA":"970 VA, 60 Hz 0.3 68 °F (20 °C)) 805 VA, 50 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-1","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Shocks contactor closed15 Gn for 11 ms Vibrations contactor closed5 Gn, 5...300 Hz Shocks contactor open7 Gn for 11 ms","Nbr. of units in pkg.":"1","Associated fuse rating":"200 A aM at 315 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bolted connection Power circuit 2 bars 25 x 3 mm Power circuit lugs-ring terminals 1 0.2 in² (150 mm²) Power circuit connector 1 0.2 in² (150 mm²)","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1480 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","motor power HP (UL / CSA)":"50 hp at 200 V AC 60 hp at 230 V AC 125 hp at 460 V AC 150 hp at 575 V AC","Power dissipation per pole":"12 W AC-3 25 W AC-1","[Uc] control circuit voltage":"24 V AC 40...400 Hz","Auxiliary contact composition":"2 NO + 2 NC","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.2...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"275 A (at 185 A (at <131 °F (55 °C)) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) 66 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1500 A 104 °F (40 °C) - 10 s 920 A 104 °F (40 °C) - 30 s 740 A 104 °F (40 °C) - 1 min 500 A 104 °F (40 °C) - 3 min 400 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"275 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/86ada129c47f7a4d5c088d3854d169b8.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1F185B722L/tesys-f-nonreversing-contactor-3p-open-600v-185a-24vac-40400hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F185B722L/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the LC1F185B722L?","answer":"We can source and quote the LC1F185B722L to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key motor power ratings for this contactor?","answer":"The LC1F185B722L is rated for 90 kW at 380–400 V AC, 100 kW at 415 V and 440 V, and 110 kW at 500 V and 660–690 V. UL/CSA ratings go up to 150 hp at 575 V."},{"question":"What is the control voltage and coil consumption?","answer":"The coil is 24 V AC, 40–400 Hz. Inrush is 805 VA at 50 Hz and 970 VA at 60 Hz; holding power is 55 VA at 50 Hz and 66 VA at 60 Hz."},{"question":"Does this contactor meet UL or CSA standards?","answer":"It carries UL/CSA horsepower ratings (50–150 hp depending on voltage) and is designed to EN/IEC 60947-4-1 and JIS C8201-4-1. The TH treatment indicates tropicalization for humid environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F185B722L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F185B722L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}