{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F225B6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F225B6","canonicalUrl":"https://aoctrl.com/schneider/LC1F225B6","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F225B6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor, LC1F225B6, 3-pole, 315 A AC-3 rated operational current, 110 kW motor power at 400 V, 24 V AC 60 Hz coil, plate mount, EOL.","salesMarkdown":"The Schneider Electric LC1F225B6 is a 3-pole TeSys F contactor rated for 315 A in AC-3 duty (motor switching) at ≤ 440 V, with a corresponding motor power of 110 kW at 380–400 V AC 50/60 Hz. That 315 A figure is the operational current under motor load, not the resistive-heating current — for resistive loads (AC-1) the contactor can handle higher current, but the AC-3 number is what governs motor applications. The 24 V AC 60 Hz control coil draws 970 VA inrush and 66 VA hold-in; the drop-out voltage range is 0.35–0.55 Uc, so the coil releases cleanly on a brownout without chattering. The mechanical durability of 10 million cycles gives a long service life in high-cycle applications like conveyor or pump cycling. ## Where it fits — panel and deployment context Plate-mounted (not DIN rail), so plan for a drilled backplate or sub-panel. The footprint is 197 mm high × 168.5 mm wide × 181 mm deep — a substantial frame that needs generous enclosure volume for air circulation around the 18–24 W heat dissipation. Power connections accept bar (32 × 4 mm busbar), ring lugs, or connector for 185 mm² cable; control wiring is screw-clamp terminals for 1–4 mm². ## Standards and approvals — what they certify The rated insulation voltage is 1000 V per IEC 60947-4-1, with a 1500 V rating per VDE 0110 Group C — relevant for 690 V line applications where insulation coordination matters. Overvoltage category III suits fixed-installation distribution panels. The TH protective treatment indicates tropicalization for humid environments.","metaTitle":"Schneider Electric LC1F225B6 TeSys F Contactor, 315 A AC-3,","metaDescription":"Schneider Electric LC1F225B6 TeSys F contactor, 315 A AC-3 rated operational current, 110 kW motor power at 400 V. End-of-life status; sourced to order against RFQ. EN/IEC 60947-4-","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"181 mm","Range":"TeSys","Width":"168.5 mm","Height":"197 mm","Standards":"EN 60947-4-1 IEC 60947-4-1 JIS C8201-4-1 IEC 60947-1 EN 60947-1","Motor power kW":"110 kW at 380...400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 110 kW at 440 V AC 50/60 Hz (AC-3) 129 kW at 500 V AC 50/60 Hz (AC-3) 129 kW at 660...690 V AC 50/60 Hz (AC-3) 63 kW at 220...230 V AC 50/60 Hz (AC-3) 40 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"18...24 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.32 mOhm - Ith 315 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 35 N.m","Compatibility code":"LC1F","Inrush power in VA":"970 VA, 60 Hz cos phi 0.3 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 60 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Associated fuse rating":"315 A gG at 250 A aM at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm Power circuit: lugs-ring terminals 1 cable(s) 185 mm² Power circuit: connector 1 cable(s) 185 mm²","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"1800 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"32 W AC-1 16 W AC-3","[Uc] control circuit voltage":"24 V AC 60 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 50/60 Hz (at 55 °C) Drop-out: 0.35...0.55 Uc 50/60 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"315 A (at 225 A (at <55 °C) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"66 VA, 60 Hz cos phi 0.3 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1800 A 40 °C - 10 s 1000 A 40 °C - 30 s 850 A 40 °C - 1 min 560 A 40 °C - 3 min 440 A 40 °C - 10 min","[Ith] conventional free air thermal current":"315 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/86389fbc9ef313e0892460202eb359cd.pdf","sourceUrl":"https://www.se.com/be/en/product/LC1F225B6/tesys-f-contactor-3p-3-no-ac3-440-v-225-a-coil-24-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F225B6/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F225B6 and what is the price?","answer":"The LC1F225B6 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published for this EOL part."},{"question":"What are the key ratings of LC1F225B6?","answer":"Rated operational current is 315 A in AC-3 (motor duty) at ≤ 440 V, with motor power of 110 kW at 380–400 V AC. The control coil is 24 V AC 60 Hz. Breaking capacity is 1800 A per IEC 60947-4-1, and mechanical durability is 10 million cycles."},{"question":"What is LC1F225B6's mounting and enclosure requirement?","answer":"Plate-mounted only — no DIN-rail clip. Dimensions are 197 H × 168.5 W × 181 D mm. IP20 front face with shrouds; install inside a sealed cabinet for washdown environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F225B6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F225B6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}