{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F185V7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F185V7","canonicalUrl":"https://aoctrl.com/schneider/LC1F185V7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F185V7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F185V7, 3-pole contactor, 90 kW at 380-400 V AC-3, 400 V AC 50/60 Hz coil, plate mount, 275 A rated operational current.","salesMarkdown":"The Schneider Electric TeSys F LC1F185V7 is a 3-pole, direct on-line contactor rated for switching motor loads up to 90 kW at 380-400 V AC in AC-3 duty (cites:). The 400 V AC coil pulls in at 0.85 to 1.1 times its rated control voltage and drops out between 0.2 and 0.55 Uc (cites:). Rated operational current is 275 A at 185 A in AC-3 at ≤ 440 V (cites:). Mounts to a plate (cites:). The power circuit accepts bar connections (25 x 3 mm busbar), ring terminals, or bolted lugs for 150 mm² cable (cites:). Control wiring uses screw-clamp terminals accepting 1 to 4 mm² flexible or solid (cites:). Tightening torque is 18 N.m on the power side, 1.2 N.m on the control side (cites:). At 415 V it delivers 100 kW, at 440 V also 100 kW, and at 500 V it reaches 110 kW (cites:). For AC-4 duty (plugging, inching) the rating drops to 33 kW at 400 V — that is the reversing or jogging limit, not the continuous running load (cites:). The utilisation categories (AC-3, AC-4, AC-1) are certified to IEC 60947-4-1 (cites:,). Rated breaking capacity is 1480 A conforming to IEC 60947-4-1 (cites:). The associated fuse recommendation is 200 A aM or 315 A gG at ≤ 440 V (cites:). Mechanical durability is 10 million cycles (cites:). Maximum operating rate is 2400 cycles per hour at 55 °C (cites:). Heat dissipation runs 8 to 9.8 W total, with 12 W per pole in AC-3 and 25 W per pole in AC-1 (cites:,). Designed and tested to IEC 60947-4-1, IEC 60947-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1 (cites:). Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C (cites:). Overvoltage category III (cites:). IP2X front face with shrouds per IEC 60529 and VDE 0106 (cites:). Protective treatment TH for tropical environments (cites:).","metaTitle":"Schneider TeSys LC1F185V7 Contactor, 90 kW AC-3, 400 V Coil","metaDescription":"Schneider Electric TeSys F LC1F185V7 contactor. 90 kW at 380-400 V AC-3, 400 V AC coil. IEC 60947-4-1. End-of-life; sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"181 mm","Range":"TeSys","Width":"168.5 mm","Height":"174 mm","Standards":"IEC 60947-4-1 JIS C8201-4-1 IEC 60947-1 EN 60947-1 EN 60947-4-1","Motor power kW":"90 kW at 380...400 V AC 50/60 Hz (AC-3) 100 kW at 415 V AC 50/60 Hz (AC-3) 100 kW at 440 V AC 50/60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 110 kW at 660...690 V AC 50/60 Hz (AC-3) 55 kW at 220...230 V AC 50/60 Hz (AC-3) 33 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"35 ms closing (at Uc) 130 ms opening (at Uc)","lifecycle_stage":"eol_hot","Heat dissipation":"8...9.8 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.33 mOhm - Ith 275 A 50 Hz","Device short name":"LC1F","Motor Power Range":"30...50 kW at 200...240 V 3 phases 55...100 kW at 200...240 V 3 phases 55...100 kW at 380...440 V 3 phases 55...100 kW at 480...500 V 3 phases 110...220 kW at 480...500 V 3 phases","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 18 N.m","Compatibility code":"LC1F","Inrush power in VA":"1070 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Motor starter type":"Direct on-line contactor","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-4 AC-1","Contactor application":"Motor control Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"200 A aM at 315 A gG at <= 440 V","Contactor coil voltage":"400 V AC standard","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm Power circuit: lugs-ring terminals 1 cable(s) 150 mm² Power circuit: connector 1 cable(s) 150 mm² Power circuit: bolted connection","IP degree of protection":"IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106","Rated breaking capacity":"1480 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"12 W AC-3 25 W AC-1","[Uc] control circuit voltage":"400 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"275 A (at 185 A (at <55 °C) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"9.9 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1500 A 40 °C - 10 s 920 A 40 °C - 30 s 740 A 40 °C - 1 min 500 A 40 °C - 3 min 400 A 40 °C - 10 min","[Ith] conventional free air thermal current":"275 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/51b9a82becd1e32c99d366a8ab0c7283.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC1F185V7/tesys-f-contactor-3p-3-no-ac3-440-v-185-a-coil-400-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F185V7/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1F185V7?","answer":"There is no official successor order code listed. For a current-production equivalent, a Schneider TeSys F contactor with the same frame size and coil voltage but an active lifecycle status would be the functional match — verify the AC-3 current rating and mounting footprint against the BOM."},{"question":"What is LC1F185V7's motor power rating?","answer":"90 kW at 380-400 V AC in AC-3 duty (cites:). At 415 V and 440 V it delivers 100 kW, and at 500 V it reaches 110 kW (cites:). For AC-4 (reversing/jogging) the rating is 33 kW at 400 V (cites:)."},{"question":"Where can I buy LC1F185V7?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What compliance documentation does Schneider provide for LC1F185V7?","answer":"The contactor is certified to IEC 60947-4-1, IEC 60947-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1 (cites:). Rated insulation voltage is 1000 V per IEC and 1500 V per VDE 0110 group C (cites:). Overvoltage category III (cites:)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F185V7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F185V7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}