{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F2100F7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F2100F7","canonicalUrl":"https://aoctrl.com/schneider/LC1F2100F7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F2100F7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F2100F7, 3-pole contactor, 2100 A AC-1, 110 V AC 40-400 Hz control circuit, plate mount, EOL lifecycle.","salesMarkdown":"The LC1F2100F7 is a 3-pole TeSys F contactor rated for 2100 A conventional free-air thermal current (Ith) and 2100 A operational current in AC-1 utilisation category — meaning it is sized for resistive heating loads, not motor starting. AC-1 duty covers loads where the current waveform stays nearly sinusoidal with no significant inrush, such as large electric furnaces, banked heaters, or power-factor correction capacitor banks. The 110 V AC control circuit (40-400 Hz) draws 2200 VA inrush and holds at 36 VA; dropout occurs between 0.3 and 0.5 Uc, so the coil reliably releases below about 55 V AC. Rated breaking capacity is 3150 A per IEC 60947-4-1, and the short-time withstand current (Icw) reaches 10 kA for 10 seconds — enough to coordinate with upstream 2000 A gG fuses at ≤ 440 V without nuisance opening during a downstream fault. The contactor carries overvoltage category III and an impulse withstand voltage of 8 kV, so it suits fixed-installation distribution panels where transient overvoltages from the mains are expected. The contactor is certified to IEC 60947-4-1, EN 60947-1, EN 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. The protective treatment (TH) indicates suitability for tropical/humid environments. Operating altitude reaches 3000 m without derating. Mounts on a plate (not DIN rail) — the 438 mm width and 332 mm height require a dedicated backplate in the enclosure. Power connections use bolted bars accepting up to 100 x 5 mm busbars; control circuit connections are screw-clamp terminals accepting 1…4 mm² flexible or solid wire. Tightening torque is 58 N.m on the power circuit and 1.2 N.m on the control circuit. Heat dissipation is 36 W total (200 W per pole in AC-1), so forced ventilation or derating may be needed in a sealed cabinet above 40 °C ambient.","metaTitle":"Schneider Electric LC1F2100F7 TeSys F Contactor, 2100 A AC-1","metaDescription":"Schneider Electric LC1F2100F7 TeSys F contactor, 2100 A AC-1, 110 VAC 40-400 Hz coil. EOL lifecycle. Sourced to order against RFQ. IEC 60947-4-1, UL, CSA.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"238.6 mm","Range":"TeSys","Width":"438 mm","Height":"332 mm","Standards":"IEC 60947-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Operating time":"100...170 ms opening 40...75 ms closing","lifecycle_stage":"eol_hot","Heat dissipation":"36 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 2100 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 58 N.m","Compatibility code":"LC1F","Inrush power in VA":"2200 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Associated fuse rating":"2000 A gG at <= 440 V","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 4 cable(s) - busbar cross section: 100 x 5 mm Power circuit: bolted connection","Rated breaking capacity":"3150 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"200 W AC-1","[Uc] control circuit voltage":"110 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C 1000 V conforming to UL 60947-4-1","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"2100 A (at <40 °C) AC AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"36 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"10000 A 40 °C - 10 s 7500 A 40 °C - 30 s 5500 A 40 °C - 1 min 4200 A 40 °C - 3 min 3000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"2100 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fd792b7d7aaa0bdfe5c64c49f38b05b6.pdf","sourceUrl":"https://www.se.com/be/en/product/LC1F2100F7/contactor-tesys-f-3p3no-ac1-1000v-2100a-coil-110v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F2100F7/alternatives.json"},"ai":{"faq":[{"question":"Who supplies LC1F2100F7 and how is it quoted for volume purchases?","answer":"This part is sourced through independent distribution channels. Availability and current pricing are confirmed at quote time against an RFQ — no stock count or price is listed here."},{"question":"What is the closest pin-compatible alternative to LC1F2100F7 in this component family?","answer":"No official successor order code is listed in the lifecycle record. A form-fit-function cross-reference would need to be evaluated against the original panel design, considering the 2100 A AC-1 rating, 110 V AC coil, and plate-mount footprint."},{"question":"What compliance documentation does this brand provide for LC1F2100F7?","answer":"The contactor carries certifications to IEC 60947-4-1, EN 60947-1, EN 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F2100F7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F2100F7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}