{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F2100L7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F2100L7","canonicalUrl":"https://aoctrl.com/schneider/LC1F2100L7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F2100L7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F2100L7, 3-pole contactor, 2100 A AC-1, 208 V AC 40-400 Hz coil, plate mount, 238.6 mm depth.","salesMarkdown":"The 208 V AC control coil (40-400 Hz) pulls 2200 VA inrush and holds at 36 VA. Opening takes 100-170 ms; closing 40-75 ms. Mounts to a plate, not a DIN rail — this is a bolted-down power contactor, not a panel-snap device. The headline number is 2100 A at ≤40 °C in AC-1 duty — that's the continuous resistive current the main poles carry. For fault handling: rated breaking capacity is 3150 A per IEC 60947-4-1, and short-time withstand (Icw) is 10 kA for 10 s, 7.5 kA for 30 s, stepping down to 3 kA for 10 min. Associated fuse rating is 2000 A gG at ≤440 V. Power dissipation per pole is 200 W in AC-1, total 36 W coil hold-in heat — factor that into enclosure ventilation if the panel is sealed. Control circuit voltage limits: pick-up at 0.85-1.1 Uc, drop-out at 0.3-0.5 Uc (55 °C). ## Integration and connections Plate-mount only — no DIN-rail adapter. Power circuit terminates via bolted bar connection, accepting up to 4 cables with a 100 x 5 mm busbar cross-section. Tightening torque: 58 N.m on the power side, 1.2 N.m on the control circuit screw clamps. Control wiring accepts 1-4 mm² flexible or solid (with or without ferrule). Dimensions: 438 mm wide, 332 mm high, 238.6 mm deep. Operating altitude 3000 m without derating; ambient temperature range -5 to 40 °C operating, -60 to 80 °C storage. Certified to IEC 60947-1, IEC 60947-4-1, EN 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Rated insulation voltage (Ui) 1000 V per IEC/UL, 1500 V per VDE 0110 group C. Impulse withstand (Uimp) 8 kV, overvoltage category III. Protective treatment TH for tropical environments. Mechanical durability 0.5 Mcycles; maximum operating rate 600 cycles/hour at 55 °C.","metaTitle":"Schneider LC1F2100L7 TeSys F Contactor, 2100 A AC-1, 208 V C","metaDescription":"Schneider Electric LC1F2100L7 TeSys F 3-pole contactor. 2100 A rated operational current (AC-1), 208 V AC 40-400 Hz coil. EOL hot stage; sourced to order. UL/CSA/IEC. Request quote","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"238.6 mm","Range":"TeSys","Width":"438 mm","Height":"332 mm","Standards":"IEC 60947-1 EN 60947-1 EN 60947-4-1 IEC 60947-4-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Operating time":"100...170 ms opening 40...75 ms closing","lifecycle_stage":"eol_hot","Heat dissipation":"36 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 2100 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 58 N.m","Compatibility code":"LC1F","Inrush power in VA":"2200 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"0.5 Mcycles","Associated fuse rating":"2000 A gG at <= 440 V","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 4 cable(s) - busbar cross section: 100 x 5 mm Power circuit: bolted connection","Rated breaking capacity":"3150 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"200 W AC-1","[Uc] control circuit voltage":"208 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C 1000 V conforming to UL 60947-4-1","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"2100 A (at <40 °C) AC AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"36 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"10000 A 40 °C - 10 s 7500 A 40 °C - 30 s 5500 A 40 °C - 1 min 4200 A 40 °C - 3 min 3000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"2100 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c2e7277ea3f28cdbbcf7171713e8c496.pdf","sourceUrl":"https://www.se.com/be/en/product/LC1F2100L7/tesys-f-contactor-3p-3-no-ac1-1000-v-2100-a-coil-208-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F2100L7/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F2100L7 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for this order code."},{"question":"What is the rated operational current of LC1F2100L7?","answer":"2100 A in AC-1 utilisation category at ≤40 °C ambient."},{"question":"What control voltage does LC1F2100L7 use?","answer":"208 V AC, 40-400 Hz. Inrush is 2200 VA; hold-in is 36 VA at cos φ 0.9."},{"question":"What compliance documentation is available for LC1F2100L7?","answer":"The contactor carries UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC 60947-4-1, and EN 60947-4-1 certifications. Rated insulation voltage 1000 V (IEC/UL), impulse withstand 8 kV, overvoltage category III."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F2100L7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F2100L7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}