{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F185D7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F185D7","canonicalUrl":"https://aoctrl.com/schneider/LC1F185D7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F185D7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor, LC1F185D7, 3-pole, 185 A AC-3 at ≤440 V, 42 V AC 40-400 Hz coil, 90 kW at 380-400 V AC-3.","salesMarkdown":"The LC1F185D7 is a 3-pole TeSys F contactor from Schneider Electric, rated for switching motor loads up to 185 A in AC-3 duty (≤440 V) — that's the current it can make and break under the inductive load of a squirrel-cage motor during starting and running. At 380-400 V AC, that translates to 90 kW motor power; at 415 V it handles 100 kW, and at 500 V it still delivers 110 kW. The 42 V AC control coil (40-400 Hz) pulls 1070 VA inrush and holds at 9.9 VA, with a dropout range of 0.2-0.55 Uc — useful to know if you're integrating into a control transformer circuit with voltage sag. The contactor also carries AC-1 (resistive load) and AC-4 (plugging/inching) ratings, with a rated breaking capacity of 1480 A per IEC 60947-4-1. The 0.33 mOhm average impedance at 275 A Ith means heat dissipation runs 8-9.8 W total, or 12 W per pole in AC-3 and 25 W per pole in AC-1 — factor that into your panel thermal budget. This part is end-of-life hot (EOL hot) — Schneider has discontinued production and the last-time-buy window is closed or closing. Mounts to a plate (not DIN rail), with dimensions 174 mm high x 168.5 mm wide x 181 mm deep. Power circuit connections accept bar (25 x 3 mm busbar), ring terminals up to 150 mm², or bolted connections. Control circuit uses screw clamp terminals accepting 1-4 mm² flexible or solid. Tightening torque: 18 N.m on power, 1.2 N.m on control. IP2X on the front face with shrouds per IEC 60529. Designed to IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1, overvoltage category III. Protective treatment TH (tropicalized). Operating altitude 3000 m without derating, ambient temperature -5 to 55 °C operation, -60 to 80 °C storage.","metaTitle":"LC1F185D7 TeSys F Contactor, 185 A AC-3, 42 V AC Coil","metaDescription":"Schneider Electric LC1F185D7 TeSys F contactor. 185 A AC-3 rated operational current, 90 kW motor power at 380-400 V. 42 V AC 40-400 Hz coil. End-of-life status; sourced to order a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"181 mm","Range":"TeSys","Width":"168.5 mm","Height":"174 mm","Standards":"IEC 60947-1 EN 60947-1 IEC 60947-4-1 JIS C8201-4-1 EN 60947-4-1","Motor power kW":"90 kW at 380...400 V AC 50/60 Hz (AC-3) 100 kW at 415 V AC 50/60 Hz (AC-3) 100 kW at 440 V AC 50/60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 110 kW at 660...690 V AC 50/60 Hz (AC-3) 55 kW at 220...230 V AC 50/60 Hz (AC-3) 33 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"8...9.8 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.33 mOhm - Ith 275 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 18 N.m","Compatibility code":"LC1F","Inrush power in VA":"1070 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-4 AC-3 AC-1","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Associated fuse rating":"200 A aM at 315 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm Power circuit: lugs-ring terminals 1 cable(s) 150 mm² Power circuit: connector 1 cable(s) 150 mm² Power circuit: bolted connection","IP degree of protection":"IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106","Rated breaking capacity":"1480 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"12 W AC-3 25 W AC-1","[Uc] control circuit voltage":"42 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"275 A (at 185 A (at <55 °C) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"9.9 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1500 A 40 °C - 10 s 920 A 40 °C - 30 s 740 A 40 °C - 1 min 500 A 40 °C - 3 min 400 A 40 °C - 10 min","[Ith] conventional free air thermal current":"275 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2bbcb6078f894c674e61f660dd407509.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F185D7/tesys-f-contactor-3p-3-no-ac3-440-v-275-a-coil-42-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F185D7/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F185D7 and get current pricing?","answer":"The LC1F185D7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a real-time picture of the surplus market."},{"question":"What is LC1F185D7's depth?","answer":"The LC1F185D7 has a depth of 181 mm."},{"question":"What series is LC1F185D7 from?","answer":"The LC1F185D7 belongs to the Schneider Electric TeSys F range of contactors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F185D7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F185D7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}