{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F2600P7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F2600P7","canonicalUrl":"https://aoctrl.com/schneider/LC1F2600P7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F2600P7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F2600P7, 3-pole contactor, 2600 A AC-1, 230 V AC 40-400 Hz coil, plate mount, EOL lifecycle.","salesMarkdown":"The 230 V AC coil draws 2500 VA inrush and 45 VA hold-in at 20 °C. It's a plate-mount part, sized for enclosure or panel backplate integration, with power circuit connections via busbar (up to 100 x 10 mm cross-section). ## Lifecycle reality — EOL hot This part carries an EOL hot lifecycle status. That means Schneider has ended production; the last-time-buy window is closed. The 2600 A AC-1 rating governs the continuous current-carrying capacity for resistive loads at up to 60 °C ambient. That's the number that decides the busbar and cable sizing. The short-time withstand current (Icw) is 12 kA for 10 seconds, 9 kA for 30 seconds, stepping down to 4 kA for 10 minutes; these are the thermal and dynamic withstand limits for selective coordination schemes where the contactor must ride through a downstream fault. Rated insulation voltage is 1000 V per both IEC and UL 60947-4-1, and the rated impulse withstand voltage is 8 kV — overvoltage category III. That means it's suitable for fixed-installation distribution boards and industrial panels where transient overvoltages are expected. The operating altitude of 3000 m without derating covers most high-altitude plant sites without needing to reduce current. The coil operates on AC control voltage at 40 to 400 Hz, with a pickup range of 0.85 to 1.1 Uc and dropout between 0.3 and 0.5 Uc at 55 °C. Closing time is 40 to 80 ms; opening time is 100 to 200 ms. That's typical for a large-frame contactor — the opening delay is mechanical, not electrical, and matters for arc extinction timing in resistive switching. The IP20 front face with shrouds (per IEC 60529 and VDE 0106) means finger-safe from the front once the shrouds are installed, but the back and sides are not touch-protected — standard for a plate-mount contactor inside a locked enclosure. The TH protective treatment indicates the part is tropicalised for humid or corrosive environments. The LC1F2600P7 carries compliance with EN 60947-4-1, IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. That's the full suite of global contactor standards — accepted in European, North American, and Japanese installations. The associated fuse rating is 2500 A gG at up to 440 V for short-circuit protection coordination.","metaTitle":"TeSys F LC1F2600P7 Contactor, 2600 A AC-1, 230 V AC Coil, EO","metaDescription":"Schneider Electric TeSys F LC1F2600P7 contactor, 2600 A AC-1, 230 V AC coil, 3-pole. EOL lifecycle. Sourced to order against RFQ. Complies with EN/IEC/UL 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"251 mm","Range":"TeSys","Width":"519 mm","Height":"382 mm","Standards":"EN 60947-4-1 IEC 60947-1 IEC 60947-4-1 EN 60947-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Operating time":"40...80 ms closing 100...200 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"40 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 2600 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 58 N.m","Compatibility code":"LC1F","Inrush power in VA":"2500 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Associated fuse rating":"2500 A gG at <= 440 V","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 3 cable(s) - busbar cross section: 100 x 10 mm","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"3900 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"250 W AC-1","[Uc] control circuit voltage":"230 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1000 V conforming to UL 60947-4-1","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"2600 A (at <60 °C) AC AC-1","[Ue] rated operational voltage":"<= 1000 V AC 50/60 Hz","Hold-in power consumption in VA":"45 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"12000 A 40 °C - 10 s 9000 A 40 °C - 30 s 7000 A 40 °C - 1 min 6000 A 40 °C - 3 min 4000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"2600 A (at 60 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a27d576e6d01b2f43a4dec9e54c76951.pdf","sourceUrl":"https://www.se.com/th/en/product/LC1F2600P7/contactor-tesys-f-3p3no-ac1-1000v-ac-2600-a-coil-230v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F2600P7/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F2600P7?","answer":"We source the LC1F2600P7 to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — send an RFQ for a firm posture."},{"question":"What is the rated operational current of LC1F2600P7?","answer":"The rated operational current (Ie) is 2600 A in AC-1 utilisation category (resistive load) at up to 60 °C ambient. That's the continuous current rating for switching resistive loads."},{"question":"What standards does LC1F2600P7 comply with?","answer":"It complies with EN 60947-4-1, IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. The rated insulation voltage is 1000 V per both IEC and UL standards."},{"question":"What is the control voltage for LC1F2600P7?","answer":"The control circuit voltage (Uc) is 230 V AC at 40 to 400 Hz. The coil draws 2500 VA inrush and 45 VA hold-in at 20 °C. Pickup range is 0.85 to 1.1 Uc; dropout is 0.3 to 0.5 Uc at 55 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F2600P7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F2600P7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}