{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F185Q522L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F185Q522L","canonicalUrl":"https://aoctrl.com/schneider/LC1F185Q522L","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F185Q522L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F185Q522L, 3-pole contactor, 275 A AC-3, 90 kW at 400 V, coil 380 V AC 50 Hz, 2 NO + 2 NC aux, plate mount.","salesMarkdown":"The LC1F185Q522L is a 3-pole TeSys F contactor from Schneider Electric, rated for motor control and resistive loads across AC-1, AC-3, and AC-4 utilisation categories. The headline number is 275 A rated operational current (Ie) in AC-3 duty at ≤ 440 V, which translates to switching a 90 kW motor at 380–400 V AC or 100 kW at 415 V. For resistive loads (AC-1), the thermal current (Ith) is 275 A at 50 Hz, with 25 W dissipation per pole. The control circuit is a 380 V AC 50 Hz coil, with an operating range of 0.85–1.1 Uc and drop-out between 0.35–0.55 Uc. Inrush power is 805 VA at 50 Hz; hold-in consumption drops to 55 VA. That 380 V coil voltage is less common than the 220–240 V or 110 V alternatives in the TeSys F family — verify your control transformer taps before committing the panel design. The contactor carries IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1 standards. For North American installations, the UL/CSA motor power ratings are 125 hp at 460 V and 150 hp at 575 V — the 460 V figure is the one most often checked for 480 V plant distribution. This contactor is plate-mounted (not DIN-rail), so it bolts directly to a backplate or mounting chassis. Dimensions are 7.1 in deep, 6.6 in wide, and 12.008 in tall. Power connections use bolted bars or ring terminals up to 150 mm²; control wiring is screw-clamp terminals accepting 1–4 mm² flexible or solid. Tightening torque on the power circuit is 159.3 lbf·in (18 N·m) — a torque wrench is expected, not optional. The front face with shrouds achieves IP2X protection per IEC 60529 and VDE 0106. Associated fuse ratings are 200 A aM or 315 A gG at ≤ 440 V. The rated breaking capacity is 1480 A per IEC 60947-4-1. Overvoltage category III and rated insulation voltage of 1000 V (IEC) or 1500 V (VDE 0110 group C) place it in the distribution-level isolation class. The protective treatment code TH indicates tropicalisation — suitable for humid or corrosive environments.","metaTitle":"Schneider Electric LC1F185Q522L TeSys F Contactor, 275 A AC-","metaDescription":"Schneider Electric LC1F185Q522L TeSys F contactor, 275 A rated operational current (AC-3), 90 kW at 400 V. EOL hot stage; sourced to order against RFQ. IEC/EN 60947-4-1, UL/CSA lis","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"7.1 in (181 mm)","Width":"6.6 in (168.5 mm)","Height":"12.008 in (305 mm)","Category":"39997-CANADIAN PRODUCTS","Standards":"EN 60947-4-1 JIS C8201-4-1 IEC 60947-1 IEC 60947-4-1 EN 60947-1","Motor power kW":"90 kW at 380...400 V AC 50/60 Hz (AC-3) 100 kW at 415 V AC 50/60 Hz (AC-3) 100 kW at 440 V AC 50/60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 110 kW at 660...690 V AC 50/60 Hz (AC-3) 100 kW at 1000 V AC 50/60 Hz (AC-3) 55 kW at 220...230 V AC 50/60 Hz (AC-3) 33 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"18...24 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.33 mOhm - Ith 275 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 159.3 lbf.in (18 N.m)","Inrush power in VA":"805 VA, 50 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-4 AC-1 AC-3","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Shocks contactor closed15 Gn for 11 ms Vibrations contactor closed5 Gn, 5...300 Hz Shocks contactor open7 Gn for 11 ms","Nbr. of units in pkg.":"1","Associated fuse rating":"200 A aM at 315 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bolted connection Power circuit 2 bars 25 x 3 mm Power circuit lugs-ring terminals 1 0.2 in² (150 mm²) Power circuit connector 1 0.2 in² (150 mm²)","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1480 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","motor power HP (UL / CSA)":"50 hp at 200 V AC 60 hp at 230 V AC 125 hp at 460 V AC 150 hp at 575 V AC","Power dissipation per pole":"12 W AC-3 25 W AC-1","[Uc] control circuit voltage":"380 V AC 50 Hz","Auxiliary contact composition":"2 NO + 2 NC","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"275 A (at 185 A (at <131 °F (55 °C)) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1500 A 104 °F (40 °C) - 10 s 920 A 104 °F (40 °C) - 30 s 740 A 104 °F (40 °C) - 1 min 500 A 104 °F (40 °C) - 3 min 400 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"275 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d2c63d9fc7eeeb3e221c92c6f727bcc2.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1F185Q522L/tesys-f-nonreversing-contactor-3p-open-600v-185a-380vac-50hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F185Q522L/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F185Q522L and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here because the inventory is finite and market-priced. Submit an RFQ for a firm quote and delivery estimate."},{"question":"What is the closest alternative to LC1F185Q522L in the TeSys F family?","answer":"Within the TeSys F range, the closest functional peer is a contactor with the same frame size and pole count but a different coil voltage. The LC1F185Q522L uses a 380 V AC 50 Hz coil; if your control voltage is different (e.g., 220 V or 110 V), the corresponding TeSys F variant with the matching coil code is the direct swap. No pin-compatible drop-in exists outside the TeSys F platform because the mounting pattern, power lug spacing, and auxiliary contact layout are specific to this series."},{"question":"What compliance documentation does Schneider Electric provide for LC1F185Q522L?","answer":"The contactor is certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. UL and CSA listings are confirmed by the motor power HP ratings (125 hp at 460 V, 150 hp at 575 V). The protective treatment TH indicates suitability for tropical environments. RoHS and REACH declarations are standard for Schneider Electric TeSys products but are not itemised in this listing — request them with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F185Q522L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F185Q522L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}