{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F2100F7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F2100F7","canonicalUrl":"https://aoctrl.com/schneider/LC1F2100F7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F2100F7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F2100F7, 3-pole contactor, 2100 A AC-1, 110 V AC 40-400 Hz control circuit, plate mount, EOL lifecycle.","salesMarkdown":"The LC1F2100F7 is a 3-pole TeSys F contactor rated for 2100 A conventional free-air thermal current (Ith) and 2100 A operational current in AC-1 utilisation category — meaning it is sized for resistive heating loads, not motor starting. AC-1 duty covers loads where the current waveform stays nearly sinusoidal with no significant inrush, such as large electric furnaces, banked heaters, or power-factor correction capacitor banks. The 110 V AC control circuit (40-400 Hz) draws 2200 VA inrush and holds at 36 VA; dropout occurs between 0.3 and 0.5 Uc, so the coil reliably releases below about 55 V AC. Rated breaking capacity is 3150 A per IEC 60947-4-1, and the short-time withstand current (Icw) reaches 10 kA for 10 seconds — enough to coordinate with upstream 2000 A gG fuses at ≤ 440 V without nuisance opening during a downstream fault. The contactor carries overvoltage category III and an impulse withstand voltage of 8 kV, so it suits fixed-installation distribution panels where transient overvoltages from the mains are expected. The contactor is certified to IEC 60947-4-1, EN 60947-1, EN 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. The protective treatment (TH) indicates suitability for tropical/humid environments. Operating altitude reaches 3000 m without derating. Mounts on a plate (not DIN rail) — the 438 mm width and 332 mm height require a dedicated backplate in the enclosure. Power connections use bolted bars accepting up to 100 x 5 mm busbars; control circuit connections are screw-clamp terminals accepting 1…4 mm² flexible or solid wire. Tightening torque is 58 N.m on the power circuit and 1.2 N.m on the control circuit. Heat dissipation is 36 W total (200 W per pole in AC-1), so forced ventilation or derating may be needed in a sealed cabinet above 40 °C ambient.","metaTitle":"Schneider Electric LC1F2100F7 TeSys F Contactor, 2100 A AC-1","metaDescription":"Schneider Electric LC1F2100F7 TeSys F contactor, 2100 A AC-1, 110 VAC 40-400 Hz coil. EOL lifecycle. Sourced to order against RFQ. IEC 60947-4-1, UL, CSA.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"238.6 mm","Width":"438 mm","Height":"332 mm","Current":"2100 A (at <40 °C) AC AC-1","Voltage":"<= 460 V DC","Application":"Resistive load","Coil Voltage":"110 V AC 40...400 Hz","Operating Time":"100...170 ms opening 40...75 ms closing","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"3150 A conforming to IEC 60947-4-1","Insulation Voltage Ui":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C 1000 V conforming to UL 60947-4-1","Temp Operating Max":"40 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 40...400 Hz","Utilization Category":"AC-1","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...40 °C","Permissible Ambient Air Temperature Around The Device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fd792b7d7aaa0bdfe5c64c49f38b05b6.pdf","sourceUrl":"https://www.se.com/be/en/product/LC1F2100F7/contactor-tesys-f-3p3no-ac1-1000v-2100a-coil-110v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F2100F7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F2100F7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F2100F7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}