{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F225G5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F225G5","canonicalUrl":"https://aoctrl.com/schneider/LC1F225G5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F225G5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F225G5, 3-pole contactor, 315 A AC-3, 110 kW at 400 V, 127-132 V AC 50 Hz coil.","salesMarkdown":"Its headline rating is 315 A at ≤440 V in AC-3 duty, which translates to 110 kW motor power at 380–400 V AC — the figure that decides whether it drives your pump, conveyor, or compressor. The control circuit is a 127–132 V AC 50 Hz coil, with an operational voltage range of 0.85–1.1 Uc and a drop-out range of 0.35–0.55 Uc. That means the coil holds in reliably down to about 108 V and drops out cleanly below about 46 V — important for brownout ride-through or undervoltage release coordination. The inrush power is 805 VA at 50 Hz, and hold-in consumption drops to 55 VA, so the control transformer must be sized for the inrush peak, not the steady-state draw. The rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C, so it's suitable for 690 V line-to-line systems with adequate clearance. If a direct drop-in replacement from the TeSys F family exists, it would need to be verified against the specific mounting footprint, coil voltage, and power ratings. The LC1F225G5 uses a plate-mounting support and bar-type power connections — any substitute must match the 168.5 mm width and 181 mm depth for panel layout compatibility. The contactor is designed and tested to IEC 60947-1, EN 60947-4-1, IEC 60947-4-1, EN 60947-1, and JIS C8201-4-1. These standards cover low-voltage switchgear and controlgear — specifically part 4-1 for contactors and motor-starters. The protective treatment is TH, which indicates tropicalized humidity protection — suitable for warm, humid environments without condensation. Overvoltage category III means it is rated for fixed-installation distribution-level transients, not just downstream equipment. The associated fuse rating is 315 A gG or 250 A aM at ≤440 V — use these for short-circuit coordination rather than relying on the contactor's own breaking capacity alone. ## Integration notes Mounting is plate-based, not DIN rail — plan for bolt-down installation on a backplate or chassis. Power circuit connections use bar-type terminals accepting 32 x 4 mm bars or lugs up to 185 mm². Tightening torque for the power circuit is 309.8 lbf·in (35 N·m) — a torque wrench is required; under-torquing creates hot spots at full load. Control circuit terminals are screw-clamp, accepting 1–4 mm² flexible or solid wire, torqued to 10.6 lbf·in (1.2 N·m). Heat dissipation is 18–24 W total, with 32 W per pole in AC-1 and 16 W per pole in AC-3. For a panel with multiple contactors side by side, derating or forced ventilation may be needed above 40 °C ambient. The average impedance per pole is 0.32 mΩ at 315 A 50 Hz, which translates to about 0.1 V drop per pole at rated current — negligible for voltage drop calculations but relevant for heat buildup in dense cabinets.","metaTitle":"Schneider Electric LC1F225G5 TeSys F Contactor, 315 A AC-3,","metaDescription":"Schneider Electric LC1F225G5 TeSys F contactor, 315 A rated operational current (AC-3), 110 kW motor power at 400 V. End-of-life phase. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"7.1 in (181 mm)","Range":"TeSys","Width":"6.6 in (168.5 mm)","Height":"7.8 in (197 mm)","Category":"22336-CTR,F-LINE,AC,OPEN,NONREV","Standards":"IEC 60947-1 EN 60947-4-1 IEC 60947-4-1 EN 60947-1 JIS C8201-4-1","Motor power kW":"110 kW at 380...400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 110 kW at 440 V AC 50/60 Hz (AC-3) 129 kW at 500 V AC 50/60 Hz (AC-3) 129 kW at 660...690 V AC 50/60 Hz (AC-3) 63 kW at 220...230 V AC 50/60 Hz (AC-3) 40 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"20...35 ms closing 7...15 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"18...24 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.32 mOhm - Ith 315 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 309.8 lbf.in (35 N.m)","Compatibility code":"LC1F","Inrush power in VA":"805 VA, 50 Hz 0.3 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Control circuit type":"AC 50 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-1 AC-4","Contactor application":"Motor control Resistive load","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"315 A gG at 250 A aM at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bar 2 32 x 4 mm Power circuit lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit connector 1 0.3 in² (185 mm²) Power circuit bolted connection","IP degree of protection":"IP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106","Rated breaking capacity":"1800 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","Power dissipation per pole":"32 W AC-1 16 W AC-3","[Uc] control circuit voltage":"127...132 V AC 50 Hz","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"315 A (at 225 A (at <131 °F (55 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"55 VA, 50 Hz 0.3 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1800 A 104 °F (40 °C) - 10 s 1000 A 104 °F (40 °C) - 30 s 850 A 104 °F (40 °C) - 1 min 560 A 104 °F (40 °C) - 3 min 440 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"315 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a79a0473b4c58dd7375b8d0b66f606ce.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1F225G5/tesys-f-contactor-3p-3-no-ac3-440-v-225-a-coil-127-132-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F225G5/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1F225G5?","answer":"No official successor order code is listed. Any replacement must match the 315 A AC-3 rating, 127–132 V AC 50 Hz coil, plate-mounting footprint (168.5 mm wide, 181 mm deep), and bar-type power connections. A parametric search within the TeSys F family for the same coil voltage and AC-3 current rating is the practical path, but physical fit must be verified against the existing panel layout."},{"question":"What are the key specifications of LC1F225G5?","answer":"The LC1F225G5 is a 3-pole contactor rated 315 A at ≤440 V AC-3, 110 kW motor power at 400 V, with a 127–132 V AC 50 Hz control coil. It complies with IEC 60947-4-1, has a rated breaking capacity of 1800 A, and mechanical durability of 10 million cycles."},{"question":"Where can I buy LC1F225G5?","answer":"The LC1F225G5 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and delivery estimate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F225G5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F225G5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}