{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F185F722L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F185F722L","canonicalUrl":"https://aoctrl.com/schneider/LC1F185F722L","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F185F722L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, 3-pole contactor, LC1F185F722L, 275 A AC-3 rated operational current, 110 V AC 50/60 Hz control coil, plate mount, end-of-life status.","salesMarkdown":"## TeSys F Contactor, 275 A AC-3 — End-of-Life Sourcing Note The Schneider Electric LC1F185F722L is a TeSys F 3-pole contactor rated for 275 A at ≤ 440 V AC in AC-3 duty, meaning it switches motor loads up to that current — typically a 90 kW motor at 400 V or 125 hp at 460 V per UL/CSA. The 110 V AC 50/60 Hz control coil draws 970 VA inrush (60 Hz) and 55 VA holding. The 275 A AC-3 rating governs motor switching; for resistive loads (AC-1), the contactor can handle higher currents — the power dissipation per pole is 12 W in AC-3 and 25 W in AC-1. The 110 V AC coil operates between 0.85 and 1.1 Uc (93.5–121 V) and drops out between 0.35 and 0.55 Uc (38.5–60.5 V). The contactor carries 2 NO + 2 NC auxiliary contacts built in. Compliant with IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Overvoltage category III. The front face with shrouds provides IP2X protection per IEC 60529 and VDE 0106. Protective treatment is TH for tropical environments. Plate-mounted (not DIN rail). Power circuit connections use bolted bars (2 bars 25 x 3 mm) or ring terminals up to 150 mm². Control circuit terminals accept 1–4 mm² solid or flexible wire (1–2.5 mm² with cable end). Tightening torque is 159.3 lbf·in (18 N·m) for power and 10.6 lbf·in (1.2 N·m) for control. Dimensions: 12.008 in (305 mm) height, 6.6 in (168.5 mm) width, 7.1 in (181 mm) depth. The LC1F185F722L is classified as end-of-life (EOL) by the manufacturer. For BOM lines requiring this exact code, sourcing is through independent channels; we can quote availability and pricing against an RFQ. The associated fuse rating is 200 A aM or 315 A gG at ≤ 440 V.","metaTitle":"Schneider LC1F185F722L TeSys F Contactor, 275 A AC-3, 110 VA","metaDescription":"Schneider Electric TeSys F LC1F185F722L 3-pole contactor. 275 A rated operational current (AC-3), 110 VAC 50/60 Hz coil. End-of-life (EOL) status; sourced to order. UL/CSA, IEC, EN","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"7.1 in (181 mm)","Width":"6.6 in (168.5 mm)","Height":"12.008 in (305 mm)","Category":"39997-CANADIAN PRODUCTS","Standards":"JIS C8201-4-1 IEC 60947-1 IEC 60947-4-1 EN 60947-1 EN 60947-4-1","Motor power kW":"90 kW at 380...400 V AC 50/60 Hz 100 kW at 415 V AC 50/60 Hz 100 kW at 440 V AC 50/60 Hz 110 kW at 500 V AC 50/60 Hz 110 kW at 660...690 V AC 50/60 Hz 100 kW at 1000 V AC 50/60 Hz 55 kW at 220...230 V AC 50/60 Hz","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"18...24 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.33 mOhm - Ith 275 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 159.3 lbf.in (18 N.m)","Inrush power in VA":"970 VA, 60 Hz 0.3 68 °F (20 °C)) 805 VA, 50 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-1","Contactor application":"Motor control Resistive load","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Shocks contactor closed15 Gn for 11 ms Vibrations contactor closed5 Gn, 5...300 Hz Shocks contactor open7 Gn for 11 ms","Nbr. of units in pkg.":"1","Associated fuse rating":"200 A aM at 315 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bolted connection Power circuit 2 bars 25 x 3 mm Power circuit lugs-ring terminals 1 0.2 in² (150 mm²) Power circuit connector 1 0.2 in² (150 mm²)","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1480 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","motor power HP (UL / CSA)":"50 hp at 200 V AC 60 hp at 230 V AC 125 hp at 460 V AC 150 hp at 575 V AC","Power dissipation per pole":"12 W AC-3 25 W AC-1","[Uc] control circuit voltage":"110 V AC 40...400 Hz","Auxiliary contact composition":"2 NO + 2 NC","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"275 A (at 185 A (at <131 °F (55 °C)) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) 66 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1500 A 104 °F (40 °C) - 10 s 920 A 104 °F (40 °C) - 30 s 740 A 104 °F (40 °C) - 1 min 500 A 104 °F (40 °C) - 3 min 400 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"275 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8b1d0fbd4ff297f20036f4bfa5b1a5e7.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1F185F722L/tesys-f-nonreversing-contactor-3p-open-600v-185a-110vac-50-60hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F185F722L/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of LC1F185F722L?","answer":"The LC1F185F722L is a 3-pole contactor rated 275 A at ≤ 440 V AC in AC-3 duty, with a 110 V AC 50/60 Hz control coil. It switches motors up to 90 kW at 400 V or 125 hp at 460 V (UL/CSA)."},{"question":"What compliance documentation does LC1F185F722L carry?","answer":"The LC1F185F722L complies with IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. It carries IP2X front-face protection and TH protective treatment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F185F722L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F185F722L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}