{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F225E6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F225E6","canonicalUrl":"https://aoctrl.com/schneider/LC1F225E6","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F225E6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F225E6, 3-pole contactor, 315 A AC-3 at ≤440 V, 48 VAC 60 Hz coil, plate mount, EOL hot lifecycle phase.","salesMarkdown":"The LC1F225E6 is a 3-pole TeSys F contactor rated 315 A operational current in AC-3 duty at ≤440 V (cite:), which means it switches three-phase motor loads up to that current — 110 kW at 400 V (cite:) — without welding the main poles under normal starting. The 48 VAC 60 Hz coil (cite:) holds in at 0.85–1.1 Uc and drops out between 0.35–0.55 Uc (cite:); if your control transformer is 50 Hz, verify the coil's frequency tolerance because the VA inrush (970 VA at 60 Hz, cite:) and hold-in (66 VA, cite:) are specified at 60 Hz only. The contactor is rated for AC-3 (squirrel-cage motor starting), AC-4 (plugging/inching), and AC-1 (resistive) duty (cite:). For AC-4 at 400 V the motor power drops to 40 kW (cite:) — the higher switching frequency and breaking under load demand a lower thermal limit. Mechanical durability is 10 Mcycles (cite:); maximum operating rate is 2400 cycles/hour at 55 °C (cite:). Mounting is plate-only (cite:) — no DIN-rail adapter. The power circuit uses bolted bar or lug connections accepting up to 185 mm² cable (cite:). Tightening torque for power terminals is 35 N.m (cite:). IP20 front face with shrouds (cite:) means it's touch-safe in an enclosed panel but not rated for washdown. The LC1F225E6 is in end-of-life hot phase (cite:) — the manufacturer has announced discontinuation but still accepts orders for a limited last-time-buy window. After that window closes, supply moves to independent distribution and surplus channels. The contactor is designed to IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1 (cite:). Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C (cite:). Overvoltage category III (cite:). Protective treatment TH (cite:) indicates tropicalized humidity resistance.","metaTitle":"Schneider Electric LC1F225E6 TeSys F Contactor, 315 A AC-3,","metaDescription":"Schneider Electric LC1F225E6 TeSys F contactor. 315 A rated operational current (AC-3), 110 kW at 400 V. 48 VAC 60 Hz coil. EOL hot phase — sourced to order against RFQ. IEC 60947-","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"181 mm","Range":"TeSys","Width":"168.5 mm","Height":"197 mm","Standards":"EN 60947-1 IEC 60947-1 EN 60947-4-1 IEC 60947-4-1 JIS C8201-4-1","Motor power kW":"110 kW at 380...400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 110 kW at 440 V AC 50/60 Hz (AC-3) 129 kW at 500 V AC 50/60 Hz (AC-3) 129 kW at 660...690 V AC 50/60 Hz (AC-3) 63 kW at 220...230 V AC 50/60 Hz (AC-3) 40 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"18...24 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.32 mOhm - Ith 315 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 35 N.m","Compatibility code":"LC1F","Inrush power in VA":"970 VA, 60 Hz cos phi 0.3 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 60 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-4 AC-1","Contactor application":"Resistive load Motor control","Mechanical durability":"10 Mcycles","Associated fuse rating":"315 A gG at 250 A aM at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm Power circuit: lugs-ring terminals 1 cable(s) 185 mm² Power circuit: connector 1 cable(s) 185 mm² Power circuit: bolted connection","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"1800 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"32 W AC-1 16 W AC-3","[Uc] control circuit voltage":"48 V AC 60 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 50/60 Hz (at 55 °C) Drop-out: 0.35...0.55 Uc 50/60 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"315 A (at 225 A (at <55 °C) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"66 VA, 60 Hz cos phi 0.3 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1800 A 40 °C - 10 s 1000 A 40 °C - 30 s 850 A 40 °C - 1 min 560 A 40 °C - 3 min 440 A 40 °C - 10 min","[Ith] conventional free air thermal current":"315 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/df3d260ef87179c7ea5153b4fc1eb12c.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F225E6/tesys-f-contactor-3p-3-no-ac3-440-v-225-a-coil-48-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F225E6/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does LC1F225E6 carry?","answer":"The contactor is certified to IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1 (cite:). Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C (cite:). Overvoltage category III (cite:). Protective treatment TH for tropicalized environments (cite:)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F225E6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F225E6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}