{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F185N522L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F185N522L","canonicalUrl":"https://aoctrl.com/schneider/LC1F185N522L","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F185N522L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F series, 3-pole contactor, 275 A rated operational current, 90 kW at 400 V AC AC-3, 415 V AC 50 Hz coil, 2 NO + 2 NC aux contacts, plate mount, EOL phase.","salesMarkdown":"The LC1F185N522L is a 3-pole TeSys F contactor from Schneider Electric, rated 275 A operational current (Ie) at ≤440 V AC in AC-3 duty. That AC-3 rating governs motor switching — it handles 90 kW on a 380–400 V supply, stepping to 100 kW at 415 V and 110 kW at 660–690 V. The 415 V AC 50 Hz coil is a fixed-voltage control circuit, so verify your panel's control transformer matches before wiring; the hold-in power draw is 55 VA at 50 Hz, which matters for transformer sizing in multi-contactor cabinets. For UL/CSA installations, the motor horsepower ratings are 125 hp at 460 V and 150 hp at 575 V — that's the number to hand the inspector if the panel carries a UL label. The contactor meets IEC 60947-4-1 and EN 60947-4-1, so it fits both IEC and North American spec'd lines without a separate part number. The auxiliary contact block comes factory-fitted with 2 NO + 2 NC, which covers most feedback and interlock needs on a motor starter without an add-on module. If you need more, the TeSys F aux contact range clips onto the front without tools. ## Deployment context — what it connects to Plate-mounted, not DIN-rail — expect to bolt it to a backplate or sub-panel. The power circuit uses bolted connections or ring terminals up to 150 mm²; torque the power terminals to 159.3 lbf·in (18 N·m). The control circuit uses screw-clamp terminals accepting 1–4 mm² flexible or solid, torqued to 10.6 lbf·in (1.2 N·m). Overvoltage category III means it's rated for fixed-installation distribution panels, not plug-connected equipment. The IP2X front face with shrouds keeps fingers out but isn't washdown-rated — keep it inside a closed enclosure. Associated fuse ratings are 200 A aM or 315 A gG at ≤440 V — that's the short-circuit protection coordination figure for the motor branch circuit. The rated breaking capacity is 1480 A per IEC 60947-4-1, which is the contactor's own ability to interrupt a fault, not the fuse's job.","metaTitle":"Schneider Electric LC1F185N522L TeSys F Contactor, 275 A, 90","metaDescription":"Schneider Electric LC1F185N522L TeSys F 3-pole contactor. 275 A rated, 90 kW at 400 V AC-3. 415 V AC coil. EOL phase. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"7.1 in (181 mm)","Width":"6.6 in (168.5 mm)","Height":"12.008 in (305 mm)","Category":"39997-CANADIAN PRODUCTS","Standards":"JIS C8201-4-1 IEC 60947-4-1 IEC 60947-1 EN 60947-1 EN 60947-4-1","Motor power kW":"90 kW at 380...400 V AC 50/60 Hz (AC-3) 100 kW at 415 V AC 50/60 Hz (AC-3) 100 kW at 440 V AC 50/60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 110 kW at 660...690 V AC 50/60 Hz (AC-3) 100 kW at 1000 V AC 50/60 Hz (AC-3) 55 kW at 220...230 V AC 50/60 Hz (AC-3) 33 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"18...24 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.33 mOhm - Ith 275 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 159.3 lbf.in (18 N.m)","Inrush power in VA":"805 VA, 50 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-4 AC-1","Contactor application":"Motor control Resistive load","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Shocks contactor closed15 Gn for 11 ms Vibrations contactor closed5 Gn, 5...300 Hz Shocks contactor open7 Gn for 11 ms","Nbr. of units in pkg.":"1","Associated fuse rating":"200 A aM at 315 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bolted connection Power circuit 2 bars 25 x 3 mm Power circuit lugs-ring terminals 1 0.2 in² (150 mm²) Power circuit connector 1 0.2 in² (150 mm²)","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1480 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","motor power HP (UL / CSA)":"50 hp at 200 V AC 60 hp at 230 V AC 125 hp at 460 V AC 150 hp at 575 V AC","Power dissipation per pole":"12 W AC-3 25 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"2 NO + 2 NC","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"275 A (at 185 A (at <131 °F (55 °C)) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1500 A 104 °F (40 °C) - 10 s 920 A 104 °F (40 °C) - 30 s 740 A 104 °F (40 °C) - 1 min 500 A 104 °F (40 °C) - 3 min 400 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"275 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8b51fa2a0fc064a99312cf904dbecff8.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1F185N522L/tesys-f-nonreversing-contactor-3p-open-600v-185a-415vac-50hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F185N522L/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for LC1F185N522L?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time from independent distribution channels — no manufacturer lead time applies since production has ended. Availability varies; a quote request is the fastest way to know what's on the shelf today."},{"question":"What compliance documentation does this brand provide for LC1F185N522L?","answer":"The contactor is certified to IEC 60947-4-1, IEC 60947-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. It carries UL/CSA horsepower ratings, so UL and CSA listing documentation is available from Schneider. Protective treatment is TH, indicating tropicalized heat-and-humidity resistance. RoHS and REACH declarations are standard for Schneider TeSys products but are not explicitly listed in this record."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F185N522L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F185N522L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}