{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F2600UD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F2600UD","canonicalUrl":"https://aoctrl.com/schneider/LC1F2600UD","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F2600UD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F2600UD, 3-pole contactor, 2600 A rated operational current (AC-1), 250 V DC control circuit, plate mount, EOL phase-out.","salesMarkdown":"## What the 2600 A AC-1 rating means for your load For motor duty (AC-3) you'd need a different frame or a derating table. The 2600 A figure governs continuous current at <60 °C; above that, thermal derating applies. Control is 250 V DC, with a hold-in power of 18 W at 20 °C and an inrush of 2600 W at the same temperature — the coil driver must handle that cold-start surge. ## Lifecycle reality — EOL phase-out This part is flagged as end-of-life hot (EOL). ## Breaking capacity and short-time withstand — selectivity planning Rated breaking capacity is 3900 A per IEC 60947-4-1, and the short-time withstand current (Icw) is 12 kA for 10 s at 40 °C, stepping down to 4 kA for 10 min. That gives you the numbers for selective coordination with upstream fuses or breakers. The associated fuse recommendation is 2500 A gG at ≤440 V — a useful starting point for the protection scheme. ## Standards and approvals — what the certification covers The contactor carries compliance with EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. That's the full suite for industrial control equipment — the IEC/EN/UL/CSA trifecta covers most global panel builds. Rated insulation voltage (Ui) is 1000 V per both IEC and UL standards. Impulse withstand (Uimp) is 8 kV, overvoltage category III, so it's suited for fixed-installation distribution boards. ## Mounting and integration — plate mount, not DIN rail Mounting is plate-only (no DIN-rail clip on this frame). The dimensions are 519 mm wide, 382 mm high, 251 mm deep — it's a large-frame contactor. Power connections are via bar, accepting up to three cables per pole with a busbar cross-section of 100 x 10 mm. Control circuit terminals are screw clamp, accepting 1 to 4 mm² flexible or solid. Torque values: 1.2 N·m for control, 58 N·m for power — the latter requires a torque wrench.","metaTitle":"Schneider Electric LC1F2600UD TeSys F Contactor, 2600 A AC-1","metaDescription":"Schneider Electric LC1F2600UD TeSys F contactor, 2600 A AC-1, 250 V DC coil, 3-pole. EOL phase-out. Sourced to order. Standards: EN/IEC/UL 60947-4-1. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"251 mm","Range":"TeSys","Width":"519 mm","Height":"382 mm","Standards":"EN 60947-4-1 IEC 60947-1 IEC 60947-4-1 EN 60947-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Operating time":"60...70 ms closing 40...50 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"40 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 2600 A 50 Hz","Device short name":"LC1F","Inrush power in W":"2600 W (at 20 °C)","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 58 N.m","Compatibility code":"LC1F","Operating altitude":"3000 m without derating","Control circuit type":"DC standard","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Associated fuse rating":"2500 A gG at <= 440 V","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 3 cable(s) - busbar cross section: 100 x 10 mm","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"3900 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"250 W AC-1","[Uc] control circuit voltage":"250 V DC","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1000 V conforming to UL 60947-4-1","Control circuit voltage limits":"Operational: 0.85...1.1 Uc (at 55 °C) Drop-out: 0.2...0.35 Uc (at 55 °C)","Hold-in power consumption in W":"18 W at 20 °C","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"2600 A (at <60 °C) AC AC-1","[Ue] rated operational voltage":"<= 1000 V AC 50/60 Hz","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"12000 A 40 °C - 10 s 9000 A 40 °C - 30 s 7000 A 40 °C - 1 min 6000 A 40 °C - 3 min 4000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"2600 A (at 60 °C)","Permissible ambient air temperature around the device":"-40...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0b8348e01662a8250800079a7dc36c15.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1F2600UD/tesys-f-contactor-3p-3-no-ac1-1000-v-ac-2600-a-coil-250-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F2600UD/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for LC1F2600UD?","answer":"The contactor is certified to EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Rated insulation voltage is 1000 V per both IEC and UL. Protective treatment is TH (tropical heat)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F2600UD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F2600UD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}