{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F2654P7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F2654P7","canonicalUrl":"https://aoctrl.com/schneider/LC1F2654P7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F2654P7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F2654P7, 4-pole contactor, 350 A AC-1, 230 V AC 40-400 Hz coil, plate mount.","salesMarkdown":"## Heavy-Duty Resistive Load Switching The Schneider Electric LC1F2654P7 is a 4-pole contactor from the TeSys F range, rated for 350 A in AC-1 utilisation category at ≤ 440 V. That AC-1 rating means it is built for resistive loads — heaters, ovens, lighting banks — where the current waveform stays sinusoidal and inrush is minimal. The 4 NO power poles give you four independently switched phases or a combined three-phase plus neutral break, common in panel builds for industrial ovens or large resistive banks. Coil is 230 V AC, 40-400 Hz, drawing 650 VA inrush and 10 VA hold-in. Drop-out voltage band is 0.15-0.2 Uc. ## Rated for the Panel Environment Mounts to a plate (not DIN rail), so plan for a drilled backplate or sub-panel in your enclosure. Dimensions are 203 mm high, 244.5 mm wide, 213 mm deep — a substantial footprint that needs clearance for the power busbars (up to 32 x 4 mm bar or 240 mm² cable lugs). Tightening torque on the power circuit is 35 N.m, which is high; a torque wrench is mandatory for the M10-class bolted connections. IP20 front face with shrouds per IEC 60529 and VDE 0106 — finger-safe from the front once shrouded, but the rear terminals are live. Install in a locked cabinet or behind a panel door. The TH protective treatment adds a conformal coating for humid or mildly corrosive atmospheres, though not a full washdown rating. ## Thermal and Coordination Data Heat dissipation is 8 W total, 37 W per pole in AC-1 duty. That 37 W per pole is the figure to use for enclosure thermal calculations — at 350 A, the pole resistance (0.3 mOhm average at 50 Hz) generates significant heat. The associated fuse recommendation is 315 A aM or 400 A gG at ≤ 440 V, giving you a coordination window for type-2 coordination with motor-protective breakers or fuses. Mechanical durability is 10 million cycles, maximum operating rate 2400 cycles per hour at 55 °C.","metaTitle":"TeSys F LC1F2654P7 Contactor, 350 A AC-1, 4 NO, 230 V AC Coi","metaDescription":"Schneider Electric TeSys F LC1F2654P7 contactor. 350 A rated operational current (AC-1), 4 NO poles, 230 V AC 40-400 Hz coil. IEC 60947 compliant. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"213 mm","Range":"TeSys","Width":"244.5 mm","Height":"203 mm","Standards":"IEC 60947-1 JIS C8201-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-4-1","Operating time":"40...65 ms closing 100...170 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"8 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.3 mOhm - Ith 350 A 50 Hz","Device short name":"LC1F","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 35 N.m","Compatibility code":"LC1F","Inrush power in VA":"650 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"315 A aM at 400 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm Power circuit: lugs-ring terminals 1 cable(s) 240 mm² Power circuit: connector 1 cable(s) 240 mm² Power circuit: bolted connection","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"2120 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"37 W AC-1","[Uc] control circuit voltage":"230 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.15...0.2 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"350 A (at <40 °C) at <= 440 V AC AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"10 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"2200 A 40 °C - 10 s 1230 A 40 °C - 30 s 950 A 40 °C - 1 min 620 A 40 °C - 3 min 480 A 40 °C - 10 min","[Ith] conventional free air thermal current":"350 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2450bdbd15d7db4dffa44f191a947c50.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC1F2654P7/tesys-f-contactor-4p-4-no-ac1-440-v-350-a-coil-230-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F2654P7/alternatives.json"},"ai":{"faq":[{"question":"What compliance standards does the LC1F2654P7 meet?","answer":"It is certified to IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1, impulse withstand 8 kV, overvoltage category III."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F2654P7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F2654P7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}