{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F4002ED","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F4002ED","canonicalUrl":"https://aoctrl.com/schneider/LC1F4002ED","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F4002ED","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F4002ED contactor, 2-pole, 500 A AC-1 at ≤440 V, 48 V DC coil, plate mount, EOL hot lifecycle.","salesMarkdown":"The Schneider Electric LC1F4002ED is a TeSys F contactor rated for 500 A in AC-1 utilisation category at ≤440 V and 40 °C, with a 48 V DC standard control coil. This is a 2-pole normally-open contactor built for resistive load switching — think large heating banks, furnace elements, or DC power supplies where the load current is non-inductive and the contactor sees steady-state current rather than motor inrush. Mounts to a plate (not DIN rail), so plan for a sub-panel or backplate with bolted connections. Power circuit uses bar connections (30 x 5 mm) or ring terminals up to 150 mm²; control circuit uses screw clamp terminals accepting 1–4 mm² flexible or solid wire. Tightening torque is 35 N.m on the power side and 1.2 N.m on the control side — a torque wrench is expected for the main lugs. Rated insulation voltage is 1000 V per IEC 60947-4-1, with a rated breaking capacity of 3200 A conforming to the same standard. The contactor dissipates 6 W holding power and 65 W per pole under AC-1 load — factor that into your enclosure thermal budget. Associated fuse protection: 400 A aM or 500 A gG at ≤440 V.","metaTitle":"Schneider LC1F4002ED TeSys F Contactor, 500 A AC-1, 48 V DC","metaDescription":"Schneider LC1F4002ED TeSys F contactor, 500 A rated operational current at 40 °C AC-1, 48 V DC coil. EOL hot phase. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"8.6 in (219 mm)","Range":"TeSys","Width":"8.4 in (213 mm)","Height":"8.1 in (206 mm)","Category":"22336-CTR,F-LINE,AC,OPEN,NONREV","Standards":"EN 60947-4-1 EN 60947-1 JIS C8201-4-1 IEC 60947-4-1 IEC 60947-1","Operating time":"50...60 ms closing 45...60 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"6 W","Mounting Support":"Plate","Range of Product":"TeSys F","Average impedance":"0.26 mOhm - Ith 500 A 50 Hz","Device short name":"LC1F","Inrush power in W":"1000 W 68 °F (20 °C))","Poles description":"2P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 309.8 lbf.in (35 N.m)","Compatibility code":"LC1F","Operating altitude":"9842.52 ft (3000 m) without derating","Control circuit type":"DC standard","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"400 A aM at 500 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bar 2 30 x 5 mm Power circuit lugs-ring terminals 2 0.2 in² (150 mm²) Power circuit bolted connection","IP degree of protection":"IP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106","Rated breaking capacity":"3200 A conforming to IEC 60947-4-1","Product or Component Type":"Contactor","Power dissipation per pole":"65 W AC-1","[Uc] control circuit voltage":"48 V DC","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.2...0.35 Uc 131 °F (55 °C))","Hold-in power consumption in W":"6 W 68 °F (20 °C)","Power Pole Contact Composition":"2 NO","[Ie] rated operational current":"500 A (at <104 °F (40 °C)) at <= 440 V AC AC-1","[Ue] rated operational voltage":"<= 460 V DC","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3600 A 104 °F (40 °C) - 10 s 2400 A 104 °F (40 °C) - 30 s 1700 A 104 °F (40 °C) - 1 min 1200 A 104 °F (40 °C) - 3 min 1000 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"500 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ec49a8dd74cd06c95c7ab8bd220ba50f.pdf","sourceUrl":"https://www.se.com/th/en/product/LC1F4002ED/tesys-f-contactor-2p-2-no-ac1-440-v-500-a-coil-48-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F4002ED/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1F4002ED in the TeSys F family?","answer":"No official successor order code is listed for the LC1F4002ED. A parametric alternative within the TeSys F range would need to match the 500 A AC-1 rating, 48 V DC coil, and 2-pole NO configuration — verify mounting and connection compatibility with your panel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F4002ED","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F4002ED when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}