{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F2254P5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F2254P5","canonicalUrl":"https://aoctrl.com/schneider/LC1F2254P5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F2254P5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F2254P5, 4-pole contactor, 315 A AC-1 at <=440 V, 230 V AC 50 Hz coil, plate mount, 181 mm depth.","salesMarkdown":"The Schneider Electric TeSys F LC1F2254P5 is a 4-pole contactor rated for 315 A in AC-1 utilisation category at <=440 V, meaning it is sized for switching resistive loads — heaters, ovens, lighting banks — not motor starting. The 230 V AC 50 Hz coil draws 805 VA inrush and holds at 55 VA. Plate-mounted, with a 181 mm depth and 208.5 mm width, it fits into a panel cutout or backplate layout where a compact 4-pole footprint is needed. Mounting is plate-only — no DIN-rail clip. The power circuit accepts bar (2 cables, 32 x 4 mm busbar), ring terminals (1 cable 185 mm²), or bolted connection. Control wiring uses screw clamp terminals for 1–4 mm² flexible or solid, with or without cable end. Torque to 35 N·m on the power side, 1.2 N·m on the control side. IP20 front face with shrouds per IEC 60529 and VDE 0106.","metaTitle":"Schneider TeSys F LC1F2254P5 Contactor, 315 A AC-1, 4-Pole,","metaDescription":"Schneider Electric TeSys F LC1F2254P5 4-pole contactor, 315 A AC-1 at <=440 V, 230 V AC coil. End-of-life status; sourced to order against RFQ. IEC 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"181 mm","Range":"TeSys","Width":"208.5 mm","Height":"197 mm","Standards":"IEC 60947-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-4-1 EN 60947-1","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"18...24 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.32 mOhm - Ith 315 A 50 Hz","Device short name":"LC1F","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 35 N.m","Compatibility code":"LC1F","Inrush power in VA":"805 VA, 50 Hz cos phi 0.3 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 50 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"315 A gG at 250 A aM at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm Power circuit: lugs-ring terminals 1 cable(s) 185 mm² Power circuit: connector 1 cable(s) 185 mm² Power circuit: bolted connection","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"1800 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"32 W AC-1","[Uc] control circuit voltage":"230 V AC 50 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 50/60 Hz (at 55 °C) Drop-out: 0.35...0.55 Uc 50/60 Hz (at 55 °C)","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"315 A (at <40 °C) at <= 440 V AC-1","[Ue] rated operational voltage":"<= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"55 VA, 50 Hz cos phi 0.3 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1800 A 40 °C - 10 s 1000 A 40 °C - 30 s 850 A 40 °C - 1 min 560 A 40 °C - 3 min 440 A 40 °C - 10 min","[Ith] conventional free air thermal current":"315 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bbd103127b57192bf7789de790571f03.pdf","sourceUrl":"https://www.se.com/th/en/product/LC1F2254P5/tesys-f-contactor-4p-4-no-ac1-440-v-315-a-coil-230-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F2254P5/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1F2254P5 in the TeSys F family?","answer":"No official successor order code is published. A parametric match within TeSys F for a 4-pole, 315 A AC-1 contactor with a 230 V AC coil is the starting point, but mounting dimensions and control circuit wiring must be cross-checked against the existing panel."},{"question":"What is LC1F2254P5's listed depth?","answer":"181 mm."},{"question":"What compliance documentation does this brand provide for LC1F2254P5?","answer":"The contactor is designed to IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Overvoltage category III. Protective treatment TH."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F2254P5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F2254P5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}