{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F330D7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F330D7","canonicalUrl":"https://aoctrl.com/schneider/LC1F330D7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F330D7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor, LC1F330D7, 3-pole, 400 A rated operational current (AC-3), 42 V AC 40-400 Hz coil, plate mount.","salesMarkdown":"The Schneider Electric LC1F330D7 is a 3-pole TeSys F contactor rated for 400 A operational current in AC-3 duty, with a 42 V AC control coil. This is a heavy-frame contactor — plate-mounted, 206 mm tall, 213 mm wide, 219 mm deep — sized for main motor circuits in industrial panels. The motor power table gives the real-world match: 160 kW at 380-400 V, 180 kW at 415 V, 200 kW at 440 V, all AC-3. For AC-4 reversing or plugging duty, the rating drops to 59 kW at 400 V — a significant derating that matters if the application involves frequent reversing or inching. The 42 V AC control coil operates across 40-400 Hz, with pickup at 85-110% of rated voltage and dropout between 35-55%. Inrush power is 650 VA at 20 °C; holding power drops to 10 VA. That's a standard AC magnet coil — verify the control transformer sizing for the inrush draw, especially if multiple contactors pull in simultaneously. Plate mounting is specified; no DIN-rail option on this frame size. Standards compliance covers IEC 60947-4-1 and EN 60947-4-1 (the contactor standard) plus IEC 60947-1 and EN 60947-1 (general rules). Overvoltage category III, rated insulation voltage 1000 V per IEC 60947-4-1. The rated breaking capacity is 2640 A per the same standard — that's the contactor's ability to interrupt fault currents, not the short-circuit withstand of the associated fuse. ## Integration Notes Power circuit connections accept lugs or ring terminals for a single 240 mm² cable, or a busbar up to 30 x 5 mm. Control circuit wiring uses screw clamp terminals accepting 1-4 mm² flexible or solid. Tightening torque is 35 N.m on the power circuit and 1.2 N.m on the control circuit — a torque wrench is advisable on the main lugs to avoid hot connections at 400 A. Heat dissipation is 8 W total for the coil, plus 44 W per pole in AC-1 or 31 W per pole in AC-3. At full AC-3 load that's about 101 W total — account for this in panel thermal calculations, especially in a sealed enclosure.","metaTitle":"Schneider LC1F330D7 TeSys F Contactor, 400A AC-3, 42V Coil","metaDescription":"Schneider Electric LC1F330D7 TeSys F contactor. 400A rated operational current (AC-3), 42V AC coil. EOL lifecycle stage. Sourced to order. Request quote for availability and pricin","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"219 mm","Range":"TeSys","Width":"213 mm","Height":"206 mm","Standards":"JIS C8201-4-1 EN 60947-4-1 IEC 60947-4-1 EN 60947-1 IEC 60947-1","Motor power kW":"160 kW at 380...400 V AC 50/60 Hz (AC-3) 180 kW at 415 V AC 50/60 Hz (AC-3) 200 kW at 440 V AC 50/60 Hz (AC-3) 200 kW at 500 V AC 50/60 Hz (AC-3) 220 kW at 660...690 V AC 50/60 Hz (AC-3) 160 kW at 1000 V AC 50/60 Hz (AC-3) 100 kW at 220...230 V AC 50/60 Hz (AC-3) 59 kW at 400 V AC 50/60 Hz (AC-4)","Operating time":"40...65 ms closing 100...170 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"8 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.28 mOhm - Ith 400 A 50 Hz","Device short name":"LC1F","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 35 N.m","Compatibility code":"LC1F","Inrush power in VA":"650 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-1","Contactor application":"Motor control Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"400 A aM at 500 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: lugs-ring terminals 1 cable(s) 240 mm² Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"2640 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"44 W AC-1 31 W AC-3","[Uc] control circuit voltage":"42 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.35...0.55 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"400 A (at 330 A (at <55 °C) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"10 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"2650 A 40 °C - 10 s 1800 A 40 °C - 30 s 1300 A 40 °C - 1 min 900 A 40 °C - 3 min 750 A 40 °C - 10 min","[Ith] conventional free air thermal current":"400 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/38c935ab5eb19f558bca9f73af3a9675.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1F330D7/tesys-f-contactor-3p-3-no-ac3-440-v-330-a-coil-42-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F330D7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC1F330D7?","answer":"The LC1F330D7 is a 3-pole contactor rated 400 A operational current in AC-3 (motor switching) at ≤ 440 V, with a 42 V AC control coil. It switches motor loads up to 160 kW at 380-400 V AC-3. Mechanical durability is 10 million cycles."},{"question":"What is the LC1F330D7 used for?","answer":"This contactor is used for motor control (AC-3 category) and resistive load switching (AC-1 category) in industrial panels. Typical applications include conveyors, pumps, compressors, and other three-phase motor loads within its power rating."},{"question":"Where can I buy the LC1F330D7?","answer":"The LC1F330D7 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time. Submit an RFQ for a current sourcing position."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F330D7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F330D7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}